Product Details:
Payment & Shipping Terms:
|
The 1769-OA8 (also written 1769OA8) is the eight-point triac output of the Compact I/O 1769 range: four points per group, two groups each with its own AC supply terminal, switching 100/240V AC loads directly from the controller.
Its surge rating is the reason it exists alongside the sixteen-point 1769-OA16: 10 A for 25 ms against 5 A on the OA16. Same per-point and per-module current, same zero-cross switching, but twice the lamp or solenoid inrush allowance — which matters when the load is an incandescent lamp bank rather than a contactor coil.
| 1769-IA16 | Compact 16-point 120V AC input module | IN STOCK |
| 1769-IQ16 | Compact 16-point 24V DC sink/source input module | IN STOCK |
| 1769-IQ32 | Compact 32-point 24V DC sink/source input module | IN STOCK |
| 1769-OA16 | Compact 16-point 120/240V AC output module | IN STOCK |
| 1769-OB16 | Compact 16-point 24V DC output module | IN STOCK |
| 1769-OB32 | Compact 32-point 24V DC output module | IN STOCK |
| 1769-OW16 | Compact 16-point relay output module | IN STOCK |
| 1769-IF4 | Compact 4-channel analog input module | IN STOCK |
| 1769-IF8 | Compact 8-channel analog input module | IN STOCK |
| 1769-IF16C | Compact 16-channel current input module | IN STOCK |
| 1769-OF4 | Compact 4-channel analog output module | IN STOCK |
| 1769-OF8V | Compact 8-channel voltage output module | IN STOCK |
| 1769-OF8C | Compact 8-channel current output module | IN STOCK |
| 1769-ARM | Compact address reserve module | IN STOCK |
Application |
Compact I/O, 1769 bus |
Cat Num |
1769-OA8 |
Brand Name |
Rockwell |
Outputs |
8 (4 points per group) |
Voltage category |
100/240V AC |
Operating voltage range |
85…265V AC, 47…63 Hz |
Output delay, on / off |
1/2 cycle / 1/2 cycle |
Current draw @ 5.1V |
145 mA |
Heat dissipation, max |
2.12 W |
Off-state leakage, max |
2.0 mA @ 132V AC; 2.5 mA @ 265V AC |
On-state current, min |
10 mA |
On-state voltage drop, max |
1.5V peak @ 2 A |
Current per point |
0.25 A @ 60 °C; 0.5 A @ 30 °C |
Current per module |
2 A @ 60 °C; 4 A @ 30 °C |
Surge current |
10 A for 25 ms, repeatable every 2 s |
Isolation |
1836V AC 1 s or 2596V DC 1 s, group to group; 265V AC working voltage |
Slot width / weight |
1 slot / 280 g |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
How many outputs does 1769-OA8 have?
Eight, in two groups of four, each group with its own AC supply terminal for a separate feed.
What is the surge rating of 1769-OA8?
10 A for 25 ms, repeatable every 2 s — twice the 5 A rating of the 16-point 1769-OA16, which is the main reason to choose it for lamp loads.
What is the minimum load for 1769-OA8?
10 mA holding current. A smaller contactor coil will not latch reliably; a loading resistor across the coil or a relay output module is the fix.
What does 1769-OA8 draw from the backplane?
145 mA at 5.1V with 2.12 W maximum heat dissipation, one slot, 280 g, eight-module distance rating.
What AC voltage range does 1769-OA8 switch?
85…265V AC at 47…63 Hz, rated 100/240V AC, with half-cycle zero-cross switching on and off.
How do I stop a 1769-OA8 output from glowing when it is off?
Fit the loading resistor the specification gives: 15 kΩ 2 W in parallel with the load at 120V AC, or 5 kΩ 5 W at 240V AC, to absorb the 2.0…2.5 mA off-state leakage.