Product Details:
Payment & Shipping Terms:
|
The 1783-ETAP1F is an embedded switch - Rockwell calls it a tap - that sits between an EtherNet/IP device and the network, providing two copper RJ45 ports plus one 100 Mbps multimode fiber LC port. Its purpose is topology, not traffic: it lets a device join a linear or device-level ring (DLR) network without adding a managed switch and without a second IP address for the infrastructure.
That distinction matters on a machine. A tap is transparent to the device it serves - the device keeps its own IP address, and the tap carries traffic for both directions of the ring. Install one at each station on a conveyor or a long line, and a single fiber break no longer takes the segment down: the ring heals and the fault is reported.
The fiber port is single-port 100 Mbps multimode with an LC connector, which is what allows runs between cabinets that are too long or too noisy for copper. Twin fiber variants (1783-ETAP2F) and the all-copper 1783-ETAP cover the other topologies.
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1783-ETAP1F
|
|
Data Transfer Rate
|
2 Copper - 10/100 Mbps, 1 Fiber - 100 Mbps
|
|
Enclosure
|
IP20, DIN rail, 104.9 x 35.05 mm front profile |
|
Height
|
132mm, 5.16in
|
|
Interface
|
2 copper RJ45 (10/100) + 1 fiber LC multimode (100 Mbps) |
|
Operating Temperature
|
-25...70 C (-13...158 F) |
|
Power Supply
|
24V DC (20.4...27.6V DC), Class 2/SELV, 200 mA max, 4.8 W max |
|
Standard
|
CCC,CE,CUL,KC,MARINE,RCM,UL
|
|
Sub Brand
|
Stratix
|
|
Type
|
EtherNet/IP embedded switch (tap) with device-level ring support |
|
UNSPSC
|
43222610
|
|
Width
|
35mm, 1.36in
|
Power: 24 V dc nominal from a 20.4...27.6 V dc source, Class 2 or SELV, drawing 200 mA maximum. Maximum power consumption 4.8 W. DC power terminals accept one 0.33...3.3 mm² (22...12 AWG) or two 0.33...1.3 mm² (22...16 AWG) copper conductors rated 75 °C or higher, with 0.6...0.8 N·m (5...7 in·lb) terminal torque and wiring category 2 on the power ports.
Isolation is 30 V continuous, basic insulation type, between network channels and power and between network channels, type tested at 1250 V dc and 853 V ac for 60 s. Ethernet connections use RJ45 per IEC 60603-7 with Category 5e or better cable per TIA 568-B.1 or Category 5 per ISO/IEC 24702. Enclosure rating IP20; North American, ATEX and IECEx temperature code T4.
Environment: operating -25...70 °C (-13...158 °F) with 70 °C maximum surrounding air, nonoperating -40...85 °C. The front profile is 104.9 mm x 35.05 mm per the dimensional drawing, DIN-rail mounted, so several taps fit in the width of one conventional switch.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
Three rules of thumb from the device's own data: keep the fiber port for the long run between cabinets and use copper for the short hops, give each tap a 24 V feed from the same supply as the device it serves so a supply failure is local, and leave the ring's fault relay to the managed switch or the controller rather than expecting the tap to report it - the tap is a passive element in the topology.
For spares planning: the tap carries no configuration, so a failed unit is replaced with an identical part number and the ring reconverges; the device's own IP address, the ring supervisor setting and the DLR parameters live elsewhere. That is the reason taps are stocked by machine builders as consumables rather than repaired.
All values are from the Stratix Ethernet Device Specifications technical data, publication 1783-TD002D-EN-P (May 2023).
Same-family catalog numbers: 1783-ETAP, 1783-ETAP2F. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1783 family.
Other Stratix taps, switches and SFP transceivers are listed on our Allen-Bradley Networks 1783 category page. Availability: sales@plc-vip.com.