Product Details:
Payment & Shipping Terms:
|
1760-IB12XOB8 is an expansion module for the Pico range: 12, 24 V DC and 8, transistor 24 V DC.
It adds I/O to a Pico -EX controller or to the GFX-70 processor through the Pico-Link connection.
| 1760-L12BBB | 12 I/O, 24 V DC, 8 DC in / 4 MOSFET out | IN STOCK |
| 1760-L12BWB | 12 I/O, 24 V DC, 8 DC in / 4 relay out | IN STOCK |
| 1760-L12BWB-NC | same as L12BWB without real-time clock | IN STOCK |
| 1760-L12BWB-ND | same as L12BWB without display | IN STOCK |
| 1760-L12DWD | 12 I/O, 12 V DC, 8 DC in / 4 relay out | IN STOCK |
| 1760-L18AWA-EX | 18 I/O, 120/240 V AC, expansion capable | IN STOCK |
| 1760-L18BWB-EX | 18 I/O, 24 V DC, expansion capable | IN STOCK |
| 1760-L20BBB-EX | 20 I/O, 24 V DC, 8 MOSFET out, expansion | IN STOCK |
| 1760-L20BBB-EXND | same as L20BBB-EX without display | IN STOCK |
| 1760-IA12XOW6I | expansion, 12 AC in / 6 relay out | IN STOCK |
| 1760-IB12XOW6I | expansion, 12 DC in / 6 relay out | IN STOCK |
| 1760-IB12XOB8 | expansion, 12 DC in / 8 transistor out | IN STOCK |
| 1760-IB12XOW4IF | GFX I/O, 12 DC in / 4 relay out, analog in | IN STOCK |
| 1760-IB12XOW4IOF | GFX I/O, 12 DC in / 4 relay out, analog in and out | IN STOCK |
| 1760-OW2 | expansion, 2 relay out | IN STOCK |
| 1760-CBL-INT01 | 0.3 m interface cable | IN STOCK |
| 1760-CBL-PC02 | PicoGFX programming cable | IN STOCK |
| 1760-CBL-PM02 | Pico programming cable | IN STOCK |
| 1760-DUB | PicoGFX display unit with keypad | IN STOCK |
| 1760-LDFC | PicoGFX GFX-70 processor, 24 V DC | IN STOCK |
| 1760-MM1 | memory module | IN STOCK |
| 1760-MM2B | memory module, larger | IN STOCK |
| 1760-NDC | protective cover | IN STOCK |
| 1760-PICOSOFT | PicoSoft programming software | IN STOCK |
| 1760-PICOSOFTPRO | PicoSoft Pro programming software | IN STOCK |
| 1760-SIM | I/O simulator | IN STOCK |
| 1760-TERM1 | Pico-Link termination resistors | IN STOCK |
| 1760-USB-PICO | Pico USB programming cable | IN STOCK |
Catalog number |
1760-IB12XOB8 |
Inputs |
12, 24 V DC |
Outputs |
8, transistor 24 V DC |
Line power |
24 V DC |
Analog capability |
None |
Used with |
Pico -EX controllers and the PicoGFX GFX-70 processor |
Lifecycle |
Discontinued, 2017 |
Documentation |
1760-UM001 / 1760-UM002 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1760-UM001 (module specifications) and 1760-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
1760-IB12XOB8 is an expansion module for the Pico range: 12, 24 V DC and 8, transistor 24 V DC.
It adds I/O to a Pico -EX controller or to the GFX-70 processor through the Pico-Link connection.
It is the only expansion with transistor outputs, rated 0.5 A per channel at 24 V DC.
Expansion inputs are addressed R1 to R12 and outputs S1 to S8 in the circuit diagram.
Input and output data is transferred serially, so the reaction time of an expansion input is 30 ms plus one cycle, and an expansion output 15 ms plus one cycle.
Analog capability: None.
The module is supplied with its connector; 1760-RPLCONN is the replacement connector catalog number.
