Product Details:
Payment & Shipping Terms:
|
The 1794-OV16 is the sinking sixteen-point output module: it pulls the load to common rather than sourcing to it, and it runs from a 4.5...5.5V DC external supply.
It is the counterpart of the 1794-OB16 for panels wired with a common-positive convention, and the module to reach for when the field device expects a sinking driver.
| 1794-OB8 | 8-point 24V DC sourcing output module | IN STOCK |
| 1794-OB8EP | 8-point 2 A electronically fused sourcing output module | IN STOCK |
| 1794-OB16 | 16-point 24V DC sourcing output module | IN STOCK |
| 1794-OB16P | 16-point protected sourcing output module | IN STOCK |
| 1794-OB16D | 16-point diagnostic 24V DC output module | IN STOCK |
| 1794-OB32P | 32-point protected sourcing output module | IN STOCK |
| 1794-OB16PXT | 16-point protected sourcing output, extended temperature | IN STOCK |
| 1794-OB8EPXT | 8-point 2 A electronically fused output, extended temperature | IN STOCK |
| 1794-OV16 | 16-point sinking output module | IN STOCK |
| 1794-OV16P | 16-point protected sinking output module | IN STOCK |
| 1794-OV32 | 32-point sinking output module | IN STOCK |
| 1794-OC16 | 16-point 48V DC sourcing output module | IN STOCK |
| 1794-OG16 | 16-point 5V DC sourcing output module | IN STOCK |
| 1794-OW8 | 8-point isolated relay output module | IN STOCK |
Application |
FLEX I/O sinking digital output |
Cat Num |
1794-OV16 |
Brand Name |
Rockwell |
Outputs |
16, current, sinking |
External supply |
4.5...5.5V DC, 50 mV p-p ripple |
On-state voltage drop |
0.2V DC max |
Output current |
500 mA per channel, 8 A per module |
Off-state leakage |
1.0 mA max |
Output delay |
0.25 ms off to on, 0.5 ms on to off |
External supply current |
20...65 mA |
Isolation |
50V continuous; tested 1770V DC for 60 s |
Power dissipation |
4.2 W max at 31.2V DC (14.3 BTU/hr) |
Terminal base |
1794-TB3, -TB3S, -TB3K, -TB3SK |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Sixteen sinking outputs with 500 mA per channel and 8 A per module, 0.2V DC maximum drop and 1.0 mA maximum off-state leakage.
The external supply is 4.5...5.5V DC with a 50 mV p-p ripple limit — this is a logic-level module, not a 24V DC output card.
0.25 ms off to on and 0.5 ms on to off are the fastest delays in the digital output range.
The 4.5...5.5V DC rail is a logic supply, so this is an interface-level driver rather than a field 24V output card.
0.2V drop at 500 mA leaves 4.3V or more at the load, which matters for an interface card with a 4.5V threshold.
A sinking stage ties returns together, so one return fault affects the group; that is inherent to the convention, not a defect.
The 0.25 ms delay is the shortest in the digital range and suits a fast interface rather than a valve.
The 800 mA per-channel fuse is specified because the module protects nothing internally.
Because the supply rail is 5V, the module's own dissipation stays near 4 W whatever the load, and the enclosure sees little extra heat from it.
Off-state leakage of 1.0 mA is the highest in the sinking pair; an interface card that reads 0.5 mA as on will treat this module's leakage as a signal.
20...65 mA from the external supply covers the module's own logic; the load current flows through the sinking output stage.
4.2 W maximum dissipation (14.3 BTU/hr) at 31.2V DC, on the 94 x 94 x 69 mm installed footprint.
-20...55 °C operating, the same envelope as the 24V DC input modules.
1770V DC for 60 s type tested at 50V continuous basic insulation, field side to system, with no isolation between channels.
<One common for sixteen outputs — a sinking module ties the load returns together, which is what the common-positive wiring convention expects.
No internal fusing. Rockwell specifies a SAN-O M04-800 mA fuse per output.
1794-TB3, -TB3S, -TB3K or -TB3SK — the TB2 base is not listed for this module.
<Keyswitch position 2 on the base, as with the other 16-point digital modules.
<Wiring category 2 applies to the signal ports, which sets the conductor routing rules in the panel.
Common-positive panels. A machine wired with +V on the field devices expects a sinking driver; mixing conventions is how outputs get damaged.
Logic-level loads. The 4.5...5.5V DC supply range suits interface cards and small indicators rather than 24V solenoids.
For 24V DC loads the sourcing 1794-OB16 or 1794-OB16P is the correct module, not this one.
Is the 1794-OV16 sourcing or sinking?
Sinking: it pulls the load to common.
What supply does it need?
4.5...5.5V DC with a 50 mV p-p ripple limit, 20...65 mA.
What is the output rating?
500 mA per channel and 8 A per module, with a 0.2V DC maximum drop.
Which terminal bases are supported?
1794-TB3, 1794-TB3S, 1794-TB3K and 1794-TB3SK.
Are the outputs fused?
No; Rockwell specifies an external SAN-O M04-800 mA fuse per output.
What are the output delays?
0.25 ms off to on and 0.5 ms on to off, both maxima.
| Catalog number | Outputs | Per-channel current | Module ceiling | Terminal base |
|---|---|---|---|---|
| 1794-OB8 | 8, current, sourcing | 500 mA per channel | 4 A per module | 1794-TB2, -TB3, -TB3S, -TB3K, -TB3SK |
| 1794-OV16 | 16, current, sinking | 500 mA per channel | 8 A per module | 1794-TB3, -TB3S, -TB3K, -TB3SK |
| 1794-OV16P | 16, current, sinking, protected | 500 mA per channel | 8 A per module | 1794-TB3, -TB3S, -TB3K, -TB3SK |
| 1794-OB16 | 16, current, sourcing | 500 mA per channel | 8 A per module | 1794-TB2, -TB3, -TB3S, -TB3K, -TB3SK |
| 1794-OB16D | 16, sourcing, with diagnostics | 500 mA per channel | 8 A per module | 1794-TB3, -TB3S, -TB3K, -TB3SK |
| 1794-OV32 | 32, current, sinking | 500 mA per channel | 8 A per module | 1794-TB32, 1794-TB32S |
| 1794-OB32P | 32, sourcing, protected, two groups of 16 | 500 mA per channel | Not published | 1794-TB32, 1794-TB32S |
A FLEX I/O island usually settles between this module and a neighbour in the same table: the point count decides the base width, and the per-channel current decides whether the load can stay on one supply.
For 1794-OV16 the published row reads 16, current, sinking, at 500 mA per channel with a module ceiling of 8 A per module; the supply window is Not published, and it mounts on 1794-TB3, -TB3S, -TB3K, -TB3SK.
The module ceiling is what stops a sixteen-point module from behaving like sixteen independent channels at the per-channel rating: the sum is capped, so a panel that loads every channel near the top has to count the total before it counts the points.
Off-state leakage is the number that decides whether a two-wire sensor sharing the field supply reads an output as off: 1.0 mA max on this module.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley Flex I/O 1794 modules category.