Product Details:
Payment & Shipping Terms:
|
1746-NO4I is the 4 Point Analog Current Output Module in the Allen-Bradley SLC 500 range: 1746 SLC System, 4 point Analog Current Output Module.
It occupies one I/O slot, takes both backplane rails, and is configured channel by channel from the processor; the ranges, resolution and filter settings below are the ones a project engineer needs before the loop is designed.
| 1746-NO4I | 4 Point Analog Current Output Module | IN STOCK |
| 1746-NO8I | 8 Point Analog Current Output Module | IN STOCK |
Application |
1746 SLC System, 4 point Analog Current Output Module |
Cat Num |
1746-NO4I |
Brand Name |
Rockwell |
Product Type |
4 Point Analog Current Output Module |
Channels |
4 current outputs |
Input range |
- |
Output range |
0...20 mA or 4...20 mA, 0...21 mA -1 LSB overrange |
Resolution |
14-bit, 2.56348 µA/LSB |
Backplane current, 5V DC |
55 mA |
Backplane current, 24V DC |
195 mA |
Update time / filtering |
Step response 2.5 ms at 95% |
Isolation |
500V dc continuous field wiring to backplane |
Lifecycle |
Discontinued |
Discontinued date |
April 29, 2021 |
Replacement category |
Engineering Replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN008 (module specifications) and 1747-UM011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Official Rockwell description: 1746 SLC System, 4 point Analog Current Output Module.
4 Point Analog Current Output Module with 4 current outputs.
Application: 1746 SLC System, 4 point Analog Current Output Module.
Cat Num: 1746-NO4I.
Brand Name: Rockwell.
Product Type: 4 Point Analog Current Output Module.
Channels: 4 current outputs.
Input range: -.
Output range: 0...20 mA or 4...20 mA, 0...21 mA -1 LSB overrange.
Resolution: 14-bit, 2.56348 µA/LSB.
Backplane current, 5V DC: 55 mA.
Backplane current, 24V DC: 195 mA.
Update time / filtering: Step response 2.5 ms at 95%.
Isolation: 500V dc continuous field wiring to backplane.
Lifecycle: Discontinued.
Discontinued date: April 29, 2021.
Replacement category: Engineering Replacement.
A current output drives 0...20 mA into a load from 0 to 500 Ω at 14-bit on the 4-channel card, which covers a typical positioner or an I/P transducer without an external amplifier.
The NO4I and NO4V have a jumper that lets the 24V dc side come from an external supply instead of the backplane; on a chassis that is already close to its power budget that jumper is the difference between adding a card and adding a power supply.
The output returns to zero on a module fault, so a valve that must fail in place needs a positioner with its own air failure setting rather than reliance on the card.
Rockwell lists 1746-NO4I as Discontinued, discontinued date April 29, 2021, replacement category Engineering Replacement.
No replacement catalog number is printed on the Rockwell page, so the route is an engineering substitution with a re-ranged analogue front end, not a part-for-part swap.
Rockwell's migration guidance for Bulletin 1746 routes analog points to Compact 5000 analog modules with a Logix controller; machines that stay on SLC 500 are supported from the secondary market.
The terminal block, the slot address and the module ID code stay the same when a card is replaced by the same catalog number, which is why the original number still has a place in a maintenance spares list after the end of sale.
A modular SLC 500 reserves slot 0 for the processor or the adapter, so this module goes in any other I/O slot; the current drawn from 5V dc and 24V dc both count against the chassis supply.
The analog front end is factory calibrated and, on the newer cards, autocalibrates at power-up and on channel enable, so an accuracy figure quoted at 25 °C is what the card delivers without a field trim.
Isolation is 500V dc continuous field wiring to backplane between the field terminals and the backplane; that figure, not the channel count, is what decides whether a card can sit next to a drive with a noisy earth.
The card in red in the catalogue table at the top of this page is the one described here.
What is 1746-NO4I?
1746 SLC System, 4 point Analog Current Output Module. 4 Point Analog Current Output Module.
How many channels does 1746-NO4I have?
4 current outputs.
What ranges does 1746-NO4I accept?
Inputs: -. Outputs: 0...20 mA or 4...20 mA, 0...21 mA -1 LSB overrange.
How much backplane current does 1746-NO4I draw?
55 mA at 5V dc and 195 mA at 24V dc.
Is 1746-NO4I still available?
Rockwell lists it as Discontinued, discontinued date April 29, 2021, replacement category Engineering Replacement.