Product Details:
Payment & Shipping Terms:
|
The 1734-IA4 takes 4 nonisolated sinking AC inputs on one slice, 7.5 mA at 120V AC. No external relay or interface card is needed between a 120V or 220V field contact and the POINTBus.
Because the input is sinking and nonisolated, all points share one common and the field supply must come from a source that matches the module voltage class exactly: 65V AC...132V AC.
| 1734-IA2 | 2 sinking 120V AC inputs, 65...132V AC, 7.5 mA at 120V | IN STOCK |
| 1734-IA4 | 4 sinking 120V AC inputs, 65...132V AC, 30.9 g | IN STOCK |
| 1734-IM2 | 2 sinking 220V AC inputs, 159...264V AC, 8.5 mA at 220V | IN STOCK |
| 1734-IM4 | 4 sinking 220V AC inputs, 159...264V AC, 30.9 g | IN STOCK |
Number of inputs |
4 (1 group of 4), nonisolated, sinking |
Voltage, on-state, nom |
120V AC |
Voltage, on-state range |
65V AC...132V AC |
Voltage, off-state, max |
43V AC |
Current, on-state, nom |
7.5 mA @ 120V AC, 60 Hz |
Current, on-state range |
4.0 mA @ 65V AC...8.5 mA @ 132V AC, 60 Hz |
Impedance, input, nom |
10.6 kOhm |
Input filter time |
20 ms hardware filter plus 1...65 ms digital filter, programmable in 1 ms steps |
POINTBus current, max |
75 mA @ 5V DC |
Power dissipation, max |
0.50 W @ 132V AC |
Thermal dissipation, max |
1.71 BTU/hr @ 132V AC |
Isolation voltage |
240V (continuous), type tested at 3250V DC for 60 s, field side to system |
External AC power supply |
120V AC @ 60 Hz, 85...132V AC, 47...63 Hz |
Terminal base |
1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS |
Wiring category |
1 - on signal ports |
Keyswitch position |
8 |
Dimensions, HxWxD |
56.0 x 12.0 x 75.5 mm |
Weight, approx |
30.9 g |
Temperature, operating |
-20...55 deg C (-4...131 deg F), T4A |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-SG001E-EN-P (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
On-state range 65V AC...132V AC, off-state guaranteed below 43V AC. That gap is what keeps a 120V circuit from reading a stray 40V induced level as a valid ON, and it is the reason this module tolerates long field wiring runs next to contactor coils.
Nominal 7.5 mA @ 120V AC, 60 Hz, with a working range of 4.0 mA @ 65V AC...8.5 mA @ 132V AC, 60 Hz. A dry contact or a small pilot relay has to carry that current reliably at the low end of the range; a sealed reed rated for switching only 1 mA may not wet properly, so check the device's minimum load before dropping a 4-point slice into a panel full of low-current sensors.
Every Series C AC input slice carries a 20 ms hardware filter, then a digital filter from 1 to 65 ms set in 1 ms steps. Twenty milliseconds is already longer than a half cycle at 60 Hz, so the hardware stage alone rejects most contact bounce; the digital stage is for a noisy bus, not for speed. Do not expect this slice to catch a 10 ms pulse.
External supply 120V AC @ 60 Hz, 85...132V AC, 47...63 Hz. Isolation is 240V continuous, type tested at 3250V DC for 60 s from field side to system - the highest test level in the POINT I/O digital family, which is what a 220V circuit demands. The slice fits a TB, TBS, TOP or TOPS base at keyswitch position 8 and dissipates 0.50 W @ 132V AC.
A 4-point AC slice removes four or eight interposing relays, their DIN rail, and the wiring between relay coil and input. On a panel that switches 120V pushbuttons and level switches directly, the saving is real; on a panel already built around 24V DC, stay with a DC slice and keep one voltage class in the cabinet. The four AC input slices share one 30.9 g moulding and one keyswitch position, so keeping a single spare on the shelf covers 2 and 4 point duties in either voltage class.
How many inputs does 1734-IA4 have?
Four, in one nonisolated sinking group of four, 120V AC nominal from 65V AC to 132V AC.
What is the input current?
7.5 mA at 120V AC nominal, 4.0 mA at 65V AC and 8.5 mA at 132V AC.
What filter time does it have?
20 ms hardware filter plus a 1...65 ms digital filter set in 1 ms steps.
Does 1734-IA4 need a separate field supply?
Yes, 120V AC at 60 Hz, 85...132V AC, 47...63 Hz, and it dissipates 0.50 W at 132V AC.
Which modules share the same slice footprint?
1734-IA2, 1734-IA4, 1734-IM2 and 1734-IM4 all use 56.0 x 12.0 x 75.5 mm and weigh 30.9 g.
1734-IA4 is a 4-point AC input in the POINT I/O family. It mounts on a terminal base assembly that is ordered separately, connects to the POINTBus through the base, and presents its field wiring on the removable terminal block.
| Attribute | Value |
| Catalog number | 1734-IA4 |
| Module type | 4-point AC input |
| POINTBus current requirement | 75 mA |
| Module width | 12.1 mm (0.48 in.) standard, 24.1 mm (0.94 in.) for safety modules |
| Terminal base | Ordered separately: 1734-TB/TBS (8 terminal) or 1734-TB3/TB3S (12 terminal) |
| Module dimensions | 77.5 x 12.1 x 56.6 mm (3.05 x 0.48 x 2.23 in.), weight approx. 31-36 g |
POINTBus current is the budget that decides how many modules a slice can carry: most digital and analog modules draw 75 mA, the 1734-OW2 draws 80 mA, and 1734-IB4D draws 50 mA. The usable current of the adapter, plus that of any expansion power supply, divided by the per-module draw gives the maximum slice length, and that is a planning calculation rather than a rule of thumb.
Every POINT I/O module mounts in a terminal base that is ordered separately, and the number of field terminals on the base has to match the module: eight terminals for single-point-per-channel digital modules, twelve where the module needs a common or a shield return per channel group.
Sink/source and AC-input variants exist because the field device decides the wiring, not the module preference: a sinking input expects the field device to switch to the positive rail, a sourcing input expects it to switch to common, and an isolated AC input exists so that a shared common between channels does not create a path between two different field circuits.
Ordering discipline for this family is the practical point: the module alone does not make a working channel, because the terminal base assembly is a separate catalog number, the RTB is a separate replacement part, and the head unit sets how many modules the slice can carry.
Producer/consumer behaviour is what makes the slice worth wiring this way: input data and output status can be shared among several Logix controllers without a second physical input module per controller, so the I/O count is set by field devices rather than by the number of controllers that need to see them.
This part sits in the Allen-Bradley POINT I/O 1734 modules category, with the other models and spare parts listed alongside it.