Product Details:
Payment & Shipping Terms:
|
The 1734-EPAC is the AC member of the expansion supply pair: 85...264V AC in, 1.3 A of POINTBus at 5.2V DC out, and a fresh AC field power segment for the modules to its right.
It exists for panels where the field devices are 120V AC pushbuttons, solenoids or contactors and there is no 24V DC bus worth running just to feed the POINT I/O slices.
| 1734-AENT | EtherNet/IP adapter, 10/100 Mbit, 63 modules, 1.0 A POINTBus | IN STOCK |
| 1734-ADN | DeviceNet adapter, 125/250/500 kbit, 63 modules | IN STOCK |
| 1734-ADNX | DeviceNet adapter with Subnet scanner, node 0 on the subnet | IN STOCK |
| 1734-ACNR | ControlNet adapter, redundant coax A/B, node 01...99 | IN STOCK |
| 1734-APB | PROFIBUS DP adapter, 63 modules on one DP node | IN STOCK |
| 1734-PDN | DeviceNet communication interface, 24V DC 400 mA, 1.3 A POINTBus | IN STOCK |
| 1734-EP24DC | 24V DC expansion power supply, 1.3 A POINTBus at 19.2...28.8V input | IN STOCK |
| 1734-EPAC | 120/240V AC expansion power supply, 1.3 A POINTBus, 3250V DC isolation | IN STOCK |
| 1734-FPD | Field potential distributor, breaks the field power bus, no current draw | IN STOCK |
| 1734-ARM | Address reserve module, 75 mA POINTBus, keeps a slot addressed | IN STOCK |
Input voltage rating |
120/240V AC nominal, 50...60 Hz, 85...264V AC range |
POINTBus output, horizontal mounting |
1.3 A @ 5.2V DC |
POINTBus output, vertical mounting |
1.0 A @ 5.2V DC |
I/O module capacity |
12 typical, 4...17 depending on current, total not exceeding 1.3 A |
Field side power requirement |
120V AC at 200 mA max; 240V AC at 100 mA max |
Inrush current, max |
2 A for 6 ms |
Power consumption, max |
15.1 W @ 264V AC |
Power dissipation, max |
8.4 W @ 264V AC |
Thermal dissipation, max |
28.7 BTU/hr @ 264V AC |
Isolation voltage |
264V continuous, tested at 3250V DC for 60 s |
Field power bus |
120/240V AC nominal, 85...264V AC, 10 A max |
Overvoltage protection |
MOV and fuse |
Module location |
Between I/O modules, breaks the field power bus |
Dimensions, HxWxD |
76.2 x 25.4 x 133.4 mm |
Weight, approx |
182 g |
Wire size |
0.34...2.5 mm2 (22...14 AWG), 75 deg C or greater |
Terminal base screw torque |
0.8 Nm (7 lb-in) |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN017 (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The POINTBus output is 1.3 A on horizontal DIN rail and 1.0 A when the assembly is mounted vertically - convection cooling sets the limit, not the converter. Twelve modules is the typical count; 4 to 17 is the range, capped by the 1.3 A total.
264V continuous, tested at 3250V DC for 60 s. Compare the 2600V DC / 50V rating on the 1734-EP24DC and 1734-PDN: the AC supply is built for mains potential on the field terminals, and the parts are not interchangeable on that basis.
Only the 1734 adapter class products: 1734-ADN, 1734-ADNX, 1734-APB, 1734-ACNR and 1734-AENT. Rockwell states explicitly that the EPAC must not be used with the 1734-PDN or with POINTBlock modules. Terminal wiring is 6/7 L1, 4/5 L2/N, 2/3 protective earth.
15.1 W consumption and 8.4 W dissipation at 264V AC, 28.7 BTU/hr - nearly three times the heat of the DC version. Two EPAC supplies in a compact cabinet add 16.8 W of internal heat before any field load, and MOV plus fuse protection means a mains transient is taken at the module, not upstream.
What input voltage does 1734-EPAC accept?
85...264V AC, 120/240V AC nominal at 50...60 Hz.
How much POINTBus current does it supply?
1.3 A at 5.2V DC on horizontal mounting, 1.0 A vertically.
Can it be used with a 1734-PDN?
No. The EPAC is restricted to the 1734-ADN, ADNX, APB, ACNR and AENT adapters, and must not be used with the PDN or POINTBlock modules.
What is its isolation rating?
264V continuous, tested at 3250V DC for 60 s - the highest in the POINT I/O supply family.
How much heat does it dissipate?
8.4 W at 264V AC, 28.7 BTU/hr, from 15.1 W maximum consumption.
1734-EPAC is a head-of-slice unit in the POINT I/O system. Head units sit to the left of the I/O modules and either own the network connection, supply the POINTBus, or distribute field power; the modules to their right exist only as a slice hanging off that head unit.
| Attribute | Value |
| Catalog number | 1734-EPAC |
| Role | AC input expansion power supply |
| Width | 56.1 mm (2.21 in.) for the network adapters, 25.4 mm (1.00 in.) for expansion supplies, distributors and the compact head unit |
| Mounting | DIN rail, at the head of the slice |
| System clearance | 25.4 mm on all sides; 50.8 mm above when safety modules are present |
| Ordering note | Terminal bases for the I/O modules are separate line items |
POINTBus current is the budget that decides how many modules a slice can carry: most digital and analog modules draw 75 mA, the 1734-OW2 draws 80 mA, and 1734-IB4D draws 50 mA. The usable current of the adapter, plus that of any expansion power supply, divided by the per-module draw gives the maximum slice length, and that is a planning calculation rather than a rule of thumb.
Mechanically the system is width-driven: adapters occupy 56.1 mm, expansion power supplies and field power distributors 25.4 mm each, standard I/O modules 12.1 mm each, and safety I/O modules 24.1 mm each. Total panel width is the sum of those, and a layout that assumes a uniform module width is wrong on both the adapter and the safety side.
Clearance is a specification, not a courtesy: 25.4 mm on all sides of the system is the minimum, and a system with POINT I/O safety modules needs 50.8 mm above the assembly. Cabinets that pass at 25 mm on a digital-only slice fail once a safety module is added to the same rail.
The width difference between 56.1 mm and 25.4 mm is the difference between an adapter that carries a network port and a unit that only carries power. Both can head a slice, and both feed the POINTBus, but only the adapter appears on the network as a node; the expansion supply and the field power distributor exist to extend the slice inside the cabinet.
Ordering discipline for this family is the practical point: the module alone does not make a working channel, because the terminal base assembly is a separate catalog number, the RTB is a separate replacement part, and the head unit sets how many modules the slice can carry.
Related models, options and spare parts for this range are listed in the Allen-Bradley POINT I/O 1734 modules category.