logo
Home ProductsAB CompactLogix 1769

Allen Bradley PLC 1769-OB32 / 1769OB32

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1769-OB32 / 1769OB32

China Allen Bradley PLC 1769-OB32 / 1769OB32 supplier
Allen Bradley PLC 1769-OB32 / 1769OB32 supplier Allen Bradley PLC 1769-OB32 / 1769OB32 supplier Allen Bradley PLC 1769-OB32 / 1769OB32 supplier Allen Bradley PLC 1769-OB32 / 1769OB32 supplier Allen Bradley PLC 1769-OB32 / 1769OB32 supplier Allen Bradley PLC 1769-OB32 / 1769OB32 supplier

Large Image :  Allen Bradley PLC 1769-OB32 / 1769OB32

Product Details:

Place of Origin: Made in MALAYSIA
Brand Name: Rockwell
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1769-OB32 / 1769OB32

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $296.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 20 PCS
Detailed Product Description

1769-OB32 technical data PDF download CompactLogix 1769-OB32 / 1769OB32 32-Point 24V DC Output Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC I/O

The 1769-OB32 (also written 1769OB32) is the thirty-two point 24V DC sourcing output of the Compact I/O 1769 range: two groups of sixteen, one DC common per group, 0.1 ms switching, and the highest 5.1V draw of any 1769 digital module at 300 mA.

Its one structural difference from the rest of the family is the power-supply distance rating: six modules instead of eight. A bank built around the usual eight-module rule can leave this module too far from its supply, and the symptom is not an obvious error but outputs that misbehave under load.

1769-IA16 Compact 16-point 120V AC input module IN STOCK
1769-IQ16 Compact 16-point 24V DC sink/source input module IN STOCK
1769-IQ32 Compact 32-point 24V DC sink/source input module IN STOCK
1769-OA16 Compact 16-point 120/240V AC output module IN STOCK
1769-OB16 Compact 16-point 24V DC output module IN STOCK
1769-OB32 Compact 32-point 24V DC output module IN STOCK
1769-OW16 Compact 16-point relay output module IN STOCK
1769-IF4 Compact 4-channel analog input module IN STOCK
1769-IF8 Compact 8-channel analog input module IN STOCK
1769-IF16C Compact 16-channel current input module IN STOCK
1769-OF4 Compact 4-channel analog output module IN STOCK
1769-OF8V Compact 8-channel voltage output module IN STOCK
1769-OF8C Compact 8-channel current output module IN STOCK
1769-ARM Compact address reserve module IN STOCK

Product Specifications 1769-OB32 (PDF)
 Application
 Compact I/O, 1769 bus
 Cat Num
 1769-OB32
 Brand Name
 Rockwell
 Outputs
 32 (16 points per group)
 Voltage category
 24V DC source
 Operating voltage range
 20.4…26.4V DC
 Output delay, on / off
 0.1 ms / 1.0 ms
 Current draw @ 5.1V
 300 mA
 Heat dissipation, max
 4.5 W
 Off-state leakage, max
 1.0 mA @ 26.4V DC
 On-state current, min
 1.0 mA
 On-state voltage drop, max
 1.0V DC @ 1 A
 Current per point
 0.5 A @ 60 °C; 1.0 A @ 30 °C
 Current per module
 4.0 A @ 60 °C; 8.0 A @ 30 °C
 Surge current
 2.0 A for 10 ms, repeatable every 2 s
 Isolation
 1200V AC 1 s or 1697V DC 1 s, output point to bus; 75V DC working voltage
 Slot width / weight
 1.5 slot / 450 g
 Power supply distance
 6 modules

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1769-OB32 Compact I/O 32-point 24V DC source output module, factory packaging 1769-OB32 module, front view with terminal block 1769-OB32 label detail showing catalog number

Where the module sits in a CompactLogix system

Distance rating 6. This module must sit within six modules of the bank's 1769-PA2 / PB2 / PA4 / PB4 supply. Plan the slot order around that, not around wiring convenience. Bank budget. 300 mA at 5.1V and 4.5 W is a large slice of a standard 1769 supply; two of them plus a 32-point input can exceed the rating, and the arithmetic has to be done before the panel is laid out. Two groups of sixteen. Each group has its own DC common, so the sixteen loads in each group must share a return. That halves the terminal count against two 1769-OB16 modules and saves bus connectors and panel width.

