The 1794-ASB Series E is the standard FLEX I/O Remote I/O adapter: 8 modules, 57.6/115.2/230.4 kbps, and rack number plus complementary rack selection on switches S1 and S2.
It is deliberately not for the Classic PLC-5/15 or PLC-5/25 — those need an ASBLT — which is the single most common wrong-catalog pick in a legacy RIO retrofit.
| 1794-AENT | EtherNet/IP adapter, single RJ45, 8 modules | IN STOCK |
| 1794-AENTR | dual-port EtherNet/IP adapter, redundancy capable | IN STOCK |
| 1794-AENTRXT | dual-port EtherNet/IP adapter, extended temperature | IN STOCK |
| 1794-ACN15 | ControlNet adapter, 15 Mbps, 8 modules | IN STOCK |
| 1794-ACN15K | ControlNet adapter, 15 Mbps, conformal coated | IN STOCK |
| 1794-ACNR | ControlNet adapter with redundant media | IN STOCK |
| 1794-ACNR15XT | ControlNet adapter, redundant media, extended temperature | IN STOCK |
| 1794-ACN | ControlNet adapter module, 8 modules | IN STOCK |
| 1794-ADN | DeviceNet adapter, 8 modules | IN STOCK |
| 1794-ADNK | DeviceNet adapter, conformal coated | IN STOCK |
| 1794-APB | Profibus DP adapter, 8 modules | IN STOCK |
| 1794-APBDPV1 | Profibus DP-V1 adapter, 8 modules | IN STOCK |
| 1794-ASB | Remote I/O adapter, 8 modules | IN STOCK |
| 1794-ASB2 | Remote I/O adapter, extended functionality | IN STOCK |
| 1794-ASBLT | Remote I/O adapter with built-in termination | IN STOCK |
Application |
FLEX I/O Remote I/O adapter |
Cat Num |
1794-ASB Series E |
Brand Name |
Rockwell |
I/O module capacity |
8 modules |
Input voltage range |
19.2...31.2V DC, 450 mA |
Output voltage |
5V DC, 640 mA |
Inrush current |
23 A at 24V DC for 2 ms |
Communication rate |
57.6, 115.2, 230.4 kbps |
Isolation |
50V continuous, tested 750V DC for 60 s |
Dimensions |
87 x 69 x 69 mm |
Operating temperature |
0...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
57.6, 115.2 or 230.4 kbps, with auto baud available when 32-point mode is switched on.
Rack number set on S1, and 32-point mode plus output behaviour (restart or hold last state) on S2.
A PRL communication reset button and Belden 9463 cable with a removable connector.
Termination resistor 82 ohm or 150 ohm where the processor documentation calls for it.
19.2...31.2V DC at 450 mA, with 330 mA typical at 24V.
23 A inrush for 2 ms demanded from the 24V supply.
5V DC 640 mA output on the Flexbus.
4.6 W and 1.7 BTU/hr at 31.2V DC.
Series E replaces 1794-ASB Series A and B in standard addressing mode.
Do not use it with Classic PLC-5/15 or PLC-5/25, where the 1794-ASBLT is the specified adapter.
50V isolation, tested at 750V DC for 60 s.
87 x 69 x 69 mm, 0...55 deg C, open-style enclosure.
1794-ASBK is the same adapter conformally coated to ISA/ANSI-71.040 Class G3.
Published in the same table with identical electrical ratings.
22...12 AWG single or 22...16 AWG double wire, 0.8 N*m torque.
European Zone 2 approved as Series E.
Remote I/O islands on PLC-5 and 1747-SN scanner systems.
Panels replacing a Series A or B adapter.
Not PLC-5/15 or PLC-5/25.
Not EtherNet/IP, ControlNet or DeviceNet.
How many modules can the 1794-ASB carry?
8 FLEX I/O modules.
Which processors must not use it?
Classic PLC-5/15 and PLC-5/25, which require the 1794-ASBLT.
What rates are supported?
57.6, 115.2 and 230.4 kbps.
What is the input draw?
19.2...31.2V DC at 450 mA maximum, 330 mA typical at 24V.
What is the isolation rating?
50V continuous, tested at 750V DC for 60 s.
What is the inrush?
23 A at 24V DC for 2 ms.