Product Details:
Payment & Shipping Terms:
|
The 1769-IA16 (also written 1769IA16) is the 120V AC input slice of the Compact I/O 1769 range: sixteen points on one common, wired straight to a 100/120V AC field circuit without an interposing relay. It is the module that lets a CompactLogix rack read push buttons, limit switches, motor starter auxiliaries and panel selector switches that already sit on plant AC control voltage.
The whole sixteen points share one internally connected common, which is what keeps the terminal count low and the wiring short. That is also its one hard limit: the module sees one AC supply only, so a panel with two different AC control feeds needs two modules or an interface relay between them.
| 1769-IA16 | Compact 16-point 120V AC input module | IN STOCK |
| 1769-IQ16 | Compact 16-point 24V DC sink/source input module | IN STOCK |
| 1769-IQ32 | Compact 32-point 24V DC sink/source input module | IN STOCK |
| 1769-OA16 | Compact 16-point 120/240V AC output module | IN STOCK |
| 1769-OB16 | Compact 16-point 24V DC output module | IN STOCK |
| 1769-OB32 | Compact 32-point 24V DC output module | IN STOCK |
| 1769-OW16 | Compact 16-point relay output module | IN STOCK |
| 1769-IF4 | Compact 4-channel analog input module | IN STOCK |
| 1769-IF8 | Compact 8-channel analog input module | IN STOCK |
| 1769-IF16C | Compact 16-channel current input module | IN STOCK |
| 1769-OF4 | Compact 4-channel analog output module | IN STOCK |
| 1769-OF8V | Compact 8-channel voltage output module | IN STOCK |
| 1769-OF8C | Compact 8-channel current output module | IN STOCK |
| 1769-ARM | Compact address reserve module | IN STOCK |
Application |
Compact I/O, 1769 bus |
Cat Num |
1769-IA16 |
Brand Name |
Rockwell |
Inputs |
16 (16 points per group, commons connected internally) |
Voltage category |
100/120V AC |
Operating voltage range |
79…132V AC, 47…63 Hz |
Input delay, on / off |
20 ms / 20 ms |
Current draw @ 5.1V |
115 mA |
Heat dissipation, max |
3.30 W |
Off-state voltage / current |
20V AC max / 2.5 mA max |
On-state voltage / current |
79V AC min / 5 mA @ 74V AC min, 12 mA @ 120V AC max |
Inrush current, max |
250 mA |
Input impedance, max |
12 kΩ @ 50 Hz; 10 kΩ @ 60 Hz |
Isolation |
1517V AC 1 s or 2145V DC 1 s, input point to bus; 132V AC working voltage |
Slot width / weight |
1 slot / 280 g |
Power supply distance |
8 modules |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
How many inputs does 1769-IA16 have and do they share a common?
Sixteen, all on one common connected internally — there is no group isolation on this catalog number. If points must sit on separate AC feeds, use 1769-IA8I.
What AC voltage range does 1769-IA16 accept?
79…132V AC at 47…63 Hz, rated 100/120V AC. Below 79V at the terminals the point is no longer guaranteed on.
What is the input delay of 1769-IA16?
20 ms on and 20 ms off, fixed. It rejects contact bounce but will not register a pulse shorter than 20 ms.
What does 1769-IA16 draw from the backplane?
115 mA at 5.1V with 3.30 W maximum heat dissipation — one slot, 280 g, eight-module power-supply distance rating.
Why does a 1769-IA16 point stay on with the switch open?
Off-state current can reach 2.5 mA per point while minimum on-state current is 5 mA at 74V AC. A neon pilot light, surge suppressor or long cable leaking near that limit holds the point on; remove the leakage path or add a bleeder.
Can inrush current on 1769-IA16 be reduced?
Yes, with a 6.8 kΩ (2.5 W minimum) series resistor, which cuts inrush to 35 mA but raises the minimum on-state voltage to 92V AC — the module then needs a higher AC level to see the point.
What wire size and torque does 1769-IA16 require?
22…14 AWG solid or 22…16 AWG stranded copper rated 90 °C; 0.68 N·m (6 lb·in) on terminals, 0.46 N·m (4.1 lb·in) on retaining screws.