logo
Home ProductsAB Drives & Motors

Allen Bradley PowerFlex 20BC015A3AYNACC1

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PowerFlex 20BC015A3AYNACC1

China Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier
Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier Allen Bradley PowerFlex 20BC015A3AYNACC1 supplier

Large Image :  Allen Bradley PowerFlex 20BC015A3AYNACC1

Product Details:

Place of Origin: Made in MEXICO
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PowerFlex 20BC015A3AYNACC1

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: 1735.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: T/T, Western Union and Paypal.
Supply Ability: 2 PCS
Detailed Product Description

20BC015A3AYNACC1

This page documents catalog number 20BC015A3AYNACC1, a PowerFlex 700 drive on the 400 V AC three-phase class: 7.5 kW normal duty, 5.5 kW heavy duty, 15.4 A continuous normal-duty output, frame 1, enclosure A. The kW, current, overload, protection and terminal figures are read from the published technical data for the 400 V class, not from a nameplate.

Decode and published rating

FieldValue
Catalog number20BC015A3AYNACC1
Family (characters 1-3)20B - PowerFlex 700 adjustable frequency AC drive
Voltage class (character 4)C - 400 V AC three-phase
Rating code (characters 5-7)015 - 15.4 A continuous normal duty
Normal duty rating7.5 kW
Heavy duty rating5.5 kW
Frame size1
Enclosure (character 8)A - IP20, NEMA/UL Type 1
Interface position (character 9)3 - carried in the string, not translated into a HIM part number here
Network position (character 10)A - carried in the string, not translated into a communication option here
Brake IGBT (character 11)Y - brake IGBT fitted
Internal braking resistor (character 12)N - no internal resistor
Control (character 13)A - Standard control, volts/hertz and sensorless vector

One number, two duty ratings

The published row for this code carries both ratings. Normal duty is 7.5 kW at 15.4 A continuous; heavy duty is 5.5 kW on the same hardware. The overload figures sit beside them at 17.2 A for 60 seconds and 23.1 A for 3 seconds, which is the envelope the drive is allowed to deliver on top of the continuous figure. An application that starts a loaded conveyor is sized on the heavy-duty column; a fan or a centrifugal pump that ramps over thirty seconds can be sized on the normal-duty one, and using the normal-duty column for a loaded start is a torque deficit that shows up as an overcurrent trip rather than as a slow ramp.

The input figures in the same row are 14.4 A and the kVA is published next to them, which is what a supply transformer and a line-side disconnect are sized against. Input current on a drive is not the motor current: it is lower than the output current at full load because the DC link carries the power at a different voltage, and a panel wired on the output rating is over-fused on the input.

Protection and the bill of materials

The 400 V class publishes protection as a floor and a ceiling per code. For this catalog number the dual-element time-delay fuse range is 20 to 30 A, the non-time-delay fuse range is 20 to 60 A, the inverse-time circuit breaker maximum is 60 A and the instantaneous-trip motor circuit protector maximum is 20 A. These are maxima with NEC guidance beside them, not one number to copy: the note under the table sets the NEC floor at 125 percent of motor full load amps, which is why the minimum and maximum columns exist separately.

The same row lists a self-protected combination motor controller at this rating as 140M-C2E-C20, 140M-D8E-C20 or 140M-F8E-C20, and the enclosure volume for a combination controller as 7,269 cubic inches. That volume is the cabinet space the Type E starter has to be installed in, and it is quoted in the same row as the fuse sizes because the two decisions are made together.

The Type E controller is the device to check against the grounding system before it reaches the bill of materials. Bulletin 140M self-protected combination motor controllers are UL listed for 208 V wye or delta, 240 V wye or delta, 480 V/277 V and 600 V/347 V, and are explicitly not listed for use on 480 V or 600 V delta-delta, corner-grounded or high-resistance grounded systems. On a 400 V class drive the device is usually a European motor protection circuit breaker rather than a 140M, and the same question is asked of that device against the site grounding arrangement.

Reactors are a separate selection and are not transferable between voltage classes. The family publishes 3 percent and 5 percent impedance tables per voltage class, with the input reactor sized on NEC fundamental motor amps and the output reactor on the drive rated output current; the pair for this code is read from the 400 V table at the duty the drive will run. A 1321 reactor with the same current rating taken off a 480 V row is the wrong impedance at 400 V.

Terminals, frame and mounting

On frame 1 the power terminal block accepts 4.0 mm2 (12 AWG) maximum and 0.5 mm2 (22 AWG) minimum at 1.7 N-m (15 lb-in), with 0.8 N-m (7 lb-in). The shield terminal is common to frames 0 to 6 at 1.6 N-m (14 lb-in), and the AUX terminal block for control power on frames 0 to 4 takes 1.5 mm2 (16 AWG) maximum and 0.2 mm2 (24 AWG) minimum. The terminal block does not change between the codes in this block, so a re-rated drive drops into the same wiring without a new lug kit.

Mechanically the drive is a footprint on the frame 0 and 1 terminal pattern; the outline is read from the frame 1 dimension drawing rather than from the weight table. Weights in the family table include the HIM and the standard I/O, so a spare ordered without either is lighter than the printed figure, and a panel drawing that uses the table weight for a bare chassis is carrying a few kilograms that are not there.

Heat loss for this rating is published in the family watts-loss table as an external figure, an internal figure and a total at full load, full speed and default carrier. The split matters for cabinet sizing: the external watts leave through the heatsink and therefore sit outside the cabinet on a flange mount and inside it on a Type 1 mount, while the internal watts stay in the cabinet on every mounting style.

The enclosure character reads A, which the family defines as IP20, NEMA/UL Type 1, intended for cabinet or wall mounting with a removable conduit plate, with no dust-tight rating of its own. That is an IP20 product: it protects against finger contact and solid objects above 12 mm and has no water rating, so the cabinet around it is what makes the installation suitable for a wash-down or outdoor location.

Braking, control and what the string leaves open

Character 11 reads Y and character 12 reads N. The brake IGBT is the switch that lets the drive dump regenerative energy into an external resistor, and the internal resistor is a separate device that is only present when the string says so. On this frame the IGBT is standard rather than optional, so the character records a state that is already fixed by the hardware: a page that promises braking capability from the current code alone is promising something the code does not carry.

Character 13 reads A for control, which on this family is the difference between Standard control and the Vector control cassette that is DPI only. That is a control-bandwidth and feedback decision, not an option that can be added by parameter later, and it is the character a replacement drive has to match when a machine is being re-driven rather than re-engineered.

Three positions are carried rather than translated: the interface position reads 3, the network position reads A, and positions 14 to 16 read CC1. This page does not turn them into part numbers, because the family option tables resolve them per code and a translation done from the string alone is the kind of guess that ends up as the wrong spare on the shelf.

Single-phase operation is published for this class at 25 degrees C with the output current derated by 50 percent of the three-phase rating, and the table lists 20BC15 as 3.75 kW with 12.5 A input and 7.7 A output on a 380 to 400 V single-phase supply. That is a supply-arrangement answer for a small machine on a single-phase service, not a normal-duty rating, and the ambient ceiling drops with it.

The practical ordering question on a 400 V class drive is rarely the current code, because three codes cover this whole block of the catalog. It is the option string behind that code, and that string is where two otherwise identical drives become different products.

Related catalog numbers in this class: 20BC022A0AYNACB0.

No lifecycle statement and no price is implied. The kW ratings, output current, overload figures, fuse and breaker ranges, combination-controller catalogs, terminal data and enclosure volume are quoted from the PowerFlex 700 published technical data for the 400 V class.