logo
Home ProductsAB CompactLogix 1769

Allen Bradley PLC 1769-OW16 / 1769OW16

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1769-OW16 / 1769OW16

China Allen Bradley PLC 1769-OW16 / 1769OW16 supplier
Allen Bradley PLC 1769-OW16 / 1769OW16 supplier Allen Bradley PLC 1769-OW16 / 1769OW16 supplier Allen Bradley PLC 1769-OW16 / 1769OW16 supplier Allen Bradley PLC 1769-OW16 / 1769OW16 supplier Allen Bradley PLC 1769-OW16 / 1769OW16 supplier Allen Bradley PLC 1769-OW16 / 1769OW16 supplier

Large Image :  Allen Bradley PLC 1769-OW16 / 1769OW16

Product Details:

Place of Origin: Made in MALAYSIA
Brand Name: Rockwell
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1769-OW16 / 1769OW16

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $230.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 10 PCS
Detailed Product Description

1769-OW16 technical data PDF download CompactLogix 1769-OW16 / 1769OW16 16-Point AC/DC Relay Output Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC I/O

The 1769-OW16 (also written 1769OW16) is the sixteen-point relay contact output of the Compact I/O 1769 range: normally open contacts rated 5…265V AC and 5…125V DC, grouped eight per common, so AC and DC loads can be switched from the same slice — even on separate supplies.

It is the module to specify when the load is unknown at design time, when a DC and an AC circuit must be driven from one rack, or when zero off-state leakage is required. What it gives up is speed: 10 ms on and 10 ms off against 0.1 ms on a DC solid-state output.

1769-IA16 Compact 16-point 120V AC input module IN STOCK
1769-IQ16 Compact 16-point 24V DC sink/source input module IN STOCK
1769-IQ32 Compact 32-point 24V DC sink/source input module IN STOCK
1769-OA16 Compact 16-point 120/240V AC output module IN STOCK
1769-OB16 Compact 16-point 24V DC output module IN STOCK
1769-OB32 Compact 32-point 24V DC output module IN STOCK
1769-OW16 Compact 16-point relay output module IN STOCK
1769-IF4 Compact 4-channel analog input module IN STOCK
1769-IF8 Compact 8-channel analog input module IN STOCK
1769-IF16C Compact 16-channel current input module IN STOCK
1769-OF4 Compact 4-channel analog output module IN STOCK
1769-OF8V Compact 8-channel voltage output module IN STOCK
1769-OF8C Compact 8-channel current output module IN STOCK
1769-ARM Compact address reserve module IN STOCK

Product Specifications 1769-OW16 (PDF)
 Application
 Compact I/O, 1769 bus
 Cat Num
 1769-OW16
 Brand Name
 Rockwell
 Outputs
 16 normally open relay contacts (8 points per group)
 Operating voltage range
 5…265V AC; 5…125V DC
 Delay, on / off
 10 ms / 10 ms
 Current draw @ 5.1V
 205 mA
 Current draw @ 24V
 180 mA
 Heat dissipation, max
 4.75 W
 Off-state leakage, max
 0 mA
 On-state current, min
 10 mA @ 5V DC
 Current per point, max
 2.5 A
 Current per module, max
 20 A
 Relay rating, 240V AC
 2.5 A continuous; make 7.5 A, break 0.75 A; 1800 VA / 180 VA; NEMA C300
 Relay rating, 120V AC
 15 A make, 1.5 A break
 Relay rating, 125V DC
 1.0 A continuous; make/break 0.22 A; 28 VA; NEMA R150
 Isolation
 1836V AC 1 s or 2596V DC 1 s, output point to bus and group to group; 265V AC working voltage
 Slot width / weight
 1.5 slot / 450 g

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1769-OW16 Compact I/O 16-point AC/DC relay output module, factory packaging 1769-OW16 module, front view with terminal block 1769-OW16 label detail showing catalog number

Where the module sits in a CompactLogix system

Bank and supply. 205 mA at 5.1V and 180 mA at 24V from the bank supply, 4.75 W, one and a half slots, eight-module distance rating. True contact isolation. Off-state leakage is 0 mA, and group-to-group isolation is rated 1836V AC. That is the reason relay outputs survive on circuits where a triac or transistor output leaks enough to keep a pilot lit or a small relay picked up. AC and DC on one module. Each group has its own VAC-VDC terminal, so group one can switch 230V AC contactors while group two switches 24V DC solenoids.

