The 1734-IE4C puts four 4...20 mA loops on one POINT I/O slice at 16 bits, 0.32 uA per count, for panels where rail space matters more than per-channel converter speed.
It is the current-only sibling of the 1734-IE8C: same converter-per-module architecture, same 60 ohm shunt, half the channels.
| 1734-IE2C | 2 analog current inputs, 4...20 mA, 16 bits over 0...21 mA, 60 ohm | IN STOCK |
| 1734-IE2V | 2 analog voltage inputs, 0...10V or +/-10V, 15 bits plus sign, 100 kOhm | IN STOCK |
| 1734-IE4S | 4 analog inputs, 0...20 mA / 0...10V, 16 bits, isolated | IN STOCK |
| 1734-IE8C | 8 analog current inputs, 4...20 mA, 16 bits | IN STOCK |
Number of inputs |
4, single-ended, non-isolated, current |
Input range |
4...20 mA or 0...20 mA |
Resolution |
16 bits over 0...21 mA, 0.32 uA per count |
Absolute accuracy |
0.1% of full scale at 25 deg C |
Accuracy drift |
30 ppm/deg C |
Input impedance |
60 ohm |
Conversion type |
Delta Sigma |
Common mode rejection |
-120 dB |
Normal mode rejection |
-60 dB, notch filter 13.1 Hz at 50 Hz and 15.7 Hz at 60 Hz |
Input update rate, per module |
240 ms at 50 Hz notch, 200 ms at 60 Hz (default), 120 ms at 100 Hz, 100 ms at 120 Hz, 60 ms at 200 Hz, 50 ms at 240 Hz, 40 ms at 300 Hz, 30 ms at 400 Hz, 25 ms at 480 Hz |
Step response, per channel |
60 ms at 50 Hz, 50 ms at 60 Hz, 30 ms at 100 Hz, 25 ms at 120 Hz, 15 ms at 200 Hz, 12.5 ms at 240 Hz, 10 ms at 300 Hz, 7.5 ms at 400 Hz, 6.25 ms at 480 Hz |
Maximum overload |
Fault protected to 28.8V DC |
POINTBus current, max |
75 mA @ 5V DC |
Power dissipation, max |
0.55 W @ 28.8V DC |
Thermal dissipation, max |
2.0 BTU/hr @ 28.8V DC |
Isolation voltage |
50V, tested at 1500V AC for 60 s, inputs and field power to system; no isolation between inputs or inputs to field power |
Field power input |
10...28.8V DC, 20 mA, Class 2 |
Terminal base |
1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS |
Keyswitch position |
3 |
Wire size |
0.25...2.5 mm2 (22...14 AWG), 100 deg C or greater, shielded |
Dimensions, HxWxD |
56.6 x 12.1 x 77.5 mm |
Temperature, operating |
-20...55 deg C (-4...131 deg F) |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN032-EN-P (module specifications) and 1734-UM016 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The IE4C digitises four single-ended current loops through a single delta-sigma converter, so the 200 ms default update rate is per module, not per channel - each channel effectively refreshes four times slower than the module figure suggests. That is the same architecture as the 1734-IE8C, and it is the single most misunderstood specification in the high density family.
16 bits over 0...21 mA gives 0.32 uA per count, but the published accuracy is 0.1% of full scale at 25 deg C - roughly 21 uA - with 30 ppm/deg C drift. The 0.32 uA step resolves a change; the 0.1% figure tells you how close the reading is. Buying 16 bits for precision rather than resolution is a common mistake on a 4...20 mA pressure loop.
A 60 ohm shunt in a 4...20 mA loop drops 1.2V at 20 mA. On a 24V loop with a two-wire transmitter you have that 1.2V less to work with, which is why the 1734-VTM supply or a transmitter with a wide compliance range matters more than the ADC on a long loop.
Inputs and field power sit behind 50V basic insulation tested at 1500V AC for 60 s, with no isolation between inputs or between inputs and field power. All four channels share the common terminal 4 or 5, so a grounded transmitter on channel 0 puts that ground potential on every channel's reference.
The notch sits at 13.1 Hz for a 50 Hz line and 15.7 Hz for a 60 Hz line. Selecting the wrong notch leaves 50 Hz ripple in a 60 Hz plant and shows up as a few counts of jitter on a steady signal. The default is 60 Hz; change it deliberately on export machines. The same notch setting drives the published update rate, so a 50 Hz notch on a 60 Hz plant buys rejection at 13.1 Hz and costs the extra 40 ms between module refreshes.
How many inputs does 1734-IE4C have?
Four single-ended, non-isolated current inputs, 4...20 mA or 0...20 mA, 16 bits over 0...21 mA at 0.32 uA per count.
Is the 200 ms update rate per channel?
No - it is per module. Four channels share one converter, so at the 60 Hz default the whole module refreshes in 200 ms.
What accuracy and drift are published?
0.1% of full scale at 25 deg C including offset, gain, non-linearity and repeatability, with 30 ppm/deg C drift.
What isolation does it provide?
50V basic, tested at 1500V AC for 60 s, inputs and field power to system. There is no isolation between inputs or between inputs and field power.
Which base and keyswitch position?
1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS, keyswitch position 3, with shielded 100 deg C wire and 75 mA from the 5V POINTBus.
The table reproduces the sibling list this page publishes, with each catalog number put in the class of module it is; the paragraph after it places this part in that ladder, and the arithmetic at the end uses this page's own POINTBus figure against the 1.0 A budget the adapters print.
| Catalog number | What the published line says | Class of module |
| 1734-IE2C | 2 analog current inputs, 4...20 mA, 16 bits over 0...21 mA, 60 ohm | Analog |
| 1734-IE2V | 2 analog voltage inputs, 0...10V or +/-10V, 15 bits plus sign, 100 kOhm | Analog |
| 1734-IE4S | 4 analog inputs, 0...20 mA / 0...10V, 16 bits, isolated | Analog |
| 1734-IE8C | 8 analog current inputs, 4...20 mA, 16 bits | Analog |
1734-IE4C is the four-channel current input: 16 bits over 0...21 mA, 0.32 uA per count, 240 ms module update at 50 Hz and 200 ms at 60 Hz. It sits between the 2-channel 1734-IE2C and the 8-channel 1734-IE8C in this list, and it is the only one of the three whose printed conversion type is named as delta sigma on the page.
At the 75 mA this module prints, the 1.0 A POINTBus carries 13 modules with nothing left over. A full 63-module rack of this module would be 4725 mA, 4.7 times the 1.0 A budget, so the 63-module figure is a slot count and the current is what decides how many expansion supplies go into the rack.
Two catalog numbers one digit apart often differ in exactly one published figure, and that figure is the one the specification is written around - which is why the ladder is worth reading as a table rather than as a list of options.
What the printed data does not carry: this page prints the sibling descriptions but not their POINTBus currents, so the 75 mA is the only draw in the table that can be used; and no page in this family states a maximum number of modules between two power supplies.
Source: Rockwell publication 1734-IN001 (POINT I/O module and adapter installation instructions) and the module specification tables published on these pages; the class column and the module count are read off the printed lines, not assumed.
The Allen-Bradley POINT I/O 1734 modules category lists the related catalog numbers, options and accessories for this range.