Product Details:

Place of Origin: Made in MALAYSIA
Brand Name: Rockwell
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1769-OW8 / 1769OW8

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $125.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 10 PCS
Detailed Product Description

1769-OW8 technical data PDF download CompactLogix 1769-OW8 / 1769OW8 8-Point AC/DC Relay Output Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC I/O

The 1769-OW8 (also written 1769OW8) is the eight-point relay contact slice of the Compact I/O 1769 range: eight normally open contacts in two groups of four, 2.5 A per point, 16 A per module, and a field range that reaches 265V AC.

Relay contacts are the only way to switch a mixed-voltage panel from one module. A 110V AC contactor coil, a 24V DC pilot light and a 220V AC solenoid can all hang on the same eight points without a voltage conversion in between — and with 0 mA off-state leakage, no loading resistor and no glowing LED pilots.

1769-IA16 Compact 16-point 120V AC input module IN STOCK
1769-IQ16 Compact 16-point 24V DC sink/source input module IN STOCK
1769-IQ32 Compact 32-point 24V DC sink/source input module IN STOCK
1769-OA16 Compact 16-point 120/240V AC output module IN STOCK
1769-OB16 Compact 16-point 24V DC output module IN STOCK
1769-OB32 Compact 32-point 24V DC output module IN STOCK
1769-OW16 Compact 16-point relay output module IN STOCK
1769-IF4 Compact 4-channel analog input module IN STOCK
1769-IF8 Compact 8-channel analog input module IN STOCK
1769-IF16C Compact 16-channel current input module IN STOCK
1769-OF4 Compact 4-channel analog output module IN STOCK
1769-OF8V Compact 8-channel voltage output module IN STOCK
1769-OF8C Compact 8-channel current output module IN STOCK
1769-ARM Compact address reserve module IN STOCK

Product Specifications 1769-OW8 (PDF)
 Application
 Compact I/O, 1769 bus
 Cat Num
 1769-OW8
 Brand Name
 Rockwell
 Outputs
 8 normally open (4 points per group)
 Operating voltage range
 5…265V AC
 Delay, on / off
 10 ms / 10 ms
 Current draw @ 5.1V
 125 mA
 Current draw @ 24V
 100 mA
 Heat dissipation, max
 2.83 W
 Off-state leakage, max
 0 mA
 On-state current, min
 10 mA @ 5V DC
 Current per point, max
 2.5 A
 Current per module, max
 16 A
 Contact rating, 240V AC
 2.5 A continuous; make 7.5 A, break 0.75 A; 1800 VA make / 180 VA break; NEMA C300
 Contact rating, 120V AC
 Make 15 A, break 1.5 A
 Contact rating, 125V DC
 1.0 A continuous; break 0.22 A; 28 VA; NEMA R150
 Contact rating, 24V DC
 2.0 A continuous; break 1.2 A; 28 VA
 Isolation
 1836V AC 1 s or 2596V DC 1 s, point to bus and group to group; 265V AC working voltage (IEC Class II reinforced)
 Slot width / weight
 1 slot / 280 g

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1769-OW8 Compact I/O 8-point AC/DC relay output module, factory packaging 1769-OW8 module, front view with terminal block 1769-OW8 label detail showing catalog number

Where the module sits in a CompactLogix system

Bank and supply. 125 mA at 5.1V plus 100 mA at 24V, 2.83 W, one slot, eight-module distance rating; the 24V draw is the relay coil supply, not the field load. Two groups of four. Each group has a VAC-VDC common terminal; contacts are dry, so the user supplies the switching voltage on that terminal. Reinforced isolation. 1836V AC for 1 s point to bus and group to group, with 265V AC working voltage under IEC Class II reinforced insulation — this is what allows a 230V field circuit on the same card as a 24V logic bus.

Contact rules that decide the wiring

Published field range is AC. The specification table for the OW8 gives 5…265V AC only, while the same page publishes 125V DC and 24V DC contact ratings. For DC loads use the 28 VA rule below and confirm the current draw with the relay datasheet rather than assuming a DC range. 28 VA rule on DC. Make/break amperes equal 28 VA divided by the applied DC voltage (28 VA / 48V = 0.58 A), and below 48V DC the make/break rating cannot exceed 2 A regardless of the arithmetic. 10 mA minimum. A contact will not wet reliably under 10 mA at 5V DC; a low-current input needs a parallel resistor or a different module. Contact life. Suppressors across inductive field loads extend relay life — the specification footnote says so directly, and it is the cheapest maintenance decision in the panel.

Commissioning in four checks

Confirm each group's VAC-VDC terminal carries the voltage the drawing intends; the contacts are dry and will switch whatever is wired to them. Check per-point current stays at or under 2.5 A and the module total under 16 A across all eight points. Fit an RC suppressor across every AC coil and a diode across every DC coil — it is what turns a relay module into a long-life relay module. Torque terminals at 0.68 N·m (6 lb·in), 22…14 AWG solid or 22…16 AWG stranded copper rated 90 °C.

Which Compact I/O relay output to specify

1769-OW8 — 8 NO contacts, 4 per group, 16 A per module, 1 slot, RTBN10. 1769-OW8I — same eight points, but individually isolated and rated for 5…125V DC as well. 1769-OW16 — 16 NO contacts, 8 per group, 20 A per module, 1.5 slots. Density and isolation are the two axes: OW16 for point count, OW8I when each channel must float independently.

Matching the contact rating to the load in front of it

AC coil or contactor — 240V AC 2.5 A continuous is ample, but inrush is the real figure: 7.5 A make covers a small contactor coil, not a 3-phase motor starter. Incandescent lamp — cold filament draws ten times running current; the 15 A make rating at 120V AC is what makes a lamp load survivable. DC solenoid — the 28 VA rule governs: at 48V DC that is 0.58 A make, capped at 2 A below 48V. Low-level signal — under 10 mA the contact will not wet reliably; use the module's logic side or a solid-state output instead.

FAQ — 1769-OW8

How much current can 1769-OW8 switch?

2.5 A per point continuous and 16 A per module. At 240V AC the contact rating is 2.5 A continuous with 7.5 A make and 0.75 A break, 1800 VA make / 180 VA break, NEMA C300.

Can 1769-OW8 switch DC loads?

The published operating range is 5…265V AC. The same page gives 125V DC (1.0 A continuous, 0.22 A break, 28 VA, R150) and 24V DC (2.0 A continuous, 1.2 A break, 28 VA) contact ratings, with the 28 VA rule — divide 28 VA by the DC voltage, capped at 2 A below 48V DC.

Why is 1769-OW8 leakage 0 mA?

These are mechanical relay contacts, not solid-state outputs, so there is no off-state leakage and no need for a loading resistor on a small load.

What is the minimum load for 1769-OW8?

10 mA at 5V DC. A contact will not wet reliably below that, so a very low-current input needs a parallel resistor.

What does 1769-OW8 draw from the backplane?

125 mA at 5.1V and 100 mA at 24V, with 2.83 W maximum heat dissipation, one slot, 280 g, eight-module distance rating.

What is the isolation rating of 1769-OW8?

1836V AC for 1 s or 2596V DC for 1 s, point to bus and group to group, with 265V AC working voltage under IEC Class II reinforced insulation.


Data sources. Technical values on this page come from Rockwell publication 1769-TD006 (1769 Compact I/O Modules Specifications) and 1769-SG001 (CompactLogix and Compact GuardLogix Systems Selection Guide), both current Rockwell Automation documents. Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.