Product Details:
Payment & Shipping Terms:
|
The 2080-LC10-12QBB is the only Micro810 with transistor outputs instead of relays: four 24 V DC source outputs.
It is the model for fast, repetitive switching where a relay would wear out, such as a solenoid valve or a small DC motor starter.
| 2080-LC10-12AWA | Micro810, 8 AC in / 4 relay out | IN STOCK |
| 2080-LC10-12QWB | Micro810, 8 DC/AC in / 4 relay out | IN STOCK |
| 2080-LC10-12QBB | Micro810, 8 DC/AC in / 4 DC source out | IN STOCK |
| 2080-LC10-12DWD | Micro810, 8 12V DC in / 4 relay out | IN STOCK |
| 2080-LC20-20AWB | Micro820, 12 AC in / 8 relay out | IN STOCK |
| 2080-LC20-20QWB | Micro820, 12 DC in / 8 relay out | IN STOCK |
| 2080-LC20-20QBB | Micro820, 12 DC in / 8 DC source out | IN STOCK |
| 2080-LC20-20AWBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC20-20QWBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC20-20QBBR | Micro820 with removable terminal blocks | IN STOCK |
| 2080-LC30-10QWB | Micro830, 6 DC/AC in / 4 relay out | IN STOCK |
| 2080-LC30-10QVB | Micro830, 6 DC/AC in / 4 DC sink out | IN STOCK |
| 2080-LC30-16AWB | Micro830, 10 AC in / 6 relay out | IN STOCK |
| 2080-LC30-16QWB | Micro830, 10 DC/AC in / 6 relay out | IN STOCK |
| 2080-LC30-16QVB | Micro830, 10 DC/AC in / 6 DC sink out | IN STOCK |
| 2080-LC30-24QWB | Micro830, 14 DC/AC in / 10 relay out | IN STOCK |
| 2080-LC30-24QVB | Micro830, 14 DC/AC in / 10 DC sink out | IN STOCK |
| 2080-LC30-24QBB | Micro830, 14 DC/AC in / 10 DC source out | IN STOCK |
| 2080-LC30-48AWB | Micro830, 28 AC in / 20 relay out | IN STOCK |
| 2080-LC30-48QWB | Micro830, 28 DC/AC in / 20 relay out | IN STOCK |
| 2080-LC30-48QVB | Micro830, 28 DC/AC in / 20 DC sink out | IN STOCK |
| 2080-LC50-24AWB | Micro850, 14 AC in / 10 relay out | IN STOCK |
| 2080-LC50-24QVB | Micro850, 14 DC/AC in / 10 DC sink out | IN STOCK |
| 2080-LC50-24QBB | Micro850, 14 DC/AC in / 10 DC source out | IN STOCK |
| 2080-LC50-48AWB | Micro850, 28 AC in / 20 relay out | IN STOCK |
| 2080-LC50-48QWB | Micro850, 28 DC/AC in / 20 relay out | IN STOCK |
| 2080-LC50-48QVB | Micro850, 28 DC/AC in / 20 DC sink out | IN STOCK |
| 2080-LC50-48QBB | Micro850, 28 DC/AC in / 20 DC source out | IN STOCK |
Catalog number |
2080-LC10-12QBB |
Family |
Micro810 12-point smart relay controller |
I/O points |
12 (8 inputs, 4 source outputs) |
Inputs |
8 inputs, 24 V DC or 24 V AC |
Outputs |
4 outputs, 24 V DC source transistor |
Supply |
12 or 24 V DC Class 2, 11.4 to 26.4 V DC |
Communication |
USB 2.0 programming port through the 2080-USBADAPTER; no Ethernet or serial port |
Plug-in modules |
None; the Micro810 has no plug-in slots, only the LCD and USB accessories |
Dimensions, H x W x D |
91 x 75 x 59 mm |
Shipping weight |
0.203 kg |
Temperature rating |
0 to 55 C (32 to 131 F) |
Power consumption, max |
3 W |
Lifecycle |
Active |
Relay output rating |
Two outputs at 8 A, two at 4 A |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 2080-TD001 (module specifications) and 2080-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The 2080-LC10-12QBB is the only Micro810 with transistor outputs instead of relays: four 24 V DC source outputs.
It is the model for fast, repetitive switching where a relay would wear out, such as a solenoid valve or a small DC motor starter.
Inputs are 24 V DC or 24 V AC, and four of them double as 0 to 10 V analog inputs.
Source output means the module supplies the positive side; the load returns to 0 V.
Supply range is 11.4 to 26.4 V DC, so it will run from either a 12 V or a 24 V battery system.
There are no relay contacts on this model, so an AC load needs an external relay or contactor.
Communication and capacity. USB 2.0 programming port through the 2080-USBADAPTER; no Ethernet or serial port
None; the Micro810 has no plug-in slots, only the LCD and USB accessories plug-in modules can be fitted, each drawing about 1.44 W of the controller's internal budget.
Connected Components Workbench is the programming environment for the whole family, so a project built for one Micro800 controller converts to another with the I/O reassigned.
Mounting is DIN rail or panel, 91 x 75 x 59 mm, shipping 0.203 kg.
Rated ambient 0 to 55 C (32 to 131 F), maximum consumption 3 W.
Lifecycle. Active
Twelve points, no plug-in slots, LCD and USB accessories only.
