The 1794-PS13 is the smaller FLEX I/O supply: 120V or 220V AC in, 24V DC at 1.3 A out, in a housing 69 mm wide instead of 87 mm.
Its 36 W input and 53 VA apparent power make it the lighter choice for a single adapter with a few modules, where 3 A would never be used.
| 1794-TB2 | 16-terminal cage clamp base, 2-wire, up to 132V AC | IN STOCK |
| 1794-TB3 | 16-terminal cage clamp base, 3-wire devices | IN STOCK |
| 1794-TB3S | 16-terminal spring clamp base, 3-wire devices | IN STOCK |
| 1794-TB32 | 32-terminal cage clamp base for 32-point modules | IN STOCK |
| 1794-TB32S | 32-terminal spring clamp base for 32-point modules | IN STOCK |
| 1794-TB3T | temperature base with two cold junction compensation sets | IN STOCK |
| 1794-TB3TS | spring clamp temperature base with CJC sets | IN STOCK |
| 1794-TB3G | grounded screw clamp base, 36 I/O, 10 chassis ground | IN STOCK |
| 1794-TB3GS | grounded spring clamp base, 36 I/O, 10 chassis ground | IN STOCK |
| 1794-TBKD | cage clamp base with 16 knife disconnects | IN STOCK |
| 1794-TBN | NEMA-style screw clamp base, up to 264V AC/DC | IN STOCK |
| 1794-TBNF | fused NEMA-style base, eight 5 x 20 mm fuses | IN STOCK |
| 1794-TB37DS | 37-pin D-shell termination for digital and analog modules | IN STOCK |
| 1794-TB62DS | 62-pin D-shell termination for digital and analog modules | IN STOCK |
Application |
FLEX I/O adapter power supply, 1794 backplane |
Cat Num |
1794-PS13 |
Brand Name |
Rockwell |
Input voltage |
120V / 220V AC |
Input power |
36 W |
Apparent input power, max |
53 VA |
Transformer load, max |
90 VA |
Output |
24V DC, 1.3 A maximum |
Surge capability |
Four adapters at 23 A for 2 ms each |
Dimensions |
87 x 69 x 69 mm |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
24V DC at 1.3 A maximum from 120V or 220V AC, enough for one adapter with a modest module count.
36 W real input power, 53 VA apparent, 90 VA transformer load — a third of the PS3's transformer demand.
Output surge drives four adapters at 23 A for 2 ms each, against six on the 3 A unit.
87 x 69 x 69 mm saves 18 mm of rail width per supply, which matters on a crowded panel.
Sum the module currents from the selection guide at the supply voltage in use, and add output load current for output and analog output modules.
If 1.3 A is not enough, the guide's instruction is to add a second supply rather than to run the unit at its limit.
A single adapter handles up to eight modules internally, but the current they draw still has to come from the supply.
Counter output load power is best on a separate supply, for noise immunity.
The supply feeds the adapter, and the adapter distributes 24V over the backplane to the modules.
Use watts for enclosure heat and VA for distribution, both printed for this unit.
Non-Allen-Bradley supplies are permitted within the device specifications; 1606 units reach 40 A when a larger rail is needed.
The K version is conformally coated for the -XT extended-temperature modules.
Small islands — one adapter, a handful of modules.
Panels with limited rail space, where 18 mm per supply counts.
Not for a fully loaded adapter with 16-point cards and their load currents; check the sum first.
Not for output load power; that belongs in the current budget or on a separate supply.
1794-PS13: 1.3 A, 36 W, 53 VA, 90 VA transformer load, four adapters surge.
1794-PS3: 3.0 A, 86 W, 205 VA, 250 VA transformer load, six adapters surge.
Both are 120/220V AC input, 24V DC output, and both mount beside the adapter on the same rail.
Transformer load (VA) is quoted per supply and added to all other loads on the transformer.
What output does the 1794-PS13 provide?
24V DC at 1.3 A maximum from 120V or 220V AC.
How is it different from the 1794-PS3?
1.3 A instead of 3.0 A, 36 W instead of 86 W, and 69 mm wide instead of 87 mm.
How many adapters can it surge?
Four adapters at 23 A for 2 ms each.
What is the transformer load?
90 VA maximum, against 250 VA on the 1794-PS3.
What happens if the load exceeds 1.3 A?
Add a second supply, as the selection guide instructs.
Can it power field output loads?
No; output load current must be included in the supply calculation or fed separately.
