Product Details:
Payment & Shipping Terms:
|
The 2080-LC30-16QVB is the transistor-output version of the 16-point Micro830, with one PTO and two high-speed counters.
The sink outputs allow pulse trains, so this model can drive a stepper drive or a small servo enable sequence that a relay version cannot.
| 2080-LC10-12AWA | Micro810, 8 AC in / 4 relay out | IN STOCK |
| 2080-LC10-12QWB | Micro810, 8 DC/AC in / 4 relay out | IN STOCK |
| 2080-LC10-12QBB | Micro810, 8 DC/AC in / 4 DC source out | IN STOCK |
| 2080-LC10-12DWD | Micro810, 8 12V DC in / 4 relay out | IN STOCK |
| 2080-LC20-20AWB | Micro820, 12 AC in / 8 relay out | IN STOCK |
| 2080-LC20-20QWB | Micro820, 12 DC in / 8 relay out | IN STOCK |
| 2080-LC20-20QBB | Micro820, 12 DC in / 8 DC source out | IN STOCK |
| 2080-LC20-20AWBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC20-20QWBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC20-20QBBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC30-10QWB | Micro830, 6 DC/AC in / 4 relay out | IN STOCK |
| 2080-LC30-10QVB | Micro830, 6 DC/AC in / 4 DC sink out | IN STOCK |
| 2080-LC30-16AWB | Micro830, 10 AC in / 6 relay out | IN STOCK |
| 2080-LC30-16QWB | Micro830, 10 DC/AC in / 6 relay out | IN STOCK |
| 2080-LC30-16QVB | Micro830, 10 DC/AC in / 6 DC sink out | IN STOCK |
| 2080-LC30-24QWB | Micro830, 14 DC/AC in / 10 relay out | IN STOCK |
| 2080-LC30-24QVB | Micro830, 14 DC/AC in / 10 DC sink out | IN STOCK |
| 2080-LC30-24QBB | Micro830, 14 DC/AC in / 10 DC source out | IN STOCK |
| 2080-LC30-48AWB | Micro830, 28 AC in / 20 relay out | IN STOCK |
| 2080-LC30-48QWB | Micro830, 28 DC/AC in / 20 relay out | IN STOCK |
| 2080-LC30-48QVB | Micro830, 28 DC/AC in / 20 DC sink out | IN STOCK |
| 2080-LC50-24AWB | Micro850, 14 AC in / 10 relay out | IN STOCK |
| 2080-LC50-24QVB | Micro850, 14 DC/AC in / 10 DC sink out | IN STOCK |
| 2080-LC50-24QBB | Micro850, 14 DC/AC in / 10 DC source out | IN STOCK |
| 2080-LC50-48AWB | Micro850, 28 AC in / 20 relay out | IN STOCK |
| 2080-LC50-48QWB | Micro850, 28 DC/AC in / 20 relay out | IN STOCK |
| 2080-LC50-48QVB | Micro850, 28 DC/AC in / 20 DC sink out | IN STOCK |
| 2080-LC50-48QBB | Micro850, 28 DC/AC in / 20 DC source out | IN STOCK |
Catalog number |
2080-LC30-16QVB |
Family |
Micro830 brick controller |
I/O points |
16 (10 inputs, 6 sink outputs) |
Inputs |
10 inputs, 24 V DC or 24 V AC |
Outputs |
6 outputs, 24 V DC sink |
Supply |
24 V DC Class 2 through the optional power supply slot |
Communication |
USB 2.0 Type B programming port and RS-232/RS-485 non-isolated combo serial port |
Plug-in modules |
2 plug-in slots |
Dimensions, H x W x D |
90 x 100 x 80 mm |
Shipping weight |
See 2080-UM002 table |
Temperature rating |
-20 to 65 C (-4 to 149 F) |
Power consumption, max |
5 W |
Lifecycle |
Listed in the current Micro830 catalog table of 2080-UM002 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 2080-UM002 (module specifications) and 2080-UM002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The 2080-LC30-16QVB is the transistor-output version of the 16-point Micro830, with one PTO and two high-speed counters.
The sink outputs allow pulse trains, so this model can drive a stepper drive or a small servo enable sequence that a relay version cannot.
It is the 16-point choice for a machine with one small motion axis.
Sink outputs pull the load to 0 V; the field supply positive rail goes to the load.
One PTO output and two HSC inputs are listed for this catalog.
The outputs are transistor, so an AC load needs an external relay.
Communication and capacity. USB 2.0 Type B programming port and RS-232/RS-485 non-isolated combo serial port
2 plug-in slots plug-in modules can be fitted, each drawing about 1.44 W of the controller's internal budget.
Connected Components Workbench is the programming environment for the whole family, so a project built for one Micro800 controller converts to another with the I/O reassigned.
Mounting is DIN rail or panel, 90 x 100 x 80 mm, shipping See 2080-UM002 table.
Rated ambient -20 to 65 C (-4 to 149 F), maximum consumption 5 W.
Lifecycle. Listed in the current Micro830 catalog table of 2080-UM002
Two plug-in slots, 5 W base consumption, 90 x 100 x 80 mm.
2080-UM002 Table 1 lists 10 inputs, 6 sink outputs and one PTO for this catalog.
Rockwell's Micro830 catalog table still lists this catalog number.
How many I/O points does 2080-LC30-16QVB have?
Micro830 brick controller: 16 (10 inputs, 6 sink outputs).
What is the input type on 2080-LC30-16QVB?
10 inputs, 24 V DC or 24 V AC.
What does 2080-LC30-16QVB use for communication?
USB 2.0 Type B programming port and RS-232/RS-485 non-isolated combo serial port.
What are the dimensions of 2080-LC30-16QVB?
90 x 100 x 80 mm, See 2080-UM002 table.
What is the lifecycle status of 2080-LC30-16QVB?
Listed in the current Micro830 catalog table of 2080-UM002.