The 1794-OW8XT is the extended-temperature version of the eight-channel relay output, rated -20...70 deg C and conformally coated, with the same 2 A Form A contacts.
The contacts and the fuse are unchanged; the coating and the temperature window are the reason to specify it in an unheated panel that still switches AC coils.
| 1794-OB8 | 8-point 24V DC sourcing output module | IN STOCK |
| 1794-OB8EP | 8-point 2 A electronically fused sourcing output module | IN STOCK |
| 1794-OB16 | 16-point 24V DC sourcing output module | IN STOCK |
| 1794-OB16P | 16-point protected sourcing output module | IN STOCK |
| 1794-OB16D | 16-point diagnostic 24V DC output module | IN STOCK |
| 1794-OB32P | 32-point protected sourcing output module | IN STOCK |
| 1794-OB16PXT | 16-point protected sourcing output, extended temperature | IN STOCK |
| 1794-OB8EPXT | 8-point 2 A electronically fused output, extended temperature | IN STOCK |
| 1794-OV16 | 16-point sinking output module | IN STOCK |
| 1794-OV16P | 16-point protected sinking output module | IN STOCK |
| 1794-OV32 | 32-point sinking output module | IN STOCK |
| 1794-OC16 | 16-point 48V DC sourcing output module | IN STOCK |
| 1794-OG16 | 16-point 5V DC sourcing output module | IN STOCK |
| 1794-OW8 | 8-point isolated relay output module | IN STOCK |
Application |
FLEX I/O relay output, 1794 terminal base |
Cat Num |
1794-OW8XT |
Brand Name |
Rockwell |
Outputs |
8, Form A normally open relay, isolated |
Contact rating |
2 A at 5...30V DC, 0.22 A at 125V DC, 2 A at 125V AC, 2 A at 250V AC |
Minimum load |
100 uA at 100 mV |
On/off delay |
10 ms |
Switching frequency |
0.3 Hz |
Mechanical life |
100,000 operations |
Fuse |
3.0 A 250V slow-blow, Littelfuse 239003 |
Isolation |
250V basic relay to relay, backplane and power; 1500V AC 60 s, 3250V DC 60 s |
External supply current |
126 mA at 24V DC |
Power dissipation |
5.5 W at 31.2V DC (18.8 BTU/hr) |
Operating temperature |
-20...70 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Eight Form A normally open contacts, isolated relay to relay, rated 2 A at 250V AC and 125V AC, 2 A at 5...30V DC and 0.22 A at 125V DC.
Minimum load 100 uA at 100 mV and 30 mOhm contact resistance are carried over, as is the 1.2 ms bounce time.
10 ms on and off delay and 0.3 Hz switching frequency are the mechanical limits at either temperature rating.
Mechanical life of 100,000 operations is the number to use in a maintenance plan, and it does not improve with the extended temperature option.
-20...70 deg C operating range against -20...55 deg C on the standard 1794-OW8.
Conformal coating protects the relay driver board through condensation at cold start.
126 mA at 24V DC against 125 mA on the standard card — effectively the same consumption.
Isolation unchanged: 250V basic relay to relay, backplane and power, with 1500V AC for 60 s and 3250V DC for 60 s type tests.
3.0 A 250V slow-blow fuse, Littelfuse 239003, protects the output group and is socketed for replacement.
An AC coil needs a snubber to reduce contact erosion, and the resulting 1.0 mA leakage at 240V AC has to suit the load's off-state.
The fuse is a wear item: a contact that welds will blow the group fuse, so spares belong in the panel.
5.5 W at 31.2V DC (18.8 BTU/hr) is the heat, unchanged from the standard card.
19.2...31.2V external supply is the input window, so a 24V rail that sags to 19V on a contactor pull-in still holds the relay coils.
Keep AC and DC circuits in separate bundles even though the contacts are isolated.
Do not use the relay for a fast pulse train; 0.3 Hz is the published ceiling at any temperature.
Check the low-temperature behaviour of the load, not only the module: a contactor coil at -20 deg C pulls more current than at 25 deg C.
Field power removed before insertion, following the FlexBus sequence in the publication.
Unheated panels switching AC coils down to -20 deg C.
Mixed AC and DC loads that need dry contacts at 250V.
Not for fast switching; a solid-state output is the only option above 0.3 Hz.
Not for high DC voltage; 0.22 A at 125V DC remains the limit.
How does the 1794-OW8XT differ from the 1794-OW8?
It is rated -20...70 deg C and conformally coated; the contact ratings and fuse are the same.
What is the contact rating?
2 A at 250V AC and 125V AC, 2 A at 5...30V DC, 0.22 A at 125V DC.
What is the switching limit?
10 ms delay and 0.3 Hz switching frequency.
What fuse does it use?
A 3.0 A 250V slow-blow fuse, Littelfuse 239003.
What current does the module draw?
126 mA at 24V DC.
What is the mechanical life?
100,000 operations.
1794-OW8XT is a relay output with 8 outputs in the FLEX I/O range, rated for isolated electromagnetic relays. It mounts on the 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TBNF, 1794-TB3SK, 1794-TBNK terminal base unit, which is ordered separately and is the part that actually carries the field terminals.
| Attribute | Value |
| Catalog number | 1794-OW8XT |
| Module type | relay output |
| Points | 8 outputs |
| Electrical range | isolated electromagnetic relays |
| Terminal base unit | 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TBNF, 1794-TB3SK, 1794-TBNK |
| Relay type | Electromagnetic relays, isolated per output as opposed to the solid state output modules |
| Base note | The 1794-TBNF is listed for this module because the fused NEMA base is a permitted field termination |
The XT suffix is the extended temperature build rather than a different circuit: the same terminal base list, the same field voltage, and an operating range that reaches 70 C instead of the 55 C of the standard version. Specifying XT and then derating the panel back to 55 C gives away the only thing that was paid for.
FLEX I/O is a backplane-free architecture: the terminal base unit snaps onto the DIN rail to the right of the adapter and the bases plug together to form the backplane. The module then sits on top of the base, so the base is chosen for the field wiring and the module for the signal, and the two are ordered separately.
FLEX I/O bases and modules are separate line items on a purchase order, and the price of getting that wrong is a second shipment: a module without its base cannot be installed, and a base of the wrong termination type cannot be reworked in the field because the module keys to the base family.
For a retrofit into an existing slice, the addressing is decided by position rather than by catalog number: FLEX I/O assigns the module its place in the rack by the order of the bases on the rail, so inserting a module in the middle shifts the addresses of everything to its right and requires the program to be re-checked.
Mounting is a DIN rail operation on both parts and the order of assembly is base first, module second: the base slides onto the rail, its backplane fingers engage the neighbouring base, and the module is then pressed onto the base and secured. Removing a module does not break the backplane, which is why a failed slice can be swapped without rewiring the row.
The 22 to 12 AWG acceptance range on the standard bases is wider than the field device terminals in most panels, so the practical constraint is usually the device end, not the base end. Where a 24V DC sensor cable is 18 AWG and the base accepts 12 AWG, the conductor still has to be torqued to the published value rather than to feel.
Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.
The Allen-Bradley Flex I/O 1794 modules category groups the other catalog numbers, options and spare parts in the same range.