No programming change is needed beyond using the R and S contacts: the controller detects an expansion module by their presence.
Rockwell lists this catalog number as discontinued in the 2017 Pico withdrawal.
Every value in the table above comes from Rockwell publication 1760-UM001 or 1760-UM002, or from the Rockwell product page for this catalog number.
Where a value is not printed in those documents it is marked as not published rather than estimated.
Rockwell discontinued the Bulletin 1760 Pico and PicoGFX range on 31 March 2017; the product pages now carry a discontinuation notice and no replacement catalogue is offered for the accessories.
These parts have been out of production since 2017, so the supply is used or surplus stock rather than new distribution.
For a controller, confirm that the memory module and the programming cable are included: without the cable the unit cannot be reprogrammed, and a memory module carries the only copy of the circuit diagram on many machines.
Ask for the label photograph: the ND and NC suffixes change the display and the clock, and the catalog number on the label is the only reliable identifier.
What does 1760-IB12XOB8 add?
12, 24 V DC and 8, transistor 24 V DC.
Which controllers accept 1760-IB12XOB8?
Pico -EX models and the PicoGFX GFX-70 processor.
How are the inputs addressed?
R1 to R12, with outputs S1 to S8.
What is the input reaction time?
30 ms plus one cycle time.
Is 1760-IB12XOB8 still available?
No, it was discontinued in 2017.
1760-IB12XOB8 is the Pico expansion module, 12 dc inputs and 8 transistor outputs in the 1760 Pico family. The family is a compact controller range with built in logic plus the display, memory, simulation and network parts that surround it, so the accessory and the controller are ordered as separate line items.
| Attribute | Value |
| Catalog number | 1760-IB12XOB8 |
| Product type | Pico expansion module, 12 dc inputs and 8 transistor outputs |
| Family | 1760 Pico and Pico GFX-70 |
| Inputs | 12 at 24V dc |
| Outputs | 8 transistor, 24V dc |
| Fault monitoring | R15 and R16 report group faults for S1 to S4 and S5 to S8 |
| Reaction time | S1 to S8 15 ms plus one cycle |
| Supply | 24V dc, 20.4 to 28.8V dc, ripple 5 percent maximum |
| Dimensions | 35.5 x 90 x 56.5 mm, 70 g |
| Source | 1760-UM001, Pico controllers |
The transistor expansion module carries group fault feedback on R15 and R16, which is what makes it usable on a machine that must not keep driving a shorted output: the fault contact sets an internal marker that the logic can use to drop the associated outputs.
The ac models are a different control problem from the dc models: the input delay is a mains property, 66 ms at 60 Hz and 80 ms at 50 Hz, with inputs I7 and I8 slower on the 12 point unit. A counting task that needs milliseconds belongs on a dc controller, not on the ac one.
Pico is an electronic control relay with built in logic, timers and counters, programmed in ladder through the display and keypad or from a PC. That is why the family carries suffixes instead of extra catalog numbers: NC means no real time clock, ND means no display and keypad, EX means expansion capability. Reading the suffix is the whole selection.
The memory module is the backup and the transfer medium, not extra controller memory: it stores the circuit diagram, the parameters, the text displays and the system settings, and 1760-MM2B holds one program up to 32K. It refuses to work in a series A controller, while the older 1760-MM1 and 1760-MM2 become read only once they are used in a series B unit.
Two generations share bulletin 1760 and they do not mix: the classic Pico uses 1760-PICOSOFT and the 1760-CBL-PM02 cable, while Pico GFX-70 uses 1760-PICOSOFTPRO and the 1760-CBL-PC02 cable, with the Pico-Link network available only on the GFX-70 processors that carry it.
Before ordering, confirm that this catalog number matches the point count, the supply voltage and the output type the machine needs, and confirm which software generation the panel is programmed with, because the classic Pico and the GFX-70 do not share cables or software.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley Micro and Nano systems category.