Product Details:
Payment & Shipping Terms:
|
1746-A10 is the 10-slot chassis of the Allen-Bradley SLC 500 modular system: 1746 SLC System, 10 Slot Chassis-Modular Hardware Style.
The chassis is the part that fixes the machine's I/O count. Every card, the processor and the power supply are sized against the slots and the backplane rails this rack provides.
| 1746-A2 | 2-Slot Expansion Chassis | IN STOCK |
| 1746-A4 | SLC 4 Slots Chassis | IN STOCK |
| 1746-A7 | SLC 7 Slots Chassis | IN STOCK |
| 1746-A10 | SLC 10 Slots Chassis | IN STOCK |
| 1746-A13 | SLC 13 Slots Chassis | IN STOCK |
Application |
1746 SLC System, 10 Slot Chassis-Modular Hardware Style |
Cat Num |
1746-A10 |
Brand Name |
Rockwell |
Product Type |
SLC 500 10-slot chassis |
Number of slots |
10 |
Chassis |
10-slot chassis, modular hardware style |
Cooling |
Convection |
Temperature rating |
0...60 °C (32...140 °F) |
Minimum enclosure size, H x W x D |
17.1 x 39.7 x 14.5 cm |
Lifecycle |
Discontinued |
Discontinued date |
March 31, 2024 |
Replacement category |
No planned RA replacement |
1746-A10 (SLC 500 modular chassis, 10 slots): 10-slot backplane for an SLC 500 modular system. The power supply mounts at the left end and slot 0 is reserved for the processor or an adapter module, so the slots left for I/O depend on how many chassis the system uses.
The chassis mounts straight to the enclosure back panel on its tabs with #10 or #12 screws, torqued to a maximum of 3.4 N·m (30 lb·in). A single SLC 500 system is limited to three chassis and 30 slots of I/O, which is why the 10- and 13-slot frames are normally paired with an interconnect cable rather than expanded again. Source: Rockwell publication 1747-UM011, mounting chapter and the SLC 500 system specifications.
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN016 (module specifications) and 1746-IN016 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Rockwell description: 1746 SLC System, 10 Slot Chassis-Modular Hardware Style.
It is a 10-slot chassis in the modular hardware style, with a card guide per slot, one backplane connector per slot and a mounting foot at each end.
Application: 1746 SLC System, 10 Slot Chassis-Modular Hardware Style.
Cat Num: 1746-A10.
Brand Name: Rockwell.
Product Type: SLC 500 10-slot chassis.
Number of slots: 10.
Chassis: 10-slot chassis, modular hardware style.
Cooling: Convection.
Temperature rating: 0...60 °C (32...140 °F).
Minimum enclosure size, H x W x D: 17.1 x 39.7 x 14.5 cm.
Lifecycle: Discontinued.
Discontinued date: March 31, 2024.
Replacement category: No planned RA replacement.
Slot 0 is reserved for the processor or for a communication adapter; the remaining 9 slots take I/O and specialty modules. The power supply mounts at the left end of the rack and is not a slot.
Rockwell documents the modular SLC 500 system as connecting up to three chassis with 30 I/O modules to a single controller or communication adapter, so a 10-slot rack is one segment of that budget, not the whole limit.
Cards are addressed by slot, so the slot number printed beside each card is what the ladder program uses; moving a card to another slot changes its addresses.
The rack runs at 0...60 °C ambient and cools by convection, so the enclosure has to let air move past the cards. The minimum enclosure figures Rockwell prints are the space the rack and its terminal blocks need, not a clearance allowance for wiring.
Rockwell lists a minimum enclosure of 17.1 x 39.7 x 14.5 cm (H x W x D) for this chassis.
Field wiring lands on the removable terminal blocks at the front of each card, so the panel needs working room in front of the rack as well as above and below it.
Rockwell lists 1746-A10 as discontinued, date March 31, 2024, replacement category No planned RA replacement.
No replacement catalog number is planned, so a failed chassis is replaced from the secondary market or the machine is migrated to a CompactLogix platform.
Rockwell's migration guidance for Bulletin 1746 routes I/O to Compact 5000 modules on a Logix controller; a chassis is the part that cannot be carried across, because the new I/O does not use this backplane.
What is 1746-A10?
1746 SLC System, 10 Slot Chassis-Modular Hardware Style. 10-slot chassis, modular hardware style.
How many slots does 1746-A10 have?
10 slots, of which slot 0 is reserved for the processor or an adapter.
What is the ambient temperature rating of 1746-A10?
0...60 °C (32...140 °F), convection cooled.
Is 1746-A10 still available?
Rockwell lists it as discontinued, date March 31, 2024, replacement category No planned RA replacement.
How many chassis can one SLC 500 controller drive?
Up to three chassis with 30 I/O modules in total, per Rockwell's SLC I/O system description.
1746-A10 is a 10-slot chassis in the SLC 500 modular range. The chassis is the backplane: it carries the processor or I/O adapter in the left-most slot, the I/O modules to its right, and it is fed by a separate power supply mounted on its left end.
Module density tops out at 32 channels per module in the 1746 range, and the chassis sizes are 4, 7, 10 and 13 slots. Open slots are closed with 1746-N2 card slot fillers, which matters because an unfilled slot changes the airflow and the mechanical retention of the modules around it rather than only the appearance of the rack.
SLC 500 processors span 1 K to 64 K of memory and can address up to 4096 inputs and 4096 outputs, and every modular processor except the SLC 5/01 can control remotely located I/O through a scanner. That distinction is what makes a 5/01 unsuitable as the head of a distributed system regardless of its I/O count.
Sizing a SLC 500 system is a fixed sequence, and it is the sequence rather than the arithmetic that stops most retrofits: count the I/O points, convert them into modules at the published channels per module, add a scanner or an adapter where the I/O sits remotely, total the 5V and 24V draws per chassis, choose the power supply that covers both totals, then choose the chassis with enough slots including fillers for the empties. Doing it in the reverse order, from a chassis that already exists, produces a system that fits mechanically and fails electrically.
Backplane budgeting is the arithmetic that decides whether a SLC 500 chassis closes: every module declares its 5V and 24V draw, the power supply declares its internal capacity for both rails, and the sum has to stay below both numbers at once. A chassis that passes on 5V and fails on 24V is the common mistake, because most digital I/O draws nothing from 24V while analog and thermocouple modules do.
Before ordering, confirm the slot count against the I/O list, confirm the 5V and 24V totals against the supply capacity rather than against the wattage, and confirm that the cable and the chassis are ordered separately, because none of these parts is included with any other.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley SLC 500 1746 I/O modules category.