1746-NR4 is the 4 Point Resistance Input Module in the Allen-Bradley SLC 500 range: SLC 4 Point Resistance Input Module.
It occupies one I/O slot, takes both backplane rails, and is configured channel by channel from the processor; the ranges, resolution and filter settings below are the ones a project engineer needs before the loop is designed.
| 1746-NR4 | 4 Point Resistance Input Module | IN STOCK |
| 1746-NR8 | 8 Point Resistance Input Module | IN STOCK |
Application |
SLC 4 Point Resistance Input Module |
Cat Num |
1746-NR4 |
Brand Name |
Rockwell |
Product Type |
4 Point Resistance Input Module |
Channels |
4 RTD or resistance inputs |
Input range |
100/200/500 Ω platinum, 10 Ω copper, 120 Ω nickel, 604 Ω nickel-iron, 150/500/1000/3000 Ω resistance |
Resolution |
16-bit |
Backplane current, 5V DC |
50 mA |
Backplane current, 24V DC |
50 mA |
Update time / filtering |
Filter 2.62...65.5 Hz, step response 12...300 ms |
Isolation |
500V dc continuous |
Lifecycle |
Discontinued |
Discontinued date |
December 30, 2015 |
Replacement category |
Functional Replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN007 (module specifications) and 1747-UM011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Official Rockwell description: SLC 4 Point Resistance Input Module.
4 Point Resistance Input Module with 4 RTD or resistance inputs.
Application: SLC 4 Point Resistance Input Module.
Cat Num: 1746-NR4.
Brand Name: Rockwell.
Product Type: 4 Point Resistance Input Module.
Channels: 4 RTD or resistance inputs.
Input range: 100/200/500 Ω platinum, 10 Ω copper, 120 Ω nickel, 604 Ω nickel-iron, 150/500/1000/3000 Ω resistance.
Resolution: 16-bit.
Backplane current, 5V DC: 50 mA.
Backplane current, 24V DC: 50 mA.
Update time / filtering: Filter 2.62...65.5 Hz, step response 12...300 ms.
Isolation: 500V dc continuous.
Lifecycle: Discontinued.
Discontinued date: December 30, 2015.
Replacement category: Functional Replacement.
The card measures resistance, not temperature: the RTD type, the excitation current and the temperature or resistance scaling are all set per channel, and a 2-wire element loses the lead resistance that a 3-wire or 4-wire connection cancels.
Broken sensor detection is per channel and reports open or short circuit, which is the reason an NR4 or NR8 is preferred over a temperature transmitter where the reading feeds a control loop.
The NR4 reads 4 channels at 50 mA from each backplane rail; the NR8 doubles the channel count at 100 mA at 5V dc, so a chassis at its limit gains channels but not power headroom.
Rockwell lists 1746-NR4 as Discontinued, discontinued date December 30, 2015, replacement category Functional Replacement.
No replacement catalog number is printed on the Rockwell page, so the route is an engineering substitution with a re-ranged analogue front end, not a part-for-part swap.
Rockwell's migration guidance for Bulletin 1746 routes analog points to Compact 5000 analog modules with a Logix controller; machines that stay on SLC 500 are supported from the secondary market.
The terminal block, the slot address and the module ID code stay the same when a card is replaced by the same catalog number, which is why the original number still has a place in a maintenance spares list after the end of sale.
A modular SLC 500 reserves slot 0 for the processor or the adapter, so this module goes in any other I/O slot; the current drawn from 5V dc and 24V dc both count against the chassis supply.
The analog front end is factory calibrated and, on the newer cards, autocalibrates at power-up and on channel enable, so an accuracy figure quoted at 25 °C is what the card delivers without a field trim.
Isolation is 500V dc continuous between the field terminals and the backplane; that figure, not the channel count, is what decides whether a card can sit next to a drive with a noisy earth.
The card in red in the catalogue table at the top of this page is the one described here.
What is 1746-NR4?
SLC 4 Point Resistance Input Module. 4 Point Resistance Input Module.
How many channels does 1746-NR4 have?
4 RTD or resistance inputs.
What ranges does 1746-NR4 accept?
Inputs: 100/200/500 Ω platinum, 10 Ω copper, 120 Ω nickel, 604 Ω nickel-iron, 150/500/1000/3000 Ω resistance.
How much backplane current does 1746-NR4 draw?
50 mA at 5V dc and 50 mA at 24V dc.
Is 1746-NR4 still available?
Rockwell lists it as Discontinued, discontinued date December 30, 2015, replacement category Functional Replacement.
1746-NR4 is a 4-channel RTD input module for the SLC 500 modular chassis. It occupies one slot to the right of the processor, draws its backplane current from the chassis power supply, and presents its field wiring on a removable terminal block.
| Attribute | Value |
| Catalog number | 1746-NR4 |
| Module type | 4-channel RTD input module |
| Inputs | 4 |
| Input type | RTD |
| Backplane current @ 5V | 50 mA |
| Backplane current @ 24V | 50 mA |
An RTD input module measures resistance, so the lead resistance is part of the measurement unless the wiring is compensated. The 50 mA draw on both rails is small, which is why several of these fit in one chassis; the accuracy question is entirely in the field wiring, not in the slot budget.
Remote I/O changes the data path, not the module: with a 1747-ASB adapter in the remote chassis, analog and thermocouple modules require block transfers, and a program written as direct I/O in a local chassis does not simply move to a remote one. The 1746-NO4I and 1746-NO4V analog outputs also accept a user-supplied 24V DC source, and that source must be 24V plus or minus 10 percent; the 1746-P1, P2, P5 and P6 user supplies do not meet that tolerance.
Power supply selection is a two-rail comparison, not a wattage comparison: 1746-P1 gives 2.0 A at 5V and 0.46 A at 24V, 1746-P2 gives 5.0 A and 0.96 A, 1746-P3 gives 3.6 A and 0.87 A from a 19.2 to 28.8V DC input, and 1746-P4 gives 10.0 A and 2.88 A with a 70 W total limit across all outputs. Choosing by input voltage alone and ignoring the 24V allowance is how a chassis ends up short on analog capacity.
Sizing a SLC 500 system is a fixed sequence, and it is the sequence rather than the arithmetic that stops most retrofits: count the I/O points, convert them into modules at the published channels per module, add a scanner or an adapter where the I/O sits remotely, total the 5V and 24V draws per chassis, choose the power supply that covers both totals, then choose the chassis with enough slots including fillers for the empties. Doing it in the reverse order, from a chassis that already exists, produces a system that fits mechanically and fails electrically.
The processor or the I/O adapter occupies the left-most slot of a 1746 chassis, and the power supply is a separate unit mounted on the left end of the chassis rather than a module inside it. That is why a spare chassis is not a spare system: chassis, power supply and processor are three catalog numbers, and the interconnect cable is a fourth.
Before ordering, confirm the slot count against the I/O list, confirm the 5V and 24V totals against the supply capacity rather than against the wattage, and confirm that the cable and the chassis are ordered separately, because none of these parts is included with any other.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley SLC 500 1746 I/O modules category.