Contact ratings that decide the wiring

Per point 2.5 A, per module 20 A. Continuous rating, not make/break. Thirty-two amps of connected load will exceed the module long before any single point reaches 2.5 A. Make and break are separate numbers. At 240V AC the contact makes 7.5 A but breaks 0.75 A; at 120V AC, 15 A make and 1.5 A break. Sizing on the continuous rating alone is how contacts weld on an inductive load. DC is derated hard. 28 VA is the DC switching allowance: at 48V DC that is 0.58 A, and below 48V the make/break rating may not exceed 2 A. A 125V DC circuit is limited to 1.0 A continuous and 0.22 A make/break. Minimum load 10 mA at 5V DC. Dry contacts need wetting current; a PLC input with very high impedance may not be enough on its own.

Commissioning in four checks

Compute the make/break current of each load, not just its steady current — a contactor coil's inrush is the number that shortens contact life. Confirm the group supply terminals are wired to the voltage each group's loads actually use, and that AC groups are not sharing a terminal with DC loads. Add a surge suppressor across every inductive load; the specification states that it extends contact life, and it is the cheapest maintenance measure available. Torque terminals at 0.68 N·m (6 lb·in) with 22…14 AWG solid copper rated 90 °C, and check that total connected load stays under 20 A per module.

Substituting or replacing a 1769-OW16

1769-OW8 — eight contacts, four per group, 125 mA at 5.1V, 100 mA at 24V, 2.83 W, 16 A per module. 1769-OW8I — eight individually isolated contacts, 290 g, for points that must not share a common. 1769-OA16 / 1769-OB16 — solid-state AC triac or 24V DC source output, 0.1 ms to half-cycle switching, no contact wear, but with leakage. Where a load switches often, a solid-state output plus an external interposing relay outlives a relay card; where the load is unknown or mixed AC/DC, this module is the flexible answer.

Which Compact I/O contact output to specify

1769-OW16 — 16 normally open contacts, 8 per group, 20 A per module, 450 g. 1769-OW8 — 8 contacts, 4 per group, 125 mA at 5.1V, 16 A per module. 1769-OW8I — 8 individually isolated contacts for points that must not share a common. 1769-OA16 / 1769-OB16 — solid-state alternatives when switching speed matters more than contact wear. Count the AC and DC loads separately before choosing: one 1769-OW16 can carry both, but each group still has a single supply terminal.

FAQ — 1769-OW16

How many outputs does 1769-OW16 have?

Sixteen normally open relay contacts in two groups of eight, each group with its own AC/DC supply terminal so AC and DC loads can be mixed on one module.

What voltage range can 1769-OW16 switch?

5…265V AC and 5…125V DC, with 2.5 A continuous per point and 20 A per module.

What are the make and break ratings of 1769-OW16?

At 240V AC: 7.5 A make, 0.75 A break, 1800 VA make, NEMA C300. At 120V AC: 15 A make, 1.5 A break. At 125V DC: 1.0 A continuous, 0.22 A make/break, 28 VA.

Does 1769-OW16 have any off-state leakage?

No — 0 mA. That is its main advantage over triac and transistor outputs when a pilot light or small relay must be fully off.

What is the switching speed of 1769-OW16?

10 ms on and 10 ms off, set by the relay. It is not suitable for fast pulsing — use 1769-OB16 at 0.1 ms for that.

What does 1769-OW16 draw from the backplane?

205 mA at 5.1V and 180 mA at 24V from the bank supply, with 4.75 W maximum heat dissipation, one and a half slots, 450 g.

Why do 1769-OW16 contacts wear out quickly?

Usually because the load was sized on continuous current rather than make/break, or because an inductive load has no suppressor. 28 VA is the DC switching allowance, and a reverse diode or RC suppressor across the coil is the standard fix.


Data sources. Technical values on this page come from Rockwell publication 1769-TD006 (1769 Compact I/O Modules Specifications) and 1769-SG001 (CompactLogix and Compact GuardLogix Systems Selection Guide), both current documents. Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Related numbers