Product Details:
Payment & Shipping Terms:
|
The 2080-LC10-12QWB is the 24 V DC version of the 12-point Micro810, with the same four relay outputs as the AC-supplied model.
It suits panels that already run a 24 V DC bus: one supply feeds the controller and the field devices, and the relay outputs still switch AC loads.
| 2080-LC10-12AWA | Micro810, 8 AC in / 4 relay out | IN STOCK |
| 2080-LC10-12QWB | Micro810, 8 DC/AC in / 4 relay out | IN STOCK |
| 2080-LC10-12QBB | Micro810, 8 DC/AC in / 4 DC source out | IN STOCK |
| 2080-LC10-12DWD | Micro810, 8 12V DC in / 4 relay out | IN STOCK |
| 2080-LC20-20AWB | Micro820, 12 AC in / 8 relay out | IN STOCK |
| 2080-LC20-20QWB | Micro820, 12 DC in / 8 relay out | IN STOCK |
| 2080-LC20-20QBB | Micro820, 12 DC in / 8 DC source out | IN STOCK |
| 2080-LC20-20AWBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC20-20QWBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC20-20QBBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC30-10QWB | Micro830, 6 DC/AC in / 4 relay out | IN STOCK |
| 2080-LC30-10QVB | Micro830, 6 DC/AC in / 4 DC sink out | IN STOCK |
| 2080-LC30-16AWB | Micro830, 10 AC in / 6 relay out | IN STOCK |
| 2080-LC30-16QWB | Micro830, 10 DC/AC in / 6 relay out | IN STOCK |
| 2080-LC30-16QVB | Micro830, 10 DC/AC in / 6 DC sink out | IN STOCK |
| 2080-LC30-24QWB | Micro830, 14 DC/AC in / 10 relay out | IN STOCK |
| 2080-LC30-24QVB | Micro830, 14 DC/AC in / 10 DC sink out | IN STOCK |
| 2080-LC30-24QBB | Micro830, 14 DC/AC in / 10 DC source out | IN STOCK |
| 2080-LC30-48AWB | Micro830, 28 AC in / 20 relay out | IN STOCK |
| 2080-LC30-48QWB | Micro830, 28 DC/AC in / 20 relay out | IN STOCK |
| 2080-LC30-48QVB | Micro830, 28 DC/AC in / 20 DC sink out | IN STOCK |
| 2080-LC50-24AWB | Micro850, 14 AC in / 10 relay out | IN STOCK |
| 2080-LC50-24QVB | Micro850, 14 DC/AC in / 10 DC sink out | IN STOCK |
| 2080-LC50-24QBB | Micro850, 14 DC/AC in / 10 DC source out | IN STOCK |
| 2080-LC50-48AWB | Micro850, 28 AC in / 20 relay out | IN STOCK |
| 2080-LC50-48QWB | Micro850, 28 DC/AC in / 20 relay out | IN STOCK |
| 2080-LC50-48QVB | Micro850, 28 DC/AC in / 20 DC sink out | IN STOCK |
| 2080-LC50-48QBB | Micro850, 28 DC/AC in / 20 DC source out | IN STOCK |
Catalog number |
2080-LC10-12QWB |
Family |
Micro810 12-point smart relay controller |
I/O points |
12 (8 inputs, 4 relay outputs) |
Inputs |
8 inputs, 24 V DC or 24 V AC |
Outputs |
4 relay outputs, two rated 8 A and two rated 4 A |
Supply |
24 V DC Class 2, 20.4 to 26.4 V DC, 3 W maximum |
Communication |
USB 2.0 programming port through the 2080-USBADAPTER; no Ethernet or serial port |
Plug-in modules |
None; the Micro810 has no plug-in slots, only the LCD and USB accessories |
Dimensions, H x W x D |
91 x 75 x 59 mm |
Shipping weight |
0.203 kg |
Temperature rating |
0 to 55 C (32 to 131 F) |
Power consumption, max |
3 W |
Lifecycle |
Active |
Relay output rating |
Two outputs at 8 A, two at 4 A |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 2080-TD001 (module specifications) and 2080-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The 2080-LC10-12QWB is the 24 V DC version of the 12-point Micro810, with the same four relay outputs as the AC-supplied model.
It suits panels that already run a 24 V DC bus: one supply feeds the controller and the field devices, and the relay outputs still switch AC loads.
DC input models share four of the eight inputs as 0 to 10 V analog channels, which is how a Micro810 reads a pressure transducer without an analog module.
Supply range is 20.4 to 26.4 V DC, so the 24 V rail has to stay inside the Class 2 window.
Relay outputs are two at 8 A and two at 4 A; the current rating is per output, not per common.
Terminal torque is 0.5 to 0.6 Nm with a 0.6 x 3.5 mm screwdriver, and the terminals are fixed, not removable.
Communication and capacity. USB 2.0 programming port through the 2080-USBADAPTER; no Ethernet or serial port
None; the Micro810 has no plug-in slots, only the LCD and USB accessories plug-in modules can be fitted, each drawing about 1.44 W of the controller's internal budget.
Connected Components Workbench is the programming environment for the whole family, so a project built for one Micro800 controller converts to another with the I/O reassigned.
Mounting is DIN rail or panel, 91 x 75 x 59 mm, shipping 0.203 kg.
Rated ambient 0 to 55 C (32 to 131 F), maximum consumption 3 W.
Lifecycle. Active
Twelve points total, with no plug-in slots: the Micro810 accepts only the LCD and USB accessories.
Rockwell lists it as Active.
It is the model to fit where a 24 V DC panel needs a handful of relay outputs and a timer.
How many I/O points does 2080-LC10-12QWB have?
Micro810 12-point smart relay controller: 12 (8 inputs, 4 relay outputs).
What is the input type on 2080-LC10-12QWB?
8 inputs, 24 V DC or 24 V AC.
What does 2080-LC10-12QWB use for communication?
USB 2.0 programming port through the 2080-USBADAPTER; no Ethernet or serial port.
What are the dimensions of 2080-LC10-12QWB?
91 x 75 x 59 mm, 0.203 kg.
What is the lifecycle status of 2080-LC10-12QWB?
Active.