Product Details:
Payment & Shipping Terms:
|
The 1769-OW8 (also written 1769OW8) is the eight-point relay contact slice of the Compact I/O 1769 range: eight normally open contacts in two groups of four, 2.5 A per point, 16 A per module, and a field range that reaches 265V AC.
Relay contacts are the only way to switch a mixed-voltage panel from one module. A 110V AC contactor coil, a 24V DC pilot light and a 220V AC solenoid can all hang on the same eight points without a voltage conversion in between — and with 0 mA off-state leakage, no loading resistor and no glowing LED pilots.
| 1769-IA16 | Compact 16-point 120V AC input module | IN STOCK |
| 1769-IQ16 | Compact 16-point 24V DC sink/source input module | IN STOCK |
| 1769-IQ32 | Compact 32-point 24V DC sink/source input module | IN STOCK |
| 1769-OA16 | Compact 16-point 120/240V AC output module | IN STOCK |
| 1769-OB16 | Compact 16-point 24V DC output module | IN STOCK |
| 1769-OB32 | Compact 32-point 24V DC output module | IN STOCK |
| 1769-OW16 | Compact 16-point relay output module | IN STOCK |
| 1769-IF4 | Compact 4-channel analog input module | IN STOCK |
| 1769-IF8 | Compact 8-channel analog input module | IN STOCK |
| 1769-IF16C | Compact 16-channel current input module | IN STOCK |
| 1769-OF4 | Compact 4-channel analog output module | IN STOCK |
| 1769-OF8V | Compact 8-channel voltage output module | IN STOCK |
| 1769-OF8C | Compact 8-channel current output module | IN STOCK |
| 1769-ARM | Compact address reserve module | IN STOCK |
Application |
Compact I/O, 1769 bus |
Cat Num |
1769-OW8 |
Brand Name |
Rockwell |
Outputs |
8 normally open (4 points per group) |
Operating voltage range |
5…265V AC |
Delay, on / off |
10 ms / 10 ms |
Current draw @ 5.1V |
125 mA |
Current draw @ 24V |
100 mA |
Heat dissipation, max |
2.83 W |
Off-state leakage, max |
0 mA |
On-state current, min |
10 mA @ 5V DC |
Current per point, max |
2.5 A |
Current per module, max |
16 A |
Contact rating, 240V AC |
2.5 A continuous; make 7.5 A, break 0.75 A; 1800 VA make / 180 VA break; NEMA C300 |
Contact rating, 120V AC |
Make 15 A, break 1.5 A |
Contact rating, 125V DC |
1.0 A continuous; break 0.22 A; 28 VA; NEMA R150 |
Contact rating, 24V DC |
2.0 A continuous; break 1.2 A; 28 VA |
Isolation |
1836V AC 1 s or 2596V DC 1 s, point to bus and group to group; 265V AC working voltage (IEC Class II reinforced) |
Slot width / weight |
1 slot / 280 g |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
How much current can 1769-OW8 switch?
2.5 A per point continuous and 16 A per module. At 240V AC the contact rating is 2.5 A continuous with 7.5 A make and 0.75 A break, 1800 VA make / 180 VA break, NEMA C300.
Can 1769-OW8 switch DC loads?
The published operating range is 5…265V AC. The same page gives 125V DC (1.0 A continuous, 0.22 A break, 28 VA, R150) and 24V DC (2.0 A continuous, 1.2 A break, 28 VA) contact ratings, with the 28 VA rule — divide 28 VA by the DC voltage, capped at 2 A below 48V DC.
Why is 1769-OW8 leakage 0 mA?
These are mechanical relay contacts, not solid-state outputs, so there is no off-state leakage and no need for a loading resistor on a small load.
What is the minimum load for 1769-OW8?
10 mA at 5V DC. A contact will not wet reliably below that, so a very low-current input needs a parallel resistor.
What does 1769-OW8 draw from the backplane?
125 mA at 5.1V and 100 mA at 24V, with 2.83 W maximum heat dissipation, one slot, 280 g, eight-module distance rating.
What is the isolation rating of 1769-OW8?
1836V AC for 1 s or 2596V DC for 1 s, point to bus and group to group, with 265V AC working voltage under IEC Class II reinforced insulation.