logo
Home ProductsAB CompactLogix 1769

Allen Bradley PLC 1769-IF4I / 1769IF4I

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1769-IF4I / 1769IF4I

China Allen Bradley PLC 1769-IF4I / 1769IF4I supplier
Allen Bradley PLC 1769-IF4I / 1769IF4I supplier Allen Bradley PLC 1769-IF4I / 1769IF4I supplier Allen Bradley PLC 1769-IF4I / 1769IF4I supplier Allen Bradley PLC 1769-IF4I / 1769IF4I supplier Allen Bradley PLC 1769-IF4I / 1769IF4I supplier

Large Image :  Allen Bradley PLC 1769-IF4I / 1769IF4I

Product Details:

Place of Origin: Made in MALAYSIA
Brand Name: Rockwell
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1769-IF4I / 1769IF4I

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $522.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 10 PCS
Detailed Product Description

1769-IF4I technical data PDF download CompactLogix 1769-IF4I / 1769IF4I 4-Channel Isolated Analog Input Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC I/O

The 1769-IF4I (also written 1769IF4I) is the four-channel analog input where every channel is isolated from every other: 500V AC for one minute, or 250V continuous, channel to rack and channel to channel.

That is what makes mixed transmitters legal on one card — a grounded thermocouple amplifier on channel 0, a loop-powered pressure transmitter on channel 1, a floating voltage signal on channel 2 — with no common node required between them. On a 1769-IF4 all four inputs share analog common, and one grounded source typically forces the rest of the wiring to follow it.

1769-IA16 Compact 16-point 120V AC input module IN STOCK
1769-IQ16 Compact 16-point 24V DC sink/source input module IN STOCK
1769-IQ32 Compact 32-point 24V DC sink/source input module IN STOCK
1769-OA16 Compact 16-point 120/240V AC output module IN STOCK
1769-OB16 Compact 16-point 24V DC output module IN STOCK
1769-OB32 Compact 32-point 24V DC output module IN STOCK
1769-OW16 Compact 16-point relay output module IN STOCK
1769-IF4 Compact 4-channel analog input module IN STOCK
1769-IF8 Compact 8-channel analog input module IN STOCK
1769-IF16C Compact 16-channel current input module IN STOCK
1769-OF4 Compact 4-channel analog output module IN STOCK
1769-OF8V Compact 8-channel voltage output module IN STOCK
1769-OF8C Compact 8-channel current output module IN STOCK
1769-ARM Compact address reserve module IN STOCK

Product Specifications 1769-IF4I (PDF)
 Application
 Compact I/O, 1769 bus
 Cat Num
 1769-IF4I
 Brand Name
 Rockwell
 Inputs
 4 isolated differential
 Input range
 ±10V, 0…10V, 0…5V, 1…5V, 0…20 mA, 4…20 mA
 Full-scale range
 ±10.5V, −0.5…10.5V, −0.5…5.25V, 0.5…5.25V, 0…21 mA, 3.2…21 mA
 Bus current draw
 5V DC 140 mA; 24V DC 110 mA
 Heat dissipation, max
 3.0 W
 Converter type
 Delta Sigma
 Resolution
 16 bits (unipolar); 15 bits plus sign (bipolar)
 Common mode rejection
 > 60 dB @ 50 Hz and 60 Hz with the 10 Hz filter
 Input impedance
 Voltage 1 MΩ; current 249 Ω
 Accuracy
 Voltage ±0.2% FS; current ±0.35% FS @ 25 °C
 Accuracy drift with temperature
 Voltage ±0.003% per °C; current ±0.0045% per °C
 Nonlinearity / repeatability
 ±0.03% / ±0.03%
 Overload at input terminals, max
 Voltage ±24V DC continuous, 0.1 mA; current ±28 mA continuous, ±7.6V DC
 Isolation, group to bus
 500V AC or 710V DC for 1 min (qualification); 30V AC/30V DC working
 Isolation, channel to channel
 500V AC or 710V DC for 1 min, or 250V continuous (optical and magnetic), channel to rack and channel to channel
 Slot width / weight
 1 slot / 300 g

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1769-IF4I Compact I/O 4-channel individually isolated analog input module, factory packaging 1769-IF4I module, front view with terminal block 1769-IF4I label detail showing catalog number

Where the module sits in a CompactLogix system

Bank and supply. 140 mA at 5.1V plus 110 mA at 24V, 3.0 W, one slot, eight-module distance rating; the 24V draw is the isolated supply for the input stages. Four isolated differential inputs. Voltage and current ranges on every channel, 1 MΩ for voltage and 249 Ω for current, independently configurable. Isolation beyond group to bus. 30V working group to bus, but 250V DC continuous between channels — the figure that matters when channels come from different panels.

