Product Details:
Payment & Shipping Terms:
|
The 1794-ACN15K is the coated build of the single-media ControlNet adapter, for panels where the standard part's uncoated board would not survive the atmosphere.
Electrically it is the 1794-ACN15 — one BNC, 8 modules, 640 mA of 5V Flexbus — with the K suffix carrying the conformal coating.
| 1794-AENT | EtherNet/IP adapter, single RJ45, 8 modules | IN STOCK |
| 1794-AENTR | dual-port EtherNet/IP adapter, redundancy capable | IN STOCK |
| 1794-AENTRXT | dual-port EtherNet/IP adapter, extended temperature | IN STOCK |
| 1794-ACN15 | ControlNet adapter, 5 Mbps, 8 modules | IN STOCK |
| 1794-ACN15K | ControlNet adapter, 5 Mbps, conformal coated | IN STOCK |
| 1794-ACNR | ControlNet adapter with redundant media | IN STOCK |
| 1794-ACNR15XT | ControlNet adapter, redundant media, extended temperature | IN STOCK |
| 1794-ACN | ControlNet adapter module, 8 modules | IN STOCK |
| 1794-ADN | DeviceNet adapter, 8 modules | IN STOCK |
| 1794-ADNK | DeviceNet adapter, conformal coated | IN STOCK |
| 1794-APB | Profibus DP adapter, 8 modules | IN STOCK |
| 1794-APBDPV1 | Profibus DP-V1 adapter, 8 modules | IN STOCK |
| 1794-ASB | Remote I/O adapter, 8 modules | IN STOCK |
| 1794-ASB2 | Remote I/O adapter, extended functionality | IN STOCK |
| 1794-ASBLT | Remote I/O adapter with built-in termination | IN STOCK |
Application |
FLEX I/O ControlNet adapter, coated |
Cat Num |
1794-ACN15K |
Brand Name |
Rockwell |
I/O module capacity |
8 modules |
Supply voltage, input |
19.2...31.2V DC, 400 mA |
Supply voltage, output |
5V DC, 640 mA |
Inrush current |
14 A for 2 ms |
Communication rate |
5 Mbps |
Coating |
Conformal coated |
ControlNet cable |
Belden RG-6/U |
Operating temperature |
-25...55 deg C |
Same-family catalog numbers: 1794-ACN15K, 1794-ACNR, 1794-ACNR15XT, 1794-ACN. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1794 family.
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Conformal coating on the assembly, for condensing and corrosive air.
Electrical ratings unchanged: 19.2...31.2V DC input at 400 mA, 5V 640 mA output.
Still 5 Mbps ControlNet, single BNC, node selectable by dial.
Still 8 modules behind the adapter.
Same 87.4 x 94 x 92 mm envelope and 220 g weight as the uncoated adapter.
22...12 AWG single wire or 22...16 AWG double wire at 105 deg C rating.
0.8 N*m torque on the power terminals, and a NAP port for programming access.
-25...55 deg C operating range.
The faceplate keeps the same red/green I/O status and Comm A indicators as the uncoated adapter, so a swap needs no new diagnostics procedure.
I/O status and Comm A indicators are red/green on the faceplate.
Firmware revision is displayed numerically in RSNetWorx for ControlNet revision 3.21 or later.
Series C drop-in replacement behaviour carries over from the standard part.
No second BNC; redundancy needs the 1794-ACNR15 family.
Corrosive plant areas on existing ControlNet.
Washdown and coastal cabinets.
Not extended temperature; the XT part is the -25...70 deg C option.
Not EtherNet/IP.
Coated FLEX I/O islands on ControlNet.
Spare-part stock where the coated build is the standard.
Not for redundant media.
Not for DeviceNet.
What does the K suffix mean on the 1794-ACN15K?
A conformally coated assembly.
How many modules can it carry?
8 FLEX I/O modules.
What is the ControlNet rate?
5 Mbps over Belden RG-6/U.
What is the supply requirement?
19.2...31.2V DC at 400 mA, 14 A inrush for 2 ms.
Does it support redundant media?
No, that requires the 1794-ACNR15 or 1794-ACNR15XT.
What is the operating range?
-25...55 deg C.
