Product Details:
Payment & Shipping Terms:
|
The 1783-US5T is the five-port copper member of the Stratix 2000 unmanaged family - Series B in current production, with the 1783-US5TG as its Gigabit twin. Five Fast Ethernet RJ45 ports, DIN-rail mounting, 24 V power from either dc or ac, and no configuration to lose after a power cycle.
Unmanaged is a deliberate choice, not a limitation. On a machine cell where the only requirement is to fan out an EtherNet/IP connection from one controller to several devices, an unmanaged switch removes the failure modes that managed devices introduce: no IP address to conflict with the plant scheme, no firmware to match, no configuration file to restore after a module swap. The switch is a spare part, not an asset to be administered.
The same family covers the other port counts a panel usually needs - 1783-US8T for eight copper ports, 1783-US4T1F for four copper plus one multimode fiber, and the US6T2F/US8TG2GX variants where fiber or Gigabit segments are required.
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1783-US5T
|
|
Mounting
|
DIN rail, open-style enclosure |
|
Network
|
Ethernet
|
|
Operating Temperature
|
-10...60 C (14...140 F) |
|
Port
|
5
|
|
RJ45 Ports
|
5 FE (Fast Ethernet) copper ports |
|
Standard
|
CCC,CE,CUL,KC,RCM,UL
|
|
Sub Brand
|
Stratix 2000
|
|
Type
|
Unmanaged, Layer 2, store-and-forward |
|
UNSPSC
|
43222612
|
Power input is 24 V nominal with a wide window: 12...48 V dc or 18...30 V ac at 50/60 Hz, SELV source required. Maximum power consumption is 3.4 W, nominal current 180 mA at 24 V dc (360 mA on ac), maximum inrush 1.85 A. Because the same part runs on ac or dc, a panel that still has a 24 V ac control transformer can use this switch without adding a dc supply.
Wiring: dc power terminals accept 0.25...4 mm² (24...12 AWG) twisted-pair copper rated for 86 °C above surrounding ambient, with 0.50...0.56 N·m (4.5...5.0 in·lb) terminal torque. The ground connection uses 2.5 mm² (14 AWG) copper with a ring terminal at 0.91 N·m (8.05 in·lb) maximum. Enclosure is open-style, so the switch must sit inside a rated enclosure.
Environment: operating -10...60 °C (14...140 °F) for the copper-only US5T and US8T, extending to -40...75 °C on the fiber and Gigabit variants; nonoperating -40...85 °C. North American temperature code T4, ATEX code T4. Ethernet connections use RJ45 per IEC 60603-7 with Category 5e or better cable per TIA 568-B.1.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
Typical use: one uplink from a CompactLogix or ControlLogix Ethernet port, four downstream devices - a drive, a remote I/O adapter, an HMI and a spare for commissioning. At 3.4 W the switch adds negligible heat to a sealed enclosure, and the 12...48 V dc window means it can hang on the same 24 V bus as the I/O without a separate supply.
One practical note on ordering: the letter after the port count matters. 1783-US5T is five Fast Ethernet copper ports; 1783-US5TG is five Gigabit ports; 1783-US4T1F is four copper plus one multimode fiber. A Gigabit uplink between cabinets and Fast Ethernet to the devices is a normal arrangement, and mixing the two part numbers in one panel is perfectly acceptable.
Specifications on this page are from the Stratix Ethernet Device Specifications technical data, publication 1783-TD002D-EN-P (May 2023). Note that this publication superseded 1783-TD001.
Same-family catalog numbers: 1783-US03T01F, 1783-US8T. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1783 family.
Managed Stratix switches, taps and SFP transceivers are grouped on our Allen-Bradley Networks 1783 category page. Quotes: sales@plc-vip.com.