The 1734-OE4C provides four 4...20 mA or 0...20 mA outputs in one 12 mm slice, with 16-bit resolution over 0...21 mA - the highest resolution of the 1734 current output family, against 13 bits on the two-channel 1734-OE2C.
Four channels in one module mean a shared reference and a shared failure domain: the dissipation rises to 2.15 W with outputs unloaded, and one module failure takes four loops with it.
| 1734-OE2C | 2 analog current outputs, 4...20 mA, 13 bits, non-isolated | IN STOCK |
| 1734-OE2V | 2 analog voltage outputs, 0...10V or +/-10V, 14 bits, non-isolated | IN STOCK |
| 1734-OE4C | 4 analog current outputs, 4...20 mA, 16 bits | IN STOCK |
Number of outputs |
4 single-ended, non-isolated, current |
Resolution |
16 bits over 0...21 mA, 2.5 uA/count |
Output current range |
4...20 mA or 0...20 mA, user configurable |
Data format |
Signed integer |
Accuracy |
0.1% full scale @ 25 °C, including offset, gain, non-linearity and repeatability |
Accuracy drift with temperature |
less than 50 ppm/deg C |
Step response to 63% of full scale |
40 us |
Output conversion rate |
1 us |
Power dissipation, max |
1.86 W with 750 ohm load on each output, 2.15 W with 0 ohm |
Thermal dissipation, max |
6.34 BTU/hr at 750 ohm, 7.33 BTU/hr at 0 ohm |
Terminal base |
1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS |
Keyswitch position |
4 |
POINTBus current, max |
75 mA @ 5V DC |
Isolation voltage |
50V continuous, basic insulation, I/O to system |
Operating temperature |
-20...55 °C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-SG001 (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Both modules quote 2.5 µA per count, but the four-channel module resolves 16 bits over 0...21 mA against 13 bits on 1734-OE2C. For a ratio control valve or a temperature setpoint that has to move in small increments the extra resolution removes visible stepping; for a simple open/close positioner the two-channel module is sufficient.
A single module now carries four current loops. Its power dissipation is 2.15 W at zero burden and 6.34 to 7.33 BTU/hr, roughly double the two-channel module, and losing the module loses all four outputs at once. Where the process needs independent loops, two 1734-OE2C modules buy isolation of failure at the cost of panel space.
1.86 W at 750 Ω burden and 2.15 W at 0 Ω reflects the same physics as the two-channel module: a shorted or very light burden is the hot case. In a closed cabinet with other heat sources, that difference between 6.34 and 7.33 BTU/hr is what the enclosure calculation has to absorb.
Less than 50 ppm/°C drift, 40 µs step response to 63% of full scale and a 1 µs conversion rate. The higher resolution costs nothing in speed, but the drift specification is the loosest of the OE family (5 ppm on OE2V, 30 ppm on OE2C) - a consideration for outdoor panels.
1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS at keyswitch position 4, POINTBus draw 75 mA at 5V DC, 50V continuous isolation to system. The four-channel module does not list the 1734-TB3/TB3S base in its published data, so a TB3-based panel needs a base check before ordering.
Where a panel already runs two 1734-OE2C modules and needs a fifth and sixth loop, one 1734-OE4C replaces both at 12 mm instead of 24 mm and one keyswitch position instead of two. The saving is panel width and two backplane addresses; the cost is that the two new loops now share a module with four others, so a spare-part strategy has to keep an OE4C on the shelf rather than an OE2C.
How does 1734-OE4C differ from 1734-OE2C?
Four current outputs instead of two, 16-bit resolution over 0...21 mA instead of 13 bits, 40 us step response instead of 24 us, and higher dissipation - 2.15 W unloaded against 1.83 W. Both use keyswitch 4 and 4...20 mA or 0...20 mA ranges.
What resolution does the module provide?
16 bits over 0...21 mA, 2.5 uA per count, with 0.1% of full scale accuracy at 25 deg C.
What is the drift over temperature?
Less than 50 ppm/deg C, looser than the 30 ppm/deg C of 1734-OE2C and the 5 ppm/deg C of 1734-OE2V.
Which terminal bases fit 1734-OE4C?
The published data lists 1734-TB, 1734-TBS, 1734-TOP and 1734-TOPS; 1734-TB3 and 1734-TB3S are not listed, so verify before using a TB3-based assembly.
Are the four outputs isolated?
No. Isolation is 50V continuous basic insulation from I/O to system, with no channel-to-channel isolation.
1734-OE4C is a 4-point current analog output in the POINT I/O family. It mounts on a terminal base assembly that is ordered separately, connects to the POINTBus through the base, and presents its field wiring on the removable terminal block.
| Attribute | Value |
| Catalog number | 1734-OE4C |
| Module type | 4-point current analog output |
| POINTBus current requirement | 75 mA |
| Module width | 12.1 mm (0.48 in.) standard, 24.1 mm (0.94 in.) for safety modules |
| Terminal base | Ordered separately: 1734-TB/TBS (8 terminal) or 1734-TB3/TB3S (12 terminal) |
| Module dimensions | 77.5 x 12.1 x 56.6 mm (3.05 x 0.48 x 2.23 in.), weight approx. 31-36 g |
POINTBus current is the budget that decides how many modules a slice can carry: most digital and analog modules draw 75 mA, the 1734-OW2 draws 80 mA, and 1734-IB4D draws 50 mA. The usable current of the adapter, plus that of any expansion power supply, divided by the per-module draw gives the maximum slice length, and that is a planning calculation rather than a rule of thumb.
Every POINT I/O module mounts in a terminal base that is ordered separately, and the number of field terminals on the base has to match the module: eight terminals for single-point-per-channel digital modules, twelve where the module needs a common or a shield return per channel group.
Safety and analog modules both spend panel width: a safety module occupies 24.1 mm rather than the standard 12.1 mm, and a slice that mixes safety and standard I/O has to be laid out from the width table rather than from the module count. The same table is what determines whether a slice still fits the rail after two safety modules are added.
Ordering discipline for this family is the practical point: the module alone does not make a working channel, because the terminal base assembly is a separate catalog number, the RTB is a separate replacement part, and the head unit sets how many modules the slice can carry.
Mechanically the system is width-driven: adapters occupy 56.1 mm, expansion power supplies and field power distributors 25.4 mm each, standard I/O modules 12.1 mm each, and safety I/O modules 24.1 mm each. Total panel width is the sum of those, and a layout that assumes a uniform module width is wrong on both the adapter and the safety side.
This part sits in the Allen-Bradley POINT I/O 1734 modules category, with the other models and spare parts listed alongside it.