All values on this page are taken from Rockwell Automation publications 1794-IN101 (Series B) and 1794-IN128F-EN-P (Series D) for the FLEX I/O ControlNet adapter modules. Where the two series differ, both figures are shown rather than merged.
The 1794-ACN15K is the conformally coated version of the single-media ControlNet adapter. The K suffix is defined in 1794-IN101 as a coating that meets the noxious gas requirements of ISA/ANSI-71.040 1985 Class G3, so the difference between this part and the plain 1794-ACN15 is the environment it survives, not the function it performs.
Electrically the K variant is identical to the adapter it is based on: eight I/O modules, 5 Mbps ControlNet, 640 mA at 5 V DC onto the backplane, 19.2...31.2 V DC input, node address 01...99 on the two dials, and the same terminal arrangement with -V common on C, +V DC on D, and pass-through on E and F.
The G3 classification is the practical selection criterion. Class G3 covers corrosive gas environments of the kind found in rubber, pulp, wastewater and some food plants, where hydrogen sulphide or chlorine compounds attack bare copper and tin plating over years rather than months. A conformal coat slows that attack on the adapter board; it does not make the slice watertight, and the enclosure still has to be selected on its own IP rating.
Mechanically the K part follows the Series B envelope, 87 x 94 x 69 mm, with 0.8 N*m (7 lb-in) terminal torque and a 22...12 AWG single-wire range. The depth difference against the later Series D adapter is the one dimension to watch when a coated replacement goes into a cabinet originally built around a Series D unit.
Coated boards change two service habits. Visual inspection of solder joints is no longer possible, so diagnostics move to the LED table: flashing red on Status still means a module was removed or the wrong module was inserted, and a solid red Status with a healthy network is an adapter failure rather than a coating problem. And any field repair involving soldering or reflow destroys the coating, so the unit is replaced rather than repaired.
Hazardous-area limits are unchanged from the uncoated part: Class I Division 2 Groups A, B, C, D, ATEX Zone 2 Ex nA IIC T4 Gc, with the same 140% transient clamp and IP54 enclosure requirement.
| Attribute | Value |
| I/O capacity | 8 FLEX I/O modules on the backplane |
| Input power | 19.2...31.2 V DC, 400 mA (Series D) / 450 mA maximum, 330 mA at 24 V (Series B) |
| Backplane output | 5 V DC, 640 mA maximum |
| Inrush | 14 A for 2 ms (Series D); 23 A for 2 ms (Series B) |
| Communication rate | 5 Mbps ControlNet |
| Isolation | 50 V continuous, basic insulation; type tested 860 V AC for 60 s power to system, power to ControlNet and ControlNet to system (Series D). No isolation between ControlNet channels. |
| Power dissipation | 3.4 W maximum at 19.2 V DC (Series D); 4.6 W maximum at 19.2 V DC (Series B) |
| Terminal torque | 0.8 N*m (7 lb-in) on terminals C, D, E, F |
| Wire size | Single wire 0.33...2.5 mm2 (22...12 AWG); double wire 0.33...1.3 mm2 (22...16 AWG, not intermixed); 75 °C rated, 1.2 mm insulation maximum |
| Dimensions | 87.4 x 94 x 92 mm (3.44 x 3.7 x 3.6 in.), Series D; 87 x 94 x 69 mm (3.4 x 3.7 x 2.7 in.), Series B |
| Weight | 220 g (7.76 oz) |
| Operating temperature | -25...+55 °C for 1794-ACN15 and 1794-ACNR15; -25...+70 °C for 1794-ACNR15XT |
Mounting follows the same sequence as the terminal bases: hook the rear lip on a 35 x 7.5 x 1 mm top-hat rail (199-DR1 / EN 50022), rotate onto the rail, press down until the locking tab snaps, then push the Flexbus connector into the adapter. The first terminal base hooks into the notch on the right rear of the adapter, and that mechanical link is what keeps the backplane connection from opening under vibration.
Panel or wall mounting uses the 1794-NM1 mounting kit, covered by a separate installation instruction rather than by the adapter publication.
This part sits in the Allen-Bradley Flex I/O 1794 modules category, with the other models and spare parts listed alongside it.