Product Details:
Payment & Shipping Terms:
|
1764-DAT is the Data Access Tool for the MicroLogix 1500: a module that lets someone at the panel read and change data file values without a laptop and without programming software.
It exists because a 1500 in a pump station or a packaging machine often has no PC anywhere near it, and recipe or setpoint changes still have to happen.
| 1764-24AWA | Base, 12 ac inputs, 12 relay outputs, ac power | IN STOCK |
| 1764-28BXB1 | Base, 28 point, 24V dc, relay + FET | IN STOCK |
| 1764-LSP | Standard processor, 7.6 KB | IN STOCK |
| 1764-DAT | Data access tool | IN STOCK |
| 1764-MM1 | Memory module, 8K | IN STOCK |
| 1764-MM2 | Memory module, 16K | IN STOCK |
| 1764-MM3 | Memory module, 16K plus recipe data | IN STOCK |
| 1764-MM1RTC | 8K memory with real-time clock | IN STOCK |
| 1764-MM2RTC | 16K memory with real-time clock | IN STOCK |
| 1764-MM3RTC | 16K memory with real-time clock and recipe data | IN STOCK |
| 1764-RTC | Real-time clock | IN STOCK |
| 1764-RPLTB1 | Replacement part | IN STOCK |
| 1764-RPLTB2 | Replacement part | IN STOCK |
| 1764-RPLCDR1 | Replacement part | IN STOCK |
Catalog number |
1764-DAT |
Description |
MicroLogix 1500 Data Access Tool |
Function |
Operator read/write access to controller data files without programming software |
Fits |
Processor option slot (same slot as the memory module or real-time clock) |
Used with |
MicroLogix 1500 with 1764-LSP or 1764-LRP processor |
Lifecycle status |
Discontinued June 30, 2017 |
Replacement category |
No planned RA replacement |
UPC |
611320018417 |
Warranty |
1 year standard |
Publication |
1764-UM001 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1764-UM001 (module specifications) and 1764-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Provides access to the controller's data files — the integer, floating point and bit files a program writes setpoints and recipes into.
It is an operator interface for data, not a programming terminal. Ladder logic cannot be edited from it.
The processor's option slot — the same physical position as a memory module or real-time clock. DAT and memory module cannot be installed at the same time.
Fitting a DAT therefore means giving up the program archive slot, which is the trade-off most sites did not want to make.
Discontinued June 30, 2017, replacement category No planned RA replacement — unlike the bases and processor, Rockwell did not point at a successor for this accessory.
With no replacement category, supply is whatever is left in the secondary market. That is the honest answer for a used DAT: availability is luck, not planning.
A small HMI on the serial port covers the same need and is still orderable. For a site already carrying a spare HMI, the DAT is not worth chasing.
Where the DAT is already installed and working, the risk is mechanical: the module sits exposed on the processor and is the first thing damaged when a panel door is closed on it.
1764-LSP and 1764-LRP processors; 1764-RTC and 1764-MM1/MM2/MM3 memory modules that compete for the same slot.
Bases: 1764-24AWA and 1764-28BXB1.
What is 1764-DAT?
The MicroLogix 1500 Data Access Tool for reading and changing data file values.
Can 1764-DAT edit ladder logic?
No. It gives access to data files only.
Where is 1764-DAT installed?
In the processor option slot, the same slot as a memory module.
Is 1764-DAT still available from Rockwell?
No. Discontinued June 30, 2017, with No planned RA replacement.
Can a memory module and a DAT be fitted together?
No. They share one slot.
1764-DAT is a data access tool in the MicroLogix 1500 system. The controller is assembled from a 1764 processor and a 1764 base unit, with the memory module and the optional display device as separate line items, and Compact I/O 1769 modules as expansion.
| Attribute | Value |
| Catalog number | 1764-DAT |
| Product type | data access tool |
| Family | MicroLogix 1500, bulletin 1764 |
| Backplane current | 350 mA at 5V dc |
| Function | Handheld programming and data access device for the MicroLogix 1500 |
| Access | The processor door or the DAT has to be removed to reach the communications toggle push button |
| Optional | Current is drawn only when the unit is installed |
The rows above are the published values for this part, and they are the ones that decide whether it fits: a memory size against the program, a current draw against the base unit budget, and a series letter against the expansion the machine needs.
Expansion is bounded by current, not by slot count alone: the base unit expansion budget is 2,250 mA at 5V dc with 400 mA at 24V dc, and each additional bank needs a 1769 power supply, a 1769-CRL or -CRR cable and a 1769-ECL or -ECR end cap. Without the end cap the bank is not a valid configuration, which is a detail that shows up only when the system is powered.
Power supply distance rating is the other planning limit: an I/O module may sit at most 8 modules from its power supply on most modules, and only 4 for the 1769-HSC and the 1769-SDN. A 16 module bank built without regard to that rating powers up and then behaves unpredictably at the far end.
The default communication state is a commissioning tool rather than a setting: DF1 full-duplex defaults to 19.2K, no parity, node 1, no handshaking, CRC, one stop bit, and the communications toggle push button on the processor switches between that default and the user configuration, with the DCOMM LED showing which is active. That is how a controller with an unknown baud rate is recovered in the field.
MicroLogix 1500 is a two part controller rather than one catalog number: a processor (1764-LSP or the enhanced 1764-LRP with its second RS-232 port) plugs into a base unit that carries the embedded I/O and the supply. A quote that names only the processor is an incomplete quote, and a spare that names only the base unit is a controller that will not run.
Before ordering, confirm the processor series and firmware release against the expansion the machine needs, confirm the memory module size against the actual program, and confirm the current budget of the base unit expansion against the modules already selected.
The Allen-Bradley MicroLogix 1500 1764 controllers category groups the other catalog numbers, options and spare parts in the same range.