The 1734-OB8 drives eight 24V DC sourcing outputs from a single 12 mm POINT I/O slice. Its default data map is one byte with channel 0 in bit 0 through channel 7 in bit 7, so the controller writes the whole byte and the module holds the state until it is changed or the connection is dropped.
Each output is rated 1.0 A with 0.2V DC maximum drop and 0.5 mA maximum off-state leakage; the module total is 3.0 A, and surge capability is 2 A for 10 ms every 3 s.
| 1734-OB2 | 2 sourcing 24V DC outputs, 2.0 A per module, 32.60 g | IN STOCK |
| 1734-OB4 | 4 sourcing 24V DC outputs, 3.0 A per module, 33.17 g | IN STOCK |
| 1734-OB8 | 8 sourcing 24V DC outputs, 3.0 A per module, 35.4 g | IN STOCK |
Outputs per module |
8 (1 group of 8), non-isolated, sourcing |
Output current rating |
1.0 A per output, not to exceed 3.0 A max per module |
External DC supply current |
32 mA |
On-state voltage range, min |
10V DC |
On-state voltage range, nominal |
24V DC |
On-state voltage range, max |
28.8V DC |
On-state voltage drop, max |
0.2V DC |
On-state current, min per channel |
1.0 mA |
Off-state leakage, max |
0.5 mA @ 28.8V DC |
Output signal delay, off to on |
0.1 ms |
Output signal delay, on to off |
0.1 ms |
Surge current |
2 A for 10 ms, repeatable every 3 s |
POINTBus current, max |
75 mA @ 5V DC |
Isolation voltage |
50V (continuous), reinforced insulation type |
External DC supply, nominal |
24V DC |
External DC supply range |
10...28.8V DC |
Terminal base screw torque |
0.8 Nm (7 lb-in) |
Dimensions, HxWxD |
56.6 x 12.1 x 77.5 mm |
Wiring category |
2 - on signal ports |
Temperature code |
T4A (North American), T4 (IEC) |
Operating temperature |
-20...55 °C |
Relative humidity |
5...95% non-condensing |
Enclosure |
None (open style) |
Power dissipation, max @ 28.8V DC |
2.0 W @ 28.8V DC |
Thermal dissipation, max @ 28.8V DC |
6.8 BTU/hr @ 28.8V DC |
Weight, approx |
35.4 g |
Module location |
1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS |
Field wiring terminations |
0...7 - Outputs 0...7, common daisy-chained to the 8 terminals or to the base common |
Indicators |
8 yellow output status, 2 green/red module and network status |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN018-EN-E (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Because all eight channels sit in one group and one byte, a single write sets the whole module. That is efficient for a bank of eight pilot valves on one manifold, and awkward when the eight loads need independent fault handling - in that case split them across two modules so a fault does not take four unrelated actuators with it.
Outputs 0 through 7 are terminals 0 through 7. Common is daisy-chained from the adapter, a 1734-FPD or a 1734-EP24DC, or from a user-supplied external terminal block; the 24V DC for the module comes from the same source through the internal power bus. Supply current for the output stage is 32 mA, and the load current passes on top of that.
At 28.8V DC the slice dissipates 2.0 W, 6.8 BTU/hr, and that is before the load current. Eight channels each sinking 0.5 A add substantial heat inside the enclosure from the load side, so cabinet sizing has to account for the driven devices, not just the module rating.
Switching is 0.1 ms in both directions. The 0.5 mA off-state leakage is the number to check against small loads: a 24V relay with a 2 mA pick-up will not reliably drop out, while a standard 24V pilot valve at 40 to 60 mA has ample margin. Surge capability covers lamp inrush and small DC motor starts at 2 A for 10 ms every 3 s.
1734-OB8 is the standard eight-point sourcing output; 1734-OB8E adds electronic protection with diagnostics for each channel, and 1734-OB2EP is the protected two-point version. All share the same 10...28.8V DC window and the same 50V isolation, so the choice is by diagnostics and point count, not by voltage.
Are the outputs isolated from the POINTBus?
The outputs are non-isolated from the field supply and isolated from the system side by 50V (continuous) reinforced insulation. Each module switches the external 24V DC supply that the adapter, a 1734-FPD or a 1734-EP24DC feeds through the base terminals.
What is the maximum current per module?
Each output carries 1.0 A. The module total is 2.0 A for 1734-OB2, while 1734-OB4 and 1734-OB8 allow up to 3.0 A per module as long as no single channel exceeds 1.0 A. Surge capability is 2 A for 10 ms, repeatable every 3 s.
What happens to the outputs when the controller stops?
The module holds the last state it was given until the adapter drops the connection or the field supply is removed; there is no watchdog in the module itself. Configure the adapter's fault action and the output module's program-to-fault state so a communication loss drives the outputs to the safe state your risk assessment requires.
Can a 1734-OB8 drive eight contactor coils directly?
Only if the total coil current stays inside the module limit. Eight coils of 0.15 A come to 1.2 A, which is acceptable on any member of the family, but a group of sealed contactors drawing 0.6 A each would exceed the 1.0 A per channel and the 3.0 A module limit - use interposing relays or split the load across two modules.
Which terminal base fits a 1734-OB8?
1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS. The two-point 1734-OB2 additionally accepts 1734-TB3, 1734-TB3S, 1734-TOP3 and 1734-TOP3S. Terminal base screw torque is 0.8 Nm (7 lb-in).
How much current does the module take from the adapter?
75 mA at 5V DC on POINTBus, plus the external 24V DC supply current for the output stage - 8 mA for 1734-OB2, 16 mA for 1734-OB4 and 32 mA for 1734-OB8, with the load current on top of that.
How many bytes of output data does a 1734-OB8 need?
One byte. Channel 0 is bit 0 through channel 7 is bit 7, with 1 meaning on. The default data map consumes that byte as scanner Tx data and the module holds the last state.
Browse the Allen-Bradley POINT I/O 1734 modules category for the other models, options and spare parts that share this range.