Accuracy and speed in the published tables

±0.2% FS voltage, ±0.35% FS current at 25 °C. The tightest analog input accuracy in the 1769 range, matched only by 1769-IF4FXOF2F. <Drift 0.003 / 0.0045% per °C. Twenty-five percent better than the non-isolated 1769-IF4 on voltage, because there is no shared multiplexer in front of the channels. Fastest filter set in the family. 28.5 Hz 108 ms, 50 Hz 62 ms, 60 Hz 52 ms, 300 Hz 12 ms, 360 Hz 10 ms channel update — the 360 Hz setting is the fastest of any 1769 analog input. Overload ±24V DC on voltage. Lower than the ±30V of the non-isolated card — the isolation barrier is what limits it.

Commissioning in four checks

Check each channel's source type before wiring: a grounded source on an isolated channel is safe, a grounded source on a non-isolated card is a design constraint for all four. Confirm the 10 Hz filter is selected where 50/60 Hz rejection matters; the 60 dB common-mode rejection figure is published with that filter. Set the range per channel — voltage and current coexist on this card without a shunt resistor. Torque terminals at 0.68 N·m (6 lb·in); use shielded cable per the wiring diagrams and land the drain at the module end.

Which isolated analog input to specify

1769-IF4I — 4 isolated differential channels, voltage and current, ±0.2% FS voltage. 1769-IF4 — 4 channels sharing analog common, 120 mA, cheaper when all sources share a return. 1769-IF8 — 8 channels, differential or single-ended, group-isolated but not channel-isolated. Channel-to-channel isolation is the property that cannot be added later; when the field sources come from separate panels, this is the card.

What channel-to-channel isolation buys in the panel

A grounded source on one channel no longer dictates the rest. On a shared-common card, one earthed thermocouple amplifier usually pulls every input to that reference. Separate panel sections can share a card. A skid panel at 0V-A and a machine panel at 0V-B meet only at the isolation barrier, with 250V DC continuous channel to channel. Loop-powered and self-powered transmitters coexist. Two-wire loops, four-wire loops and a 0…10V signal from a drive can sit on the same four terminals. What it does not buy. Group-to-bus isolation stays at 30V working voltage, so the module as a whole is still referenced to the bank's ground.

FAQ — 1769-IF4I

What does the I mean in 1769-IF4I?

Individually isolated: each of the four channels is isolated from the others at 500V AC for 1 minute or 250V continuous, channel to rack and channel to channel.

What is the accuracy of 1769-IF4I?

±0.2% of full scale on voltage and ±0.35% on current at 25 °C, the tightest of the 1769 analog inputs, with ±0.003% and ±0.0045% per °C drift.

How fast does 1769-IF4I update?

Channel update is Ff-dependent: 108 ms at 28.5 Hz, 62 ms at 50 Hz, 52 ms at 60 Hz, 12 ms at 300 Hz and 10 ms at 360 Hz — the fastest analog filter setting in the family.

Can 1769-IF4I mix voltage and current inputs?

Yes — all six ranges (±10V, 0…10V, 0…5V, 1…5V, 0…20 mA, 4…20 mA) are available per channel, with 1 MΩ on voltage and 249 Ω on current.

What is the isolation rating of 1769-IF4I?

500V AC or 710V DC for 1 minute qualification, 250V continuous channel to rack and channel to channel, with 30V AC/30V DC group-to-bus working voltage.

What does 1769-IF4I draw from the backplane?

140 mA at 5.1V and 110 mA at 24V, 3.0 W maximum heat dissipation, one slot, 300 g, eight-module distance rating.


Data sources. Technical values on this page come from Rockwell publication 1769-TD006 (1769 Compact I/O Modules Specifications) and 1769-SG001 (CompactLogix and Compact GuardLogix Systems Selection Guide), both current Rockwell Automation documents. Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.