Product Details:
Payment & Shipping Terms:
|
1746-NR4 is the 4 Point Resistance Input Module in the Allen-Bradley SLC 500 range: SLC 4 Point Resistance Input Module.
It occupies one I/O slot, takes both backplane rails, and is configured channel by channel from the processor; the ranges, resolution and filter settings below are the ones a project engineer needs before the loop is designed.
| 1746-NR4 | 4 Point Resistance Input Module | IN STOCK |
| 1746-NR8 | 8 Point Resistance Input Module | IN STOCK |
Application |
SLC 4 Point Resistance Input Module |
Cat Num |
1746-NR4 |
Brand Name |
Rockwell |
Product Type |
4 Point Resistance Input Module |
Channels |
4 RTD or resistance inputs |
Input range |
100/200/500 Ω platinum, 10 Ω copper, 120 Ω nickel, 604 Ω nickel-iron, 150/500/1000/3000 Ω resistance |
Resolution |
16-bit |
Backplane current, 5V DC |
50 mA |
Backplane current, 24V DC |
50 mA |
Update time / filtering |
Filter 2.62...65.5 Hz, step response 12...300 ms |
Isolation |
500V dc continuous |
Lifecycle |
Discontinued |
Discontinued date |
December 30, 2015 |
Replacement category |
Functional Replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN007 (module specifications) and 1747-UM011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Official Rockwell description: SLC 4 Point Resistance Input Module.
4 Point Resistance Input Module with 4 RTD or resistance inputs.
Application: SLC 4 Point Resistance Input Module.
Cat Num: 1746-NR4.
Brand Name: Rockwell.
Product Type: 4 Point Resistance Input Module.
Channels: 4 RTD or resistance inputs.
Input range: 100/200/500 Ω platinum, 10 Ω copper, 120 Ω nickel, 604 Ω nickel-iron, 150/500/1000/3000 Ω resistance.
Resolution: 16-bit.
Backplane current, 5V DC: 50 mA.
Backplane current, 24V DC: 50 mA.
Update time / filtering: Filter 2.62...65.5 Hz, step response 12...300 ms.
Isolation: 500V dc continuous.
Lifecycle: Discontinued.
Discontinued date: December 30, 2015.
Replacement category: Functional Replacement.
The card measures resistance, not temperature: the RTD type, the excitation current and the temperature or resistance scaling are all set per channel, and a 2-wire element loses the lead resistance that a 3-wire or 4-wire connection cancels.
Broken sensor detection is per channel and reports open or short circuit, which is the reason an NR4 or NR8 is preferred over a temperature transmitter where the reading feeds a control loop.
The NR4 reads 4 channels at 50 mA from each backplane rail; the NR8 doubles the channel count at 100 mA at 5V dc, so a chassis at its limit gains channels but not power headroom.
Rockwell lists 1746-NR4 as Discontinued, discontinued date December 30, 2015, replacement category Functional Replacement.
No replacement catalog number is printed on the Rockwell page, so the route is an engineering substitution with a re-ranged analogue front end, not a part-for-part swap.
Rockwell's migration guidance for Bulletin 1746 routes analog points to Compact 5000 analog modules with a Logix controller; machines that stay on SLC 500 are supported from the secondary market.
The terminal block, the slot address and the module ID code stay the same when a card is replaced by the same catalog number, which is why the original number still has a place in a maintenance spares list after the end of sale.
A modular SLC 500 reserves slot 0 for the processor or the adapter, so this module goes in any other I/O slot; the current drawn from 5V dc and 24V dc both count against the chassis supply.
The analog front end is factory calibrated and, on the newer cards, autocalibrates at power-up and on channel enable, so an accuracy figure quoted at 25 °C is what the card delivers without a field trim.
Isolation is 500V dc continuous between the field terminals and the backplane; that figure, not the channel count, is what decides whether a card can sit next to a drive with a noisy earth.
The card in red in the catalogue table at the top of this page is the one described here.
What is 1746-NR4?
SLC 4 Point Resistance Input Module. 4 Point Resistance Input Module.
How many channels does 1746-NR4 have?
4 RTD or resistance inputs.
What ranges does 1746-NR4 accept?
Inputs: 100/200/500 Ω platinum, 10 Ω copper, 120 Ω nickel, 604 Ω nickel-iron, 150/500/1000/3000 Ω resistance.
How much backplane current does 1746-NR4 draw?
50 mA at 5V dc and 50 mA at 24V dc.
Is 1746-NR4 still available?
Rockwell lists it as Discontinued, discontinued date December 30, 2015, replacement category Functional Replacement.