Product Details:
Payment & Shipping Terms:
|
The 1769-OW16 (also written 1769OW16) is the sixteen-point relay contact output of the Compact I/O 1769 range: normally open contacts rated 5…265V AC and 5…125V DC, grouped eight per common, so AC and DC loads can be switched from the same slice — even on separate supplies.
It is the module to specify when the load is unknown at design time, when a DC and an AC circuit must be driven from one rack, or when zero off-state leakage is required. What it gives up is speed: 10 ms on and 10 ms off against 0.1 ms on a DC solid-state output.
| 1769-IA16 | Compact 16-point 120V AC input module | IN STOCK |
| 1769-IQ16 | Compact 16-point 24V DC sink/source input module | IN STOCK |
| 1769-IQ32 | Compact 32-point 24V DC sink/source input module | IN STOCK |
| 1769-OA16 | Compact 16-point 120/240V AC output module | IN STOCK |
| 1769-OB16 | Compact 16-point 24V DC output module | IN STOCK |
| 1769-OB32 | Compact 32-point 24V DC output module | IN STOCK |
| 1769-OW16 | Compact 16-point relay output module | IN STOCK |
| 1769-IF4 | Compact 4-channel analog input module | IN STOCK |
| 1769-IF8 | Compact 8-channel analog input module | IN STOCK |
| 1769-IF16C | Compact 16-channel current input module | IN STOCK |
| 1769-OF4 | Compact 4-channel analog output module | IN STOCK |
| 1769-OF8V | Compact 8-channel voltage output module | IN STOCK |
| 1769-OF8C | Compact 8-channel current output module | IN STOCK |
| 1769-ARM | Compact address reserve module | IN STOCK |
Application |
Compact I/O, 1769 bus |
Cat Num |
1769-OW16 |
Brand Name |
Rockwell |
Outputs |
16 normally open relay contacts (8 points per group) |
Operating voltage range |
5…265V AC; 5…125V DC |
Delay, on / off |
10 ms / 10 ms |
Current draw @ 5.1V |
205 mA |
Current draw @ 24V |
180 mA |
Heat dissipation, max |
4.75 W |
Off-state leakage, max |
0 mA |
On-state current, min |
10 mA @ 5V DC |
Current per point, max |
2.5 A |
Current per module, max |
20 A |
Relay rating, 240V AC |
2.5 A continuous; make 7.5 A, break 0.75 A; 1800 VA / 180 VA; NEMA C300 |
Relay rating, 120V AC |
15 A make, 1.5 A break |
Relay rating, 125V DC |
1.0 A continuous; make/break 0.22 A; 28 VA; NEMA R150 |
Isolation |
1836V AC 1 s or 2596V DC 1 s, output point to bus and group to group; 265V AC working voltage |
Slot width / weight |
1.5 slot / 450 g |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
How many outputs does 1769-OW16 have?
Sixteen normally open relay contacts in two groups of eight, each group with its own AC/DC supply terminal so AC and DC loads can be mixed on one module.
What voltage range can 1769-OW16 switch?
5…265V AC and 5…125V DC, with 2.5 A continuous per point and 20 A per module.
What are the make and break ratings of 1769-OW16?
At 240V AC: 7.5 A make, 0.75 A break, 1800 VA make, NEMA C300. At 120V AC: 15 A make, 1.5 A break. At 125V DC: 1.0 A continuous, 0.22 A make/break, 28 VA.
Does 1769-OW16 have any off-state leakage?
No — 0 mA. That is its main advantage over triac and transistor outputs when a pilot light or small relay must be fully off.
What is the switching speed of 1769-OW16?
10 ms on and 10 ms off, set by the relay. It is not suitable for fast pulsing — use 1769-OB16 at 0.1 ms for that.
What does 1769-OW16 draw from the backplane?
205 mA at 5.1V and 180 mA at 24V from the bank supply, with 4.75 W maximum heat dissipation, one and a half slots, 450 g.
Why do 1769-OW16 contacts wear out quickly?
Usually because the load was sized on continuous current rather than make/break, or because an inductive load has no suppressor. 28 VA is the DC switching allowance, and a reverse diode or RC suppressor across the coil is the standard fix.