Product Details:
Payment & Shipping Terms:
|
The 1794-NM1 is the panel mounting kit: 18 screws, two for the adapter and two for each module in the system.
It exists because the bases have screw holes for direct panel mounting, and without a rail the chassis ground has to come through those screws instead.
| 1794-PS3 | 120/220V AC power supply, 24V DC 3.0 A | IN STOCK |
| 1794-PS13 | 120/220V AC power supply, 24V DC 1.3 A | IN STOCK |
| 1794-CE1 | 0.3 m (1 ft) extender cable for FLEX I/O | IN STOCK |
| 1794-CE3 | 0.9 m (3 ft) extender cable for FLEX I/O | IN STOCK |
| 1794-NM1 | panel mounting kit with 18 screws | IN STOCK |
| 1794-N2 | empty slot filler module, no electronics | IN STOCK |
| 1794-CJC2 | cold junction compensation kit, two parts | IN STOCK |
| 1794-LBL | label kit with die-cut sheet and five labels | IN STOCK |
Application |
FLEX I/O panel mounting without DIN rail |
Cat Num |
1794-NM1 |
Brand Name |
Rockwell |
Contents |
18 mounting screws |
Coverage |
2 screws for the adapter, 2 for each module |
Use |
Panel mount into an enclosure, horizontal or vertical |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
18 screws, which covers an adapter plus eight modules at two screws each.
Two screws per component through the base mounting holes, horizontal or vertical.
The kit is the accessory catalog for the panel-mount option in the selection guide.
Star-washer screws are the grounding practice when the rail is absent.
No rail means no rail grounding, so the chassis path runs through the mounting screws.
The guide recommends star washers with the mounting screws in that case.
Panel mounting is permitted horizontally or vertically, with 25 mm of air space maintained.
Aluminium or plastic mounting surfaces do not provide a ground path.
Enclosures with no DIN rail, or where the rail is already occupied.
Retrofit panels where drilling two holes per component is easier than adding rail.
Not a substitute for rail in a high-vibration machine; rail plus 1492-EA35 locks holds better.
Not a grounding kit; it supplies screws, not a bonding strap.
One kit per system, sized for an adapter and eight modules.
Larger systems need more screws, so count components before ordering.
1492-EA35 rail locks are the separate accessory for rail-mounted systems.
Publication 1794-IN092 covers the base mounting holes.
Panel-mounted islands in a plain enclosure.
Mixed panels where some islands are on rail and some are not.
Not for wet locations; the enclosure rating still governs.
Not for frequent module changes; rail is faster to service.
How many screws are in the 1794-NM1 kit?
18: two for the adapter and two for each module.
What is it for?
Panel mounting the FLEX I/O system without DIN rail.
What grounding practice applies?
Star-washer screws through the mounting holes, since no rail is present.
Can the system be mounted vertically?
Yes, horizontally or vertically, with 25 mm air space.
Is one kit enough for a large system?
No; the kit covers an adapter plus eight modules.
Does it include a bonding strap?
No, only the mounting screws.
1794-NM1 is a 1794 FLEX I/O panel mounting kit, described here from the Rockwell FLEX I/O selection guide and the related publication so that the identity, the published rating and the compatibility statement are on the page for this catalog number.
| Specification | Value |
|---|---|
| Catalog number | 1794-NM1, FLEX I/O panel mounting kit |
| Function | Mounts a FLEX I/O system on a panel or wall without DIN rail |
| Contents | 18 screws: 2 for the adapter and 2 for each module, which covers an eight module group |
| Screw type | 6-32 |
| Compatible systems | 1794 FLEX I/O adapter, terminal bases and modules |
| Source | 1794-SG002D-EN-P selection guide, select optional accessories section |
Eighteen screws and a 6-32 thread is the whole content of a part that decides whether a panel needs a rail. Two screws per module and two for the adapter means the kit is sized for an eight module group, which is also the maximum group size for the family.
Panel mounting without rail is common where the enclosure is drilled and painted before the electrical design is frozen. The kit lets the layout follow the mechanical drawing, and the trade is that service access requires unscrewing a module rather than sliding it along a rail.
This page states only what the Rockwell FLEX I/O documentation publishes for 1794-NM1: the catalog identity, the published rating or dimension, the compatibility statement and the source publication. Where the manufacturer does not publish a figure, the page says so instead of estimating one.
Temperature ratings on a passive accessory are inherited from the materials. A cable rated to sixty degrees limits the panel interior temperature just as firmly as a module rated to fifty five, and a hot enclosure will fail the cable before it fails the electronics.
Every accessory on this page is sourced from the same FLEX selection guide that specifies the adapters and the terminal bases, which means the compatibility statement is the manufacturer statement rather than a distributor inference.
Panel mounting without DIN rail is a common requirement in machine tools exported to regions where the rail is not standard, and the mounting kit with its screws is cheaper than a rail plus the labour to fit it.
A filler is not a spare slot. Some integrators install a filler to reserve capacity for a later expansion, and that works only if the adapter was sized for the eventual module count at commissioning time, not at expansion time.
The extender cable rule is one per system, not one per row. A second extender in series breaks the flexbus timing assumptions the adapter was designed around, so the two row layout is a one cable layout, and a three row layout is not supported at all.
Labels matter more than they look. A terminal base that is not marked with its slot and its module type turns every future maintenance visit into a wire tracing exercise, which is exactly what the label kit exists to prevent.
Accessory part numbers are frequently the difference between a system that ships and a system that waits. A missing extender cable is a one week delay on a panel that is otherwise complete, and the order of magnitude of that delay belongs in the planning conversation.
A dummy filler module exists because an empty terminal base is an open slot in the flexbus chain. The filler carries no electronics, and its whole job is mechanical and documentation: the rail is complete, the slot is accounted for, and the drawing shows an intentional gap rather than a missing part.
Country of origin and part number structure belong on the page because procurement asks. A conformally coated variant and a standard variant share the same mechanical drawing and differ in the suffix, which is the kind of detail that only shows up at goods receipt.
Accessories are where a FLEX system stops being a catalog page and becomes a panel. The rail, the extender cable, the mounting screws and the filler module all change the drawing, and none of them appear in the module data sheet that the integrator reads first.
Screws in a mounting kit are a count, not a suggestion. Two for the adapter and two for each module means the kit covers a full eight module group, and a ninth module requires either a second kit or a sourced screw, which is a purchasing detail worth stating.
The flexbus connector is the fragile part of the assembly. It is pushed to the left to connect and retracted to disconnect, and a base installed with the connector partly extended will produce intermittent I/O that survives a power cycle and reappears under vibration.
A right angle split between horizontal and vertical orientation is the real reason the extender exists. Mounting the adapter horizontally in a shallow enclosure and the modules vertically in a deeper section is a mechanical decision that the cable makes possible without a second adapter.
Count the screws per group before the panel drawing is released, and add a second kit when the group exceeds eight modules.
The Allen-Bradley Flex I/O 1794 modules category groups the other catalog numbers, options and spare parts in the same range.