Product Details:
Payment & Shipping Terms:
|
1764-28BXB1 is a MicroLogix 1500 base unit: the I/O and power half of a controller that only becomes a PLC when a 1764-LSP processor is fitted on top.
That two-piece construction is the reason the base keeps turning up in spares lists years after the line was retired — a base with a dead processor can be brought back with a processor alone, and vice versa.
| 1764-24AWA | Base, 12 ac inputs, 12 relay outputs, ac power | IN STOCK |
| 1764-28BXB1 | Base, 28 point, 24V dc, relay + FET | IN STOCK |
| 1764-LSP | Standard processor, 7.6 KB | IN STOCK |
| 1764-DAT | Data access tool | IN STOCK |
| 1764-MM1 | Memory module, 8K | IN STOCK |
| 1764-MM2 | Memory module, 16K | IN STOCK |
| 1764-MM3 | Memory module, 16K plus recipe data | IN STOCK |
| 1764-MM1RTC | 8K memory with real-time clock | IN STOCK |
| 1764-MM2RTC | 16K memory with real-time clock | IN STOCK |
| 1764-MM3RTC | 16K memory with real-time clock and recipe data | IN STOCK |
| 1764-RTC | Real-time clock | IN STOCK |
| 1764-RPLTB1 | Replacement part | IN STOCK |
| 1764-RPLTB2 | Replacement part | IN STOCK |
| 1764-RPLCDR1 | Replacement part | IN STOCK |
Catalog number |
1764-28BXB1 |
Description |
MicroLogix 1500 base, 28 point, 24V dc |
Line power |
24V dc |
Inputs |
8 standard 24V dc inputs plus 8 fast 24V dc inputs |
Outputs |
6 relay outputs (2 isolated), 4 standard 24V dc FET, 2 fast 24V dc FET |
High-speed I/O |
8 inputs at 20 kHz, 2 outputs at 20 kHz |
Dimensions |
118 mm high (138 mm with DIN latch open), 168 mm wide, 87 mm deep |
Relay contact rating |
240V ac 7.5 A make / 0.75 A break, 120V ac 15 A make / 1.5 A break |
Continuous relay current |
8 A per common; 18 A at 150V and at 240V per controller |
Heat dissipation |
18 W + (0.3 x system loading) |
Mounting |
Horizontal, Compact I/O expansion to the right, 50 mm free space all round |
Lifecycle status |
Discontinued June 30, 2017 |
Replacement category |
Functional Replacement |
UPC |
781180892929 |
Publication |
1764-UM001 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1764-UM001 (module specifications) and 1764-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
8 standard 24V dc inputs plus 8 fast 24V dc inputs on the 24V dc line power.
6 relay outputs (2 isolated), 4 standard 24V dc FET, 2 fast 24V dc FET
Two relays on the base are isolated from the rest, which lets one contact switch a different circuit potential without a separate interposing relay.
Relay contacts are rated 7.5 A make and 0.75 A break at 240V ac, 15 A make and 1.5 A break at 120V ac, 2.5 A continuous. The total load controlled by the base is limited to 1440 VA break.
Continuous relay current is 8 A per common; 18 A at 150V and at 240V per controller, and per-common grouping therefore matters when several outputs feed the same machine section.
18 W + (0.3 x system loading). A fully loaded base in a sealed enclosure is a real heat source — the 50 mm of free space on all sides is the minimum, not a target.
118 mm high with the DIN latch closed, 138 mm open, 168 mm wide, 87 mm deep.
The base is useless without a processor: 1764-LSP (7.6 KB, standard) or 1764-LRP (enhanced, RS-232 port). Only the LRP supports programs above 8K, which is why MM2/MM3 modules are specified with it.
Compact I/O expansion modules mount to the right of the base and draw from its backplane supply.
Discontinued June 30, 2017, replacement category Functional Replacement — Rockwell pointed customers at a successor family rather than a like-for-like part.
For a running line the practical path is a tested spare base, or a migration project. Mixing a used base with a used processor of unknown history is how a panel ends up with two faults instead of one.
What I/O does 1764-28BXB1 have?
8 standard 24V dc inputs plus 8 fast 24V dc inputs; 6 relay outputs (2 isolated), 4 standard 24V dc FET, 2 fast 24V dc FET.
What line power does 1764-28BXB1 take?
24V dc.
Is 1764-28BXB1 still available from Rockwell?
No. Discontinued June 30, 2017; replacement category Functional Replacement.
Does 1764-28BXB1 work without a processor?
No. It needs a 1764-LSP or 1764-LRP processor.
What is the relay rating on 1764-28BXB1?
240V ac 7.5 A make / 0.75 A break, 2.5 A continuous, 1440 VA total load break.
1764-28BXB1 is a 28 point base unit with FET outputs in the MicroLogix 1500 system. The controller is assembled from a 1764 processor and a 1764 base unit, with the memory module and the optional display device as separate line items, and Compact I/O 1769 modules as expansion.
| Attribute | Value |
| Catalog number | 1764-28BXB1 |
| Product type | 28 point base unit with FET outputs |
| Family | MicroLogix 1500, bulletin 1764 |
| Points | 28 I/O points in the base unit |
| Output type | The FET transistor outputs are available on the 1764-28BXB base unit only |
| Base unit role | Carries the embedded I/O and the supply for the processor |
| Expansion budget | Base unit expansion 2,250 mA at 5V dc and 400 mA at 24V dc |
| Related base units | 1764-24AWA and 1764-24BWA, which do not carry FET outputs |
The rows above are the published values for this part, and they are the ones that decide whether it fits: a memory size against the program, a current draw against the base unit budget, and a series letter against the expansion the machine needs.
The default communication state is a commissioning tool rather than a setting: DF1 full-duplex defaults to 19.2K, no parity, node 1, no handshaking, CRC, one stop bit, and the communications toggle push button on the processor switches between that default and the user configuration, with the DCOMM LED showing which is active. That is how a controller with an unknown baud rate is recovered in the field.
Modbus RTU slave is a series B and later capability: the protocol maps coils, contacts, input registers and status words into MicroLogix data files, with four ranges mappable and three Modbus ranges fixed to the status file. A series A processor cannot be turned into a Modbus slave by configuration alone.
The memory module ladder is easy to mis-order: 1764-MM1 is 8K, 1764-MM2 and 1764-MM3 are 16K, and the RTC suffix adds a real-time clock on the same module. For a 1764-LRP program larger than 8K the published instruction is to use 1764-MM2 or 1764-MM2RTC, and the 1764-MM3 parts differ only by being able to store recipe data from the Data Log Queue.
Power supply distance rating is the other planning limit: an I/O module may sit at most 8 modules from its power supply on most modules, and only 4 for the 1769-HSC and the 1769-SDN. A 16 module bank built without regard to that rating powers up and then behaves unpredictably at the far end.
Before ordering, confirm the processor series and firmware release against the expansion the machine needs, confirm the memory module size against the actual program, and confirm the current budget of the base unit expansion against the modules already selected.
Related models, options and spare parts for this range are listed in the Allen-Bradley MicroLogix 1500 1764 controllers category.