1794-PS13 is a FLEX I/O rail power supply for the 1794 system, documented here from the Rockwell FlexLogix manual so that the input window, the three power figures and the output current are stated together rather than as a single headline number.
| Specification | Value |
|---|---|
| Catalog number | 1794-PS13 |
| Nominal input voltage | 120/230V AC |
| Input voltage range | 85 to 265V AC |
| Maximum real input power | 36 W |
| Maximum apparent input power | 53 VA |
| Maximum transformer load | 90 VA |
| Output | 24V DC at 1.3 A |
| Family comparison | 1794-PS3 delivers 3.0 A at 24V DC horizontally mounted, 2.8 A non-horizontal, with 86 W real, 205 VA apparent and 250 VA transformer load |
| Sharing rule | Controller power and FLEX I/O module power are supplied separately |
| SELV note | CSA compliant applications require a SELV supply per IEC 61010-1 Annex H |
| Rail capacity | FlexLogix supports up to 8 I/O modules on the local rail and 8 on the extended local rail; the extended local adapter is treated as a communication adapter in the power budget |
| Source | 1794-UM001G-EN-P FlexLogix controller user manual, selecting a power supply |
One and three tenths of an amp is enough for a small rail of digital modules and not enough for a rail with analog modules and field loads. The larger 1794-PS3 at three amps is the alternative, and the manual publishes the vertical mounting derating to 2.8 A in the same table.
The three power figures are not interchangeable. Thirty six watts real, fifty three volt amperes apparent and ninety volt amperes transformer load describe the same unit from three angles, and the transformer figure is the one an upstream device has to be selected against.
A rail supply is judged on four published numbers: the input window, the real input power, the apparent input power and the output current at 24 volts. The first decides whether the unit can be stocked for both 120 and 230 volt panels, the middle two size the upstream transformer and protection, and the last one decides how many modules and field devices the rail can carry.
The two catalog numbers in this family differ by a factor of more than two in output current, and that is the whole selection decision. One and three tenths of an amp covers a small rail of digital modules; three amps covers a rail with analog modules and a heavier field load.
Power for the controller and power for the I/O are separate circuits by design. Sharing one supply between the controller and a rail full of modules couples every field fault into the processor, and the installation steps in the manual keep them apart for that reason.
A power supply failure looks like a module failure because the symptoms appear at the I/O. The published output current and the measured rail voltage under load are the two numbers that separate the two, and checking them first saves a module swap that would not have fixed anything.
Input range is wide on both units, 85 to 265 volts AC, which is what allows the same part number to be stocked for a 120 volt panel and a 230 volt panel. The nameplate nominal is a label rather than a limit, and a plant with a sagging supply still runs the supply inside its published window.
An extended local rail is treated as a communication adapter when the power budget is calculated, not as an I/O module. That single sentence changes the arithmetic on a two rail system, and it is the sentence most often missed when a rail is expanded after commissioning.
Ambient temperature derates any 24 volt supply, and the datasheet figure is at a stated temperature inside an enclosure. A sealed cabinet with a supply at full load will run hotter than the number assumes, which is why the thermal calculation and the current budget are done together.
Real power, apparent power and transformer load are three different numbers for the same unit, and only one of them sizes the transformer. Thirty six watts of real input against fifty three volt amperes apparent is a power factor statement, and the ninety volt ampere transformer load is what the upstream device has to carry.
Eight modules per local rail and eight per extended rail is the FlexLogix limit, and it is a count rather than a current limit. Both constraints apply, so a rail of eight low power digital modules and a rail of eight analog modules can be inside the count and outside the current budget.
The terminal blocks and the DIN rail mount are the mechanical side of the same decision. A supply that needs a separate fuse, a separate disconnect and a clear finger safe cover takes panel space that the rail itself does not, and that space belongs in the layout drawing.
Mounting orientation changes the rating on the larger unit and not on the smaller one. Three amps horizontally and two point eight vertically is a real derating, and a rail mounted sideways in a shallow cabinet is exactly the case where that clause applies.
Field devices fed from the rail are the quiet load that pushes a supply over the edge. A rail that is comfortable at commissioning grows by a sensor or a relay coil each service visit, and a supply running above eighty percent of its rating has no margin for that drift.
A 24 volt supply on a FLEX rail is a budget item, not a convenience. The adapter, every module on the rail and the field devices that are fed from the rail all draw from the same output, and the arithmetic has to be done before the rail is built rather than after the first module browns out.
Separated extra low voltage is a requirement rather than a preference in CSA jurisdictions. The manual asks for a supply compliant with IEC 61010-1 Annex H, which is a statement about isolation and about the field wiring that the rail is allowed to feed.
Do the rail budget before the modules are ordered, keep the controller on its own supply, and confirm the SELV requirement if the panel is built to CSA rules.
The Allen-Bradley Flex I/O 1794 modules category lists the related catalog numbers, options and accessories for this range.