Rockwell lists it as Active.
It is the Micro810 to choose when output life matters more than output voltage flexibility.
How many I/O points does 2080-LC10-12QBB have?
Micro810 12-point smart relay controller: 12 (8 inputs, 4 source outputs).
What is the input type on 2080-LC10-12QBB?
8 inputs, 24 V DC or 24 V AC.
What does 2080-LC10-12QBB use for communication?
USB 2.0 programming port through the 2080-USBADAPTER; no Ethernet or serial port.
What are the dimensions of 2080-LC10-12QBB?
91 x 75 x 59 mm, 0.203 kg.
What is the lifecycle status of 2080-LC10-12QBB?
Active.
2080-LC10-12QBB is a 12 point Micro810 controller with DC inputs and source outputs in the Micro800 family, and the point table below is the published configuration for this catalog number rather than a family summary.
| Specification | Value |
|---|---|
| Catalog number | 2080-LC10-12QBB, Micro810 controller, 12 point, 12 to 24V DC input, source outputs |
| Power | 12 to 24V DC |
| Inputs | 8 inputs at 12 to 24V DC |
| Outputs | 4 outputs, 24V DC source type |
| Analog inputs | 4 channels of 0 to 10V, shared with four of the DC inputs |
| Form factor | 12 point, Micro810 |
| Difference from the relay models | Solid state source outputs instead of relays, for loads that switch often enough that relay life would be the limit |
| Source | 2080-SG001 Micro800 selection guide, Micro810 controllers input and output table |
Source outputs change the wiring more than the logic. A source output supplies positive to the load and the load returns to common, which is the opposite of the sink convention used on most industrial input cards, and the field wiring has to be drawn accordingly.
Solid state outputs on a twelve point controller exist for duty cycle rather than for current. A relay rated at eight amp will outlast a solid state output on a load that switches twice a day, and the solid state part wins on a load that switches twice a second.
The point mix, the communication ports and the analog channel sharing on this page are taken from the Micro800 selection guide entry for this catalog number. Where a feature depends on a firmware revision, the row states the revision rather than implying it is universal.
The 2080 numbering carries the point mix in the suffix. AC input models are A, DC input models are Q, and the last letters describe the outputs: W for relay, V for sink, B for source. Reading the suffix is faster than opening the selection guide, and it is the same logic the family uses for expansion modules.
Communication ports on a small controller decide the architecture as much as the I/O does. An embedded Ethernet port with four Class 1 nodes is enough for a drive and a panel, and a serial port with Modbus RTU is enough for a weigh scale, but a machine that needs both protocols on multiple devices has outgrown the compact model.
A twelve point controller with relay outputs is a smart relay replacement, and the design intent is visible in the function blocks: delay on and off, time of day, time of week and time of year are built in rather than programmed, which is what a lighting or pump alternation panel needs.
Rated outputs are the reason these controllers exist in machine building. Two eight amp and two four amp relay outputs on the smallest model remove the external interposing relays for a small pump or a lamp, and the eight amp figure is per output with a total module limit that has to be read before the loads are added up.
The remote LCD module is a configuration aid, not an operator interface. It sets an IP address and shows a text display for a compact controller that has no screen, and its IP65 rating is the reason it can be mounted on the outside of an enclosure rather than behind the door.
A Micro800 controller is specified by the point mix rather than by the point count. Two catalogs with twenty points can carry eight AC inputs and seven relays, or twelve DC inputs and seven relays with an analog output, and the drawing that assumed the wrong mix has to be redone at the terminal level.
Expansion capacity is a hard number, not a suggestion. Micro850 controllers accept up to four expansion modules, and the 2085 family is the one that fits them, while the 2080 plug-in modules occupy the two plug-in slots on the compact models. Mixing the two kinds of expansion is a common ordering error.
Firmware revision gates features on these controllers. EtherNet/IP Class 1 connections to drives and remote LCD support arrive at specific revisions, and a controller from stock may predate them, so the revision belongs in the commissioning checklist rather than in the brochure.
Power supply choice follows from the input type, not from the output type. A controller with 120 to 240 volt AC inputs takes its field power from the same source that feeds the inputs, while a 24 volt DC input model needs a separate supply and puts that supply on the bill of materials.
The microSD slot is a maintenance feature more than a data feature. Project backup and restore from a card is what allows a service technician to replace a controller without a laptop and the original project file, and data logging and recipes are the secondary uses.
Conformal coating suffixes exist across the family for the same reason they exist elsewhere: condensing humidity, corrosive atmospheres and washdown areas. The suffix changes the materials, not the point mix, and the electrical ratings stay with the base catalog number.
Analog channels shared with digital inputs are a compromise worth understanding. Four 24 volt DC inputs can be configured as 0 to 10 volt analog inputs on the DC input models, which means the channel count is shared rather than added, and a machine that needs both cannot have both.
Plug-in modules and expansion modules are different form factors with different buses. A plug-in module sits in a slot inside the controller housing and shares its power, while an expansion module is a separate DIN rail device with its own terminal blocks, and the wiring effort differs accordingly.
Choose it where the load cycles fast enough that relay life would be the limit, and draw the source wiring explicitly.
Related models, options and spare parts for this range are listed in the Allen-Bradley Micro and Nano systems category.