Product Details:
Payment & Shipping Terms:
|
1764-MM3RTC is a 16K with real-time clock memory module for the MicroLogix 1500: 16K of user memory, clock included.
Its job is transport and recovery — the program goes onto the module at the panel and comes back onto a replacement processor without a laptop.
| 1764-24AWA | Base, 12 ac inputs, 12 relay outputs, ac power | IN STOCK |
| 1764-28BXB1 | Base, 28 point, 24V dc, relay + FET | IN STOCK |
| 1764-LSP | Standard processor, 7.6 KB | IN STOCK |
| 1764-DAT | Data access tool | IN STOCK |
| 1764-MM1 | Memory module, 8K | IN STOCK |
| 1764-MM2 | Memory module, 16K | IN STOCK |
| 1764-MM3 | Memory module, 16K plus recipe data | IN STOCK |
| 1764-MM1RTC | 8K memory with real-time clock | IN STOCK |
| 1764-MM2RTC | 16K memory with real-time clock | IN STOCK |
| 1764-MM3RTC | 16K memory with real-time clock and recipe data | IN STOCK |
| 1764-RTC | Real-time clock | IN STOCK |
| 1764-RPLTB1 | Replacement part | IN STOCK |
| 1764-RPLTB2 | Replacement part | IN STOCK |
| 1764-RPLCDR1 | Replacement part | IN STOCK |
Catalog number |
1764-MM3RTC |
Description |
MicroLogix 1500 memory module with real-time clock |
Memory size |
16K |
Real-time clock |
Included |
Programs held |
One user program at a time |
Fits |
1764-LSP or 1764-LRP processor option slot |
Lifecycle status |
Discontinued March 13, 2017 |
Replacement category |
No planned RA replacement |
UPC |
662074273508 |
Warranty |
1 year standard |
Publication |
1764-UM001 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1764-UM001 (module specifications) and 1764-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
16K of user memory, and carries the real-time clock. The module stores one program at a time; the controller's RUN LED flashes during transfer.
The RTC variant exists because the processor has no clock of its own — timestamped fault records and scheduled operations need this module.
8K modules suit the 1764-LSP and its 8K program limit. Programs above 8K need the enhanced 1764-LRP and a 16K module.
MM3RTC differs from MM2RTC only in recipe data storage from the Data Log Queue, not in user memory.
The module goes into the processor option slot and is loaded or stored from the programming software. It shares that slot with 1764-RTC and 1764-DAT — one device at a time.
Power down before fitting. The connector pins are exposed the moment the cover comes off, and a module fitted with the controller live is how processors get killed.
Discontinued March 13, 2017, replacement category No planned RA replacement. The whole MicroLogix 1500 line was retired in 2017.
Modules are consumable-grade hardware: limited write cycles, easily bent pins, and no way to test them without a working processor.
1764-RTC is the clock-only module; 1764-MM1/MM2/MM3 are the memory-only versions of the same part.
1764-LSP and 1764-LRP processors, 1764-24AWA and 1764-28BXB1 base units.
How much memory does 1764-MM3RTC hold?
16K of user memory.
Does 1764-MM3RTC include a real-time clock?
Yes.
Is 1764-MM3RTC still available from Rockwell?
No. Discontinued March 13, 2017; No planned RA replacement.
Can 1764-MM3RTC store more than one program?
No — one user program at a time.
Does 1764-MM3RTC fit the 1764-LSP?
Yes, in the processor option slot.
1764-MM3RTC is a 16K memory module with recipe data storage and real-time clock in the MicroLogix 1500 system. The controller is assembled from a 1764 processor and a 1764 base unit, with the memory module and the optional display device as separate line items, and Compact I/O 1769 modules as expansion.
| Attribute | Value |
| Catalog number | 1764-MM3RTC |
| Product type | 16K memory module with recipe data storage and real-time clock |
| Family | MicroLogix 1500, bulletin 1764 |
| Memory | 16K user memory |
| Extra functions | Recipe data storage from the Data Log Queue plus a real-time clock |
| Difference from MM2RTC | Same memory and clock, plus the recipe data capability |
| Use | Where the program needs 16K and the data log has to hold recipes after a power cycle |
The rows above are the published values for this part, and they are the ones that decide whether it fits: a memory size against the program, a current draw against the base unit budget, and a series letter against the expansion the machine needs.
Firmware series decides capability, not just version: series C at FRN 6 adds floating point files, programmable limit switch, recipe instructions and message support for the 1769-SDN, and the 16 module bank requires a series C processor, a series B base unit, FRN 6 and RSLogix 500 version 5.10.00 or later. A used controller of the right catalog number but an older series will not reach that configuration.
The default communication state is a commissioning tool rather than a setting: DF1 full-duplex defaults to 19.2K, no parity, node 1, no handshaking, CRC, one stop bit, and the communications toggle push button on the processor switches between that default and the user configuration, with the DCOMM LED showing which is active. That is how a controller with an unknown baud rate is recovered in the field.
MicroLogix 1500 is a two part controller rather than one catalog number: a processor (1764-LSP or the enhanced 1764-LRP with its second RS-232 port) plugs into a base unit that carries the embedded I/O and the supply. A quote that names only the processor is an incomplete quote, and a spare that names only the base unit is a controller that will not run.
Expansion is bounded by current, not by slot count alone: the base unit expansion budget is 2,250 mA at 5V dc with 400 mA at 24V dc, and each additional bank needs a 1769 power supply, a 1769-CRL or -CRR cable and a 1769-ECL or -ECR end cap. Without the end cap the bank is not a valid configuration, which is a detail that shows up only when the system is powered.
Before ordering, confirm the processor series and firmware release against the expansion the machine needs, confirm the memory module size against the actual program, and confirm the current budget of the base unit expansion against the modules already selected.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley MicroLogix 1500 1764 controllers category.