logo
Home ProductsAB FlexLogix I/O 1794

Allen Bradley PLC 1794-IB16D / 1794IB16D

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1794-IB16D / 1794IB16D

China Allen Bradley PLC 1794-IB16D / 1794IB16D supplier
Allen Bradley PLC 1794-IB16D / 1794IB16D supplier Allen Bradley PLC 1794-IB16D / 1794IB16D supplier Allen Bradley PLC 1794-IB16D / 1794IB16D supplier Allen Bradley PLC 1794-IB16D / 1794IB16D supplier Allen Bradley PLC 1794-IB16D / 1794IB16D supplier Allen Bradley PLC 1794-IB16D / 1794IB16D supplier

Large Image :  Allen Bradley PLC 1794-IB16D / 1794IB16D

Product Details:

Place of Origin: Made in SINGAPORE
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1794-IB16D / 1794IB16D

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $156.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 10 PCS
Detailed Product Description

1794-IB16D technical data PDF download FLEX I/O 1794-IB16D / 1794IB16D 16-Point Diagnostic Input

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC I/O

The 1794-IB16D is the diagnostic version of the 16-point sinking input: each sensor port is monitored for short circuit, open wire and reverse polarity, and a red channel LED marks the faulted point.

Because the diagnostics need a defined current path, every unused sensor port must be fitted with a dummy resistor, a requirement the installation instructions state explicitly.

1794-IB8 8-point 24V DC sinking input module IN STOCK
1794-IB16 16-point 24V DC sinking input module IN STOCK
1794-IB32 32-point 24V DC sinking input module IN STOCK
1794-IB10XOB6 10 inputs / 6 sourcing outputs, 24V DC combo module IN STOCK
1794-IB16XOB16P 16 inputs / 16 protected sourcing outputs combo module IN STOCK
1794-IB16D 16-point diagnostic sinking input module IN STOCK
1794-IB16XT 16-point 24V DC sinking input, extended temperature IN STOCK
1794-IB10XOB6XT 10 inputs / 6 sourcing outputs, extended temperature IN STOCK
1794-IA8 8-point 120V AC input module IN STOCK
1794-IA16 16-point 120V AC input module IN STOCK
1794-IC16 16-point 48V DC sinking input module IN STOCK
1794-IG16 16-point 5V DC TTL input module IN STOCK
1794-IH16 16-point 125V DC sinking input module IN STOCK
1794-IM8 8-point 240V AC input module IN STOCK
1794-IM16 16-point 240V AC input module IN STOCK
1794-IV16 16-point 24V DC sourcing input module IN STOCK
1794-IV32 32-point 24V DC sourcing input module IN STOCK

Product Specifications 1794-IB16D (PDF)
 Application
 FLEX I/O diagnostic digital input
 Cat Num
 1794-IB16D
 Brand Name
 Rockwell
 Number of inputs
 16, sinking, with per-channel diagnostics
 On-state voltage, max
 31.2V DC
 On-state current
 2.0 mA min, 12.1 mA max
 Off-state voltage, max
 5.0V DC
 Off-state current, max
 1.5 mA
 Input impedance
 3.1 k ohm nominal
 Isolation
 type tested 2121V DC for 2 s
 Flexbus current
 30 mA at 5V DC
 Filter time
 0.25...32 ms, selectable

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1794-IB16D original product photograph, wide view 1794-IB16D original product photograph, wide view 1794-IB16D original product photograph, wide view

What the diagnostics report

Read word 2 carries four status bits: module error, external power reverse polarity, sensor power short, sensor power open wire.

The module monitors each sensor-power port for current and voltage, setting the error bit when the port loses voltage (short) or loses current (open wire).

A red channel LED marks the faulted sensor, while a healthy On channel shows red and yellow together.

Reverse polarity is its own error bit, so a miswired external supply is distinguishable from a field fault.

Wiring and dummy resistors

Unused sensor ports need a dummy resistor to mask the diagnostic function, per the publication note.

