The 1794-IA16 puts sixteen 120V AC inputs on one FLEX I/O slot, at 10 mA and 10 kOhm per channel, with a 74V AC on threshold and 20V AC off threshold.
Sixteen points per slot is the reason to choose it over the 1794-IA8: a panel with a full row of 120V pushbuttons, selector switches and starter contacts fits one island instead of two.
| 1794-IA8 | 8-point 120V AC input module | IN STOCK |
| 1794-IA8I | 8-point 120V AC input module, 1240V isolation | IN STOCK |
| 1794-IA16 | 16-point 120V AC input module | IN STOCK |
| 1794-IA16K | 16-point 120V AC input module, conformal coated | IN STOCK |
| 1794-IM8 | 8-point 240V AC input module | IN STOCK |
| 1794-IM16 | 16-point 240V AC input module | IN STOCK |
| 1794-OA8 | 8-point 120V AC output module | IN STOCK |
| 1794-OA8I | 8-point 120V AC isolated output module | IN STOCK |
| 1794-OA8K | 8-point 120V AC output module, conformal coated | IN STOCK |
| 1794-OA16 | 16-point 220V AC output module | IN STOCK |
| 1794-OA16K | 16-point 220V AC output module, conformal coated | IN STOCK |
| 1794-OM8 | 8-point 240V AC output module | IN STOCK |
| 1794-OM16 | 16-point 240V AC output module | IN STOCK |
Application |
FLEX I/O digital input, 1794 terminal base |
Cat Num |
1794-IA16 |
Brand Name |
Rockwell |
Inputs |
16, AC |
Input voltage |
120V AC nominal |
On-state voltage |
74V AC minimum |
Off-state voltage |
20V AC maximum |
Input current |
10 mA at 120V AC |
Input impedance |
10 kOhm |
Input filter |
7.5...42 ms off to on, 26.5...60.5 ms on to off |
Isolation |
1264V AC for 60 s field to system; 2150V DC for 1 s routine test |
Power dissipation |
6.4 W at 132V AC (21.8 BTU/hr) |
Terminal base |
1794-TB3, -TB3S, -TBN, -TB3K, -TB3SK, -TBNK |
Operating temperature |
0...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
16 channels at 120V AC nominal, 10 mA each, 10 kOhm input impedance, with 74V AC on and 20V AC off thresholds.
74V AC is a high threshold compared with the 65V AC of the 8-point card, which rejects more of the noise a crowded 120V panel carries.
A 20V AC off threshold means an induced voltage from an adjacent cable has to reach 20V before a channel is held on — more margin than the 43V AC figure suggests at first reading.
The narrower on/off band is a deliberate trade: the card reads more decisively but is less tolerant of a circuit whose voltage sags below 74V under load.
10 mA per channel keeps the load on a mechanical switch low; sixteen channels at once draw 160 mA from the circuit, which most 120V control circuits supply without comment.
7.5...42 ms off to on and 26.5...60.5 ms on to off is the selectable range, set per module in the adapter or controller configuration.
The slowest setting cleans a contactor arc but a 40 ms pulse disappears in it; the response time has to be checked against the fastest real event on the machine.
One setting for all sixteen channels means a mixed panel of mechanical and solid-state devices compromises on a single value or splits across modules.
Filtering in the module keeps behaviour identical across ControlNet, EtherNet/IP and Remote I/O adapters.
Delay is not a fault symptom. A channel that responds late at a slow filter setting is working as configured; compare against the configured value before condemning the card.
1264V AC for 60 s is the type test between field and system, with a 2150V DC routine test at 1 s published alongside it.
Six bases: 1794-TB3, -TB3S, -TBN, -TB3K, -TB3SK and -TBNK; the TBN variants add fused terminals for the field circuit.
6.4 W at 132V AC (21.8 BTU/hr) is the worst-case dissipation, printed at the high line voltage rather than at nominal.
Base replacement is the serviceable part. The field terminals sit on the base, so a card swap does not disturb sixteen wires.
0...55 deg C operating range is narrower than the 8-point card's -20 deg C start; a cold-store panel is not this card's application.
Keep the 120V input wiring separate from analog and low-level signal cables; the 74V threshold helps, but a shared duct still couples switching transients.
Use the fused TBN base where the panel does not already protect each 120V circuit; a shorted field wire otherwise takes the common down with it.
Check the voltage at the terminal, not at the source: a long run that drops below 74V reads off and looks like a dead input.
Eight channel LEDs are yellow and show the filtered state — a lit LED with no signal in the program points at the adapter or the mapping, not at the field.
Group returns per circuit where the panel allows it, so one grounded sensor cannot put its ground on all sixteen channels.
Set the key, push the FlexBus connector fully left, inspect the bottom pins, align the module with the base groove, then press until the latch locks.
Do not insert or remove a module with the island powered unless the publication for that adapter explicitly allows RIUP; the general rule in 1794-IN093 is to remove field power first.
The general environmental ratings apply: -40...85 deg C storage, 5...95% RH non-condensing, 5 g vibration at 10...500 Hz, 30 g shock.
EMC compliance is IEC 61000-6-4 for the system, with 10 V/m radiated immunity from 80 to 6000 MHz and 2 kV EFT on signal ports.
Certificate numbers are on the label, and the ATEX and IECEx markings are type approvals of the module and base combination, not of the enclosure.
How many inputs has the 1794-IA16?
Sixteen 120V AC inputs at 10 mA each, 10 kOhm impedance.
What are the thresholds?
74V AC minimum to read on and 20V AC maximum to read off.
What filter range is available?
7.5...42 ms off to on and 26.5...60.5 ms on to off, selectable per module.
Which bases fit the 1794-IA16?
1794-TB3, -TB3S, -TBN, -TB3K, -TB3SK and -TBNK.
What is the isolation rating?
1264V AC for 60 s field to system, type tested, with a 2150V DC for 1 s routine test.
What temperature range does it accept?
0...55 deg C operating, against -20...55 deg C on the 8-point AC input cards.