logo
Home ProductsAB CompactLogix 1769

Allen Bradley PLC 1769-IA16 / 1769IA16

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1769-IA16 / 1769IA16

China Allen Bradley PLC 1769-IA16 / 1769IA16 supplier
Allen Bradley PLC 1769-IA16 / 1769IA16 supplier Allen Bradley PLC 1769-IA16 / 1769IA16 supplier Allen Bradley PLC 1769-IA16 / 1769IA16 supplier Allen Bradley PLC 1769-IA16 / 1769IA16 supplier Allen Bradley PLC 1769-IA16 / 1769IA16 supplier Allen Bradley PLC 1769-IA16 / 1769IA16 supplier Allen Bradley PLC 1769-IA16 / 1769IA16 supplier

Large Image :  Allen Bradley PLC 1769-IA16 / 1769IA16

Product Details:

Place of Origin: Made in MALAYSIA
Brand Name: Rockwell
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1769-IA16 / 1769IA16

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $164.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 10 PCS
Detailed Product Description

1769-IA16 technical data PDF download CompactLogix 1769-IA16 / 1769IA16 16-Point 120V AC Input Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC I/O

The 1769-IA16 (also written 1769IA16) is the 120V AC input slice of the Compact I/O 1769 range: sixteen points on one common, wired straight to a 100/120V AC field circuit without an interposing relay. It is the module that lets a CompactLogix rack read push buttons, limit switches, motor starter auxiliaries and panel selector switches that already sit on plant AC control voltage.

The whole sixteen points share one internally connected common, which is what keeps the terminal count low and the wiring short. That is also its one hard limit: the module sees one AC supply only, so a panel with two different AC control feeds needs two modules or an interface relay between them.

1769-IA16 Compact 16-point 120V AC input module IN STOCK
1769-IQ16 Compact 16-point 24V DC sink/source input module IN STOCK
1769-IQ32 Compact 32-point 24V DC sink/source input module IN STOCK
1769-OA16 Compact 16-point 120/240V AC output module IN STOCK
1769-OB16 Compact 16-point 24V DC output module IN STOCK
1769-OB32 Compact 32-point 24V DC output module IN STOCK
1769-OW16 Compact 16-point relay output module IN STOCK
1769-IF4 Compact 4-channel analog input module IN STOCK
1769-IF8 Compact 8-channel analog input module IN STOCK
1769-IF16C Compact 16-channel current input module IN STOCK
1769-OF4 Compact 4-channel analog output module IN STOCK
1769-OF8V Compact 8-channel voltage output module IN STOCK
1769-OF8C Compact 8-channel current output module IN STOCK
1769-ARM Compact address reserve module IN STOCK

Product Specifications 1769-IA16 (PDF)
 Application
 Compact I/O, 1769 bus
 Cat Num
 1769-IA16
 Brand Name
 Rockwell
 Inputs
 16 (16 points per group, commons connected internally)
 Voltage category
 100/120V AC
 Operating voltage range
 79…132V AC, 47…63 Hz
 Input delay, on / off
 20 ms / 20 ms
 Current draw @ 5.1V
 115 mA
 Heat dissipation, max
 3.30 W
 Off-state voltage / current
 20V AC max / 2.5 mA max
 On-state voltage / current
 79V AC min / 5 mA @ 74V AC min, 12 mA @ 120V AC max
 Inrush current, max
 250 mA
 Input impedance, max
 12 kΩ @ 50 Hz; 10 kΩ @ 60 Hz
 Isolation
 1517V AC 1 s or 2145V DC 1 s, input point to bus; 132V AC working voltage
 Slot width / weight
 1 slot / 280 g
 Power supply distance
 8 modules

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1769-TD006 (module specifications) and 1769-SG001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1769-IA16 Compact I/O 16-point 120V AC input module, factory packaging 1769-IA16 module, front view with terminal block 1769-IA16 label detail showing catalog number

Where the module sits in a CompactLogix system

Bank and supply. Each bank carries its own 1769-PA2, PB2, PA4 or PB4 supply; this module draws 115 mA from the 5.1V bus and counts one slot against the eight-module power-supply distance rating. One common, sixteen points. The commons are connected internally, so all field devices must return to the same AC source. Splitting a cabinet across two control transformers is the usual reason a 1769-IA16 is replaced by two modules or by 1769-IA8I, which isolates each point. AC voltage window. The published range is 79…132V AC at 47…63 Hz. A nominal 120V circuit that sags below 79V at the terminals will drop out, and 50 Hz versus 60 Hz changes the input impedance (12 kΩ against 10 kΩ), which matters when a leakage path is being judged.