Load rules that decide the wiring

Per point and per module. 1.0 A per point and 8.0 A per module at 30 °C fall to 0.5 A and 4.0 A at 60 °C. Thirty-two points at 0.5 A each would exceed the module limit long before the per-point limit — the module figure is the binding constraint. Leakage. 1.0 mA at 26.4V DC off-state will not hold a solenoid but can hold a small relay; a 5.6 kΩ half-watt resistor across the load absorbs it. Inductive loads. A 1N4004 diode reverse-wired across each 24V DC coil is the published practice, and the only cheap way to stop repeated driver failures. Surge. 2.0 A for 10 ms, repeatable every 2 s — generous for coils, not for a capacitive or lamp load with a large inrush.

Commissioning in four checks

Count the modules between this slice and the bank supply and confirm it is six or fewer — the distance rating is lower here than on every other 1769 digital module. Add this module's 300 mA to the bank's 5.1V total and check the supply rating before energising the bank. Recompute per-point current against the cabinet's real internal temperature, and check the module total as well as the per-point figure. Fit a 1N4004 across every 24V DC coil and torque terminals at 0.68 N·m (6 lb·in) with 22…14 AWG solid or 22…16 AWG stranded copper rated 90 °C.

Substituting or replacing a 1769-OB32

1769-OB16 — sixteen points, 200 mA, 2.11 W, eight-module distance rating; two of them restore the distance margin at the cost of slots. 1769-OB32T — terminated version, 220 mA, 0.5 / 4.0 ms delays, 230 g, 1746-N3 connector. 1769-OV32T — the sinking (24V DC sink) counterpart for loads returning to +DC. 1769-OB16P — protected output when short-circuit robustness matters more than the 0.1 ms switching.

Which Compact I/O DC output to specify

1769-OB32 — 32 sourcing points in two groups of sixteen, 300 mA, 4.5 W. 1769-OB16 — 16 points, 200 mA, 2.11 W, eight-module distance rating. 1769-OB32T — one slot, 220 mA, 230 g, terminated connector, slower 0.5 / 4.0 ms. 1769-OV32T — the sinking counterpart for loads returning to +DC. Where the bank has little spare 5.1V current, two 1769-OB16 modules cost 100 mA more than one 1769-OB32 but restore the eight-module distance margin.

FAQ — 1769-OB32

How many outputs does 1769-OB32 have?

Thirty-two, in two groups of sixteen, each group with its own DC common, switching the +DC rail (sourcing).

What is the power-supply distance rating of 1769-OB32?

Six modules, against eight for the other 1769 digital modules. That is the number to plan slot order around.

What does 1769-OB32 draw from the backplane?

300 mA at 5.1V with 4.5 W maximum heat dissipation — the highest 5.1V draw in the 1769 digital range, one and a half slots, 450 g.

How much current can 1769-OB32 switch?

1.0 A per point and 8.0 A per module at 30 °C; 0.5 A per point and 4.0 A per module at 60 °C. The module total is usually the binding limit.

What field voltage does 1769-OB32 require?

20.4…26.4V DC, with 0.1 ms on and 1.0 ms off switching and 1.0V DC maximum drop at 1 A.

Why does a 1769-OB32 output chatter or fail repeatedly?

Check the inductive load first: a 24V DC coil without a reverse-wired 1N4004 diode subjects the driver to repeated transients. Then check the bank supply current and the distance rating.

What is the difference between 1769-OB32 and 1769-OB32T?

1769-OB32 is the standard 1.5-slot module, 300 mA, 0.1 / 1.0 ms, 450 g. 1769-OB32T is the terminated version: one slot, 220 mA, 0.5 / 4.0 ms, 230 g, using a 1746-N3 connector.


Data sources. Technical values on this page come from Rockwell publication 1769-TD006 (1769 Compact I/O Modules Specifications) and 1769-SG001 (CompactLogix and Compact GuardLogix Systems Selection Guide), both current Rockwell Automation documents. Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956