logo
Home ProductsAB CompactLogix 1769

Allen Bradley PLC 1769-OB32T / 1769OB32T

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1769-OB32T / 1769OB32T

China Allen Bradley PLC 1769-OB32T / 1769OB32T supplier
Allen Bradley PLC 1769-OB32T / 1769OB32T supplier Allen Bradley PLC 1769-OB32T / 1769OB32T supplier Allen Bradley PLC 1769-OB32T / 1769OB32T supplier Allen Bradley PLC 1769-OB32T / 1769OB32T supplier Allen Bradley PLC 1769-OB32T / 1769OB32T supplier

Large Image :  Allen Bradley PLC 1769-OB32T / 1769OB32T

Product Details:

Place of Origin: Made in MALAYSIA
Brand Name: Rockwell
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1769-OB32T / 1769OB32T

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $275.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 25 PCS
Detailed Product Description

1769-OB32T technical data PDF download CompactLogix 1769-OB32T / 1769OB32T 32-Point Terminated 24V DC Output Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC I/O

The 1769-OB32T (also written 1769OB32T) is the terminated thirty-two point 24V DC sourcing output: sixteen points per group on a 1746-N3 connector, one slot, 230 g, and an off-state leakage of 0.1 mA where every other 24V DC output in the family leaks 1.0 mA.

Two other published figures set it apart. The field range starts at 10.2V DC rather than 20.4V, so it keeps working on a battery-backed or sagging rail, and the drop is 0.3V DC at 0.5 A rather than 1.0V — which is why it can hold a 24V valve that a standard module leaves at 23V.

1769-IA16 Compact 16-point 120V AC input module IN STOCK
1769-IQ16 Compact 16-point 24V DC sink/source input module IN STOCK
1769-IQ32 Compact 32-point 24V DC sink/source input module IN STOCK
1769-OA16 Compact 16-point 120/240V AC output module IN STOCK
1769-OB16 Compact 16-point 24V DC output module IN STOCK
1769-OB32 Compact 32-point 24V DC output module IN STOCK
1769-OW16 Compact 16-point relay output module IN STOCK
1769-IF4 Compact 4-channel analog input module IN STOCK
1769-IF8 Compact 8-channel analog input module IN STOCK
1769-IF16C Compact 16-channel current input module IN STOCK
1769-OF4 Compact 4-channel analog output module IN STOCK
1769-OF8V Compact 8-channel voltage output module IN STOCK
1769-OF8C Compact 8-channel current output module IN STOCK
1769-ARM Compact address reserve module IN STOCK

Product Specifications 1769-OB32T (PDF)
 Application
 Compact I/O, 1769 bus
 Cat Num
 1769-OB32T
 Brand Name
 Rockwell
 Outputs
 32 terminated (16 points per group)
 Voltage category
 24V DC source
 Operating voltage range
 10.2…26.4V DC
 Output delay, on / off
 0.5 ms / 4.0 ms
 Current draw @ 5.1V
 220 mA
 Heat dissipation, max
 4.76 W
 Off-state leakage, max
 0.1 mA @ 26.4V DC
 On-state current, min
 1.0 mA
 On-state voltage drop, max
 0.3V DC @ 0.5 A
 Current per point, max
 0.5 A
 Current per module, max
 4.0 A
 Surge current
 2.0 A for 10 ms, repeatable every 2 s
 Isolation
 1200V AC 2 s or 1697V DC 2 s, point to bus; 75V DC working voltage
 Slot width / weight
 1 slot / 230 g

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1769-OB32T Compact I/O 32-point terminated 24V DC output module, factory packaging 1769-OB32T module, front view with terminator 1769-OB32T label detail showing catalog number

Where the module sits in a CompactLogix system

Bank and supply. 220 mA at 5.1V, 4.76 W, one slot, eight-module distance rating; the terminated connector buys back the half slot the 1769-OB32 spends. Two groups of sixteen. Each group has its own +VDC and DC common, isolated to 1200V AC for 2 seconds — note the isolation test time is 2 s here, not the 1 s of the screw-terminal modules. <Wide field range. 10.2…26.4V DC is the published window, so a 12V rail inside that range is usable, and a 24V supply in deep sag still drives the load.

Load rules that decide the wiring

Current per point 0.5 A, per module 4.0 A, no temperature split. Unlike the 1769-OB32, the T variant publishes a single pair of figures rather than 60 °C / 30 °C columns — 4.0 A per module is the hard limit. 0.1 mA leakage. Ten times lower than the standard modules; small relays and LED pilots that glow on other 1769 outputs will stay off here. Drop 0.3V at 0.5 A. Half a volt more at the load than the 1769-OB32 delivers, which is often the difference between a valve picking up and not. Off delay 4.0 ms. The slowest off-time in the 24V DC output family; on-time is 0.5 ms. A 32-point module on a 4 ms release is not a fast-pulse device.

Commissioning in four checks

Confirm the 1746-N3 connector is fully latched and every wire is on the intended terminal — 40 terminals, sixteen per group, is where one-off errors hide. Add the group loads and check the module total stays under 4.0 A; there is no 30 °C allowance to lean on here. Check the release time the sequence needs against 4.0 ms off delay before commissioning a fast interlock. Torque terminals at 0.68 N·m (6 lb·in), 22…14 AWG solid or 22…16 AWG stranded copper rated 90 °C.

Substituting or replacing a 1769-OB32T

1769-OB32 — screw terminals, 1.5 slots, 300 mA, 0.1 / 1.0 ms, 1.0V drop, six-module distance rating. 1769-OB16 — sixteen screw-terminal points, 200 mA, 0.1 / 1.0 ms, eight-module rating. 1769-OV32T — the sinking counterpart, 10.2…26.4V DC, 0.3V drop, same connector. The T family trades switching speed for connector density and low leakage; a fast pulse train belongs on 1769-OB16, not here.

Which Compact I/O 32-point output to specify

1769-OB32T — 32 terminated sourcing points, 0.1 mA leakage, 10.2…26.4V DC, 220 mA. 1769-OB32 — 32 screw-terminal points, 1.0 mA leakage, 20.4…26.4V DC, 300 mA, 6-module distance rating. 1769-OB16 — 16 points when 32 is more than the machine needs and speed matters. Pre-wired 1746-N3 panels and low-leakage requirements point to the T; marginal field voltage and screw terminals point to the standard module.

FAQ — 1769-OB32T

What does the T mean in 1769-OB32T?

Terminated: it uses a 1746-N3 connector of 40 terminals, which is how 32 points fit into a single slot at 230 g.

What is the off-state leakage of 1769-OB32T?

0.1 mA at 26.4V DC — ten times lower than the 1.0 mA of the other 1769 24V DC outputs, so small relays and LED pilots stay off.

What field voltage range does 1769-OB32T accept?

10.2…26.4V DC, wider at the bottom than the 20.4V of the screw-terminal modules.

What are the switching times of 1769-OB32T?

0.5 ms on and 4.0 ms off — the slowest release in the 1769 24V DC output family.

What current can 1769-OB32T carry?

0.5 A per point and 4.0 A per module, published as single figures with no 30 °C / 60 °C split.

What is the on-state voltage drop of 1769-OB32T?

0.3V DC at 0.5 A, against 1.0V on the standard 1769-OB32 — more voltage at the load for the same supply.


Data sources. Technical values on this page come from Rockwell publication 1769-TD006 (1769 Compact I/O Modules Specifications) and 1769-SG001 (CompactLogix and Compact GuardLogix Systems Selection Guide), both current Rockwell Automation documents. Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)