Sensor power comes from the external supply on the base, not from the backplane.

A 3.1 k ohm nominal input impedance and 12.1 mA maximum on-state current set what the sensor has to drive.

Isolation is 50V continuous, type tested at 2121V DC for 2 s, with none between channels.

Filtering and image table

Filter time is written to word 3, bits 8...10, with eight settings from 0.25 to 32 ms.

Filter 0 is the 0.25 ms default; filter 7 gives 32 ms for slow or noisy contacts.

An FLL instruction can preload the filter word at startup, the example the publication gives.

30 mA Flexbus current is the module's own overhead on the backplane.

Application

Panels where a sensor failure must be identified, not just detected as a missing bit.

Lines that run unattended, where an open wire needs a maintenance call rather than a restart.

Not a substitute for the plain 1794-IB16 when diagnostics are not needed.

Not for 125V DC or 48V DC inputs.

Where it fits

Diagnostic input islands on 1794-TB3 or 1794-TB3S bases.

Retrofit of a plain input card where fault visibility was the complaint.

Not the 32-point density; there is no 32-point diagnostic input in this family.

Not extended temperature; the -XT parts do not carry these diagnostics.

FAQ — 1794-IB16D

What does the 1794-IB16D diagnose?

Per-port short circuit, open wire and reverse polarity, with a red LED on each faulted channel.

How many inputs has it?

16 sinking inputs with individual diagnostics.

What is the input impedance?

3.1 k ohm nominal.

What current does an input draw?

2.0 mA minimum and 12.1 mA maximum on-state.

Do unused channels need anything?

Yes, a dummy resistor on each unused sensor port to mask the diagnostic.

What filter times are available?

0.25 to 32 ms in eight settings, 0.25 ms default.


Data sources. Technical values on this page come from Rockwell publication 1794-IN096 (FLEX I/O Diagnostic Digital Modules). Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Related numbers

Where the 1794-IB16D sits in the FLEX I/O range

1794-IB16D is a diagnostic digital DC input with 16 inputs in the FLEX I/O range, rated for 24V DC, group isolated. It mounts on the 1794-TB32, 1794-TB32S terminal base unit, which is ordered separately and is the part that actually carries the field terminals.

AttributeValue
Catalog number1794-IB16D
Module typediagnostic digital DC input
Points16 inputs
Electrical range24V DC, group isolated
Terminal base unit1794-TB32, 1794-TB32S
DiagnosticsDetects and reports open field devices or wiring, shorted field devices, shorted wiring, and reverse polarity of the user supply
FilterSelectable input filter times from below 1 ms to 60 ms

The wiring category matters as much as the gauge: category 2 bases are the general field wiring class, while grounded bases in the 1794-TB3G family carry 10 chassis ground terminals for analog and temperature modules where a separate signal common is needed.

Temperature class is written per module and per base, and the lower of the two governs the slice. A 70 C base carrying a 55 C module is a 55 C slice, which is why the extended temperature modules exist as a matched set rather than as an upgrade to one part of the pair.

One point about the 24V DC digital slices that catches panel builders: the adapter supplies the field power for the modules on its own 24V output, and that output is current limited. On a 1794-ADN the supply output is 450 mA at 24V, so a slice of 16 point DC modules can exhaust the adapter before the cabinet is half filled, and a separate field supply has to be introduced rather than assumed.

The 22 to 12 AWG acceptance range on the standard bases is wider than the field device terminals in most panels, so the practical constraint is usually the device end, not the base end. Where a 24V DC sensor cable is 18 AWG and the base accepts 12 AWG, the conductor still has to be torqued to the published value rather than to feel.

Conformal coating on a K suffix base is applied to the assembled board and not to the terminals, so the coating protects the electronics against condensation while the field terminals remain serviceable. That is the point of ordering the coated base instead of sealing the whole enclosure.

Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.

The Allen-Bradley Flex I/O 1794 modules category lists the related catalog numbers, options and accessories for this range.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)