Input behaviour that decides field wiring

20 ms on and 20 ms off. The delay is fixed. That is slow enough to reject contact bounce on a push button and fast enough for a normal PLC scan, but it will not capture a pulse shorter than 20 ms. Leakage and minimum current. Off-state current may reach 2.5 mA per point while the minimum on-state current is 5 mA at 74V AC. Neon indicators, surge suppressors or long cable runs that leak near that limit can hold a point on; a bleeder or a different pilot device is the fix. Inrush. 250 mA per point is the inrush rating. Where the circuit has to be gentler, a 6.8 kΩ (2.5 W minimum) resistor in series with the input reduces inrush to 35 mA, but it also raises the minimum on-state voltage to 92V AC — a documented trade, not a free fix.

Commissioning in four checks

Confirm all sixteen field devices return to the same AC source as the common terminals; a second feed is a wiring error, not a configuration option. Measure the AC voltage at the terminals under load — not at the panel busbar — and confirm it stays above 79V AC at the worst case. Torque terminals at 0.68 N·m (6 lb·in) and retaining screws at 0.46 N·m (4.1 lb·in), with 22…14 AWG solid copper rated 90 °C. Verify each point's state in the controller against a known pilot device before closing the panel; a stuck point is far cheaper to find now than during a startup window.

Substituting or replacing a 1769-IA16

1769-IA8I — eight individually isolated 120V AC inputs, 90 mA at 5.1V, 1.81 W. The right answer when points sit on different AC feeds. 1769-IM12 — twelve points at 200/240V AC for 230V control circuits, with four terminals marked NC that must be left unconnected. 1769-IQ16 — sixteen 24V DC sink/source inputs, when the field devices are DC and only the coil circuit is AC. There is no 32-point 120V AC module in the family; past sixteen AC points the choice is two modules or a move to 24V DC field wiring.

Which Compact I/O digital input to specify

1769-IA16 — 16 points, 120V AC, one common, 115 mA at 5.1V. 1769-IA8I — 8 points, 120V AC, point-by-point isolation. 1769-IM12 — 12 points, 240V AC. 1769-IQ16 / 1769-IQ32 — 24V DC sink/source, 16 or 32 points. Choose by field voltage and by whether the points share one source; then check the 5.1V draw and the distance rating against the bank.

FAQ — 1769-IA16

How many inputs does 1769-IA16 have and do they share a common?

Sixteen, all on one common connected internally — there is no group isolation on this catalog number. If points must sit on separate AC feeds, use 1769-IA8I.

What AC voltage range does 1769-IA16 accept?

79…132V AC at 47…63 Hz, rated 100/120V AC. Below 79V at the terminals the point is no longer guaranteed on.

What is the input delay of 1769-IA16?

20 ms on and 20 ms off, fixed. It rejects contact bounce but will not register a pulse shorter than 20 ms.

What does 1769-IA16 draw from the backplane?

115 mA at 5.1V with 3.30 W maximum heat dissipation — one slot, 280 g, eight-module power-supply distance rating.

Why does a 1769-IA16 point stay on with the switch open?

Off-state current can reach 2.5 mA per point while minimum on-state current is 5 mA at 74V AC. A neon pilot light, surge suppressor or long cable leaking near that limit holds the point on; remove the leakage path or add a bleeder.

Can inrush current on 1769-IA16 be reduced?

Yes, with a 6.8 kΩ (2.5 W minimum) series resistor, which cuts inrush to 35 mA but raises the minimum on-state voltage to 92V AC — the module then needs a higher AC level to see the point.

What wire size and torque does 1769-IA16 require?

22…14 AWG solid or 22…16 AWG stranded copper rated 90 °C; 0.68 N·m (6 lb·in) on terminals, 0.46 N·m (4.1 lb·in) on retaining screws.


Data sources. Technical values on this page come from Rockwell publication 1769-TD006 (1769 Compact I/O Modules Specifications) and 1769-SG001 (CompactLogix and Compact GuardLogix Systems Selection Guide), both current documents. Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Related numbers

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)