1792D-8BVT8D 8 input / 8 output module, 8 connectors
1792D-8BVT8D is an ArmorBlock MaXum catalog number: armorblock maxum 8 input / 8 output module, 8 connectors. The figures below come from the ArmorBlock MaXum tables of Publication 1792-SG001A-EN-P, July 2004, which is the publication that lists this number with its point count, ratings, connector count and diagnostic level.
At a glance
Every row below is taken from the ArmorBlock MaXum tables of Publication 1792-SG001A-EN-P, July 2004. Nothing is inferred from the catalog number, and a value the publication does not print is left out rather than guessed.
| Inputs | 8, sink/source |
| Input voltage, operating | 10 to 25 V dc |
| Input current, off-state, max | 1.5 mA |
| Outputs | 8, source |
| Output voltage, operating | 10 to 30 V dc |
| Output current, on-state, max | 0.5 A |
| Number of connectors | 8 |
| Diagnostics | Connector-level |
| DeviceNet current | 470 mA with 8 sensors at 25 mA |
| Enclosure type rating | IP67, sealed housing rated NEMA 4X and 6P |
| Mounting | On-machine |
| Operating temperature | -25 to 60 °C (-13 to 140 °F) |
| Storage temperature | -25 to 80 °C (-13 to 176 °F) |
| Relative humidity | 5 to 100 percent |
| Shock, operating | 30 g peak acceleration, 11 (±1) ms pulse width |
| Certifications | CSA, CE |
Attributes printed for this number
The rows in the table are the attributes that separate this number from its neighbours in the 1792D range: the point count and type, the voltage window, the maximum on-state or off-state current, the number of M12 connectors, the diagnostic level and the DeviceNet current the block draws. They are the values to compare first when a substitute or a second source is proposed, because the enclosure, temperature range and certification set are common to the family.
Where it sits in the range
ArmorBlock MaXum is the diagnostic-rich branch of the ArmorBlock family: the 1792D blocks are stand-alone 24 V dc I/O modules that talk DeviceNet and sit in a sealed IP67 housing, so they mount on the machine next to sensors and actuators without an extra enclosure. The family is built around a cable base, which is what carries the block and brings in the network and, where needed, output power.
Series B MaXum modules add DeviceLogix, so outputs can be controlled and status handled inside the block through function-block logic in RSNetWorx for DeviceNet, without a controller in the loop. The same generation also carries rotary node address switches, selectable input filters, universal sinking/sourcing inputs, electronic fusing and resettable faulted I/O, which is the set of features that separates MaXum from the plain 1732 ArmorBlock I/O.
Checks before the number is ordered
- Confirm the point count and mix you need against the table above: input-only, output-only and combination blocks are separate catalog numbers, and the connector count follows the block.
- Add a cable base unless this is the 1792D-88HC high current block; the base decides whether outputs are fed from an external 24 V dc source or from DeviceNet power.
- Add the DeviceNet current of the block to the sensor load on the segment before committing the power budget, using the figure printed above at its stated sensor count.
Questions engineers ask
What does 1792D-8BVT8D provide?
ArmorBlock MaXum 8 input / 8 output module, 8 connectors, as listed in the ArmorBlock MaXum catalogue tables of Publication 1792-SG001A-EN-P, July 2004.
Does 1792D-8BVT8D need a separate cable base?
Yes. Each ArmorBlock MaXum I/O block, except for the 1792D-88HC high current block, requires a separate cable base.
What connectors does 1792D-8BVT8D use?
M12 quick-disconnect terminations, with %s connectors on the block.
What are the output ratings of 1792D-8BVT8D?
Outputs are source type with a nominal 24 V dc and an operating range of 10 to 30 V dc, rated 0.5 A maximum on-state current per point.
What are the input ratings of 1792D-8BVT8D?
Inputs are sink/source on all MaXum input and combination blocks except 1792D-8BIO8E, which is sink only, operating over 10 to 25 V dc with 1.5 mA maximum off-state current.
What diagnostic level does 1792D-8BVT8D offer?
Diagnostics on this catalog number are connector-level, as printed in the MaXum digital I/O tables.
How much DeviceNet current does 1792D-8BVT8D draw?
The block draws 470 mA with 8 sensors at 25 mA from the DeviceNet network.
Documentation
- Publication 1792-SG001A-EN-P, July 2004
- RSNetWorx for DeviceNet configuration software is used to set module parameters.
Related numbers
- 1792D-12BVT4D
- 1792D-8BVT8CD
- 1792D-4BVT4D
- 1792D-4BV4D
- 1792D-8BIO8E
- 1792D-0B4D
- 1792D-0B8D
- 1792D-0VT16E
- 1792D-16BVT0D
Catalog data quoted from publication 1792-SG001A-EN-P. Availability and pricing are quoted per order.