Product Details:
Payment & Shipping Terms:
|
The 1794-IB10XOB6XT combines 10 sinking inputs with 6 sourcing outputs in one extended-temperature module, for a small island where a full 16-point card would waste half its points.
The outputs are the high-current half: 2.0 A per channel and 10.0 A per module, so the card can drive valves and small contactors directly.
| 1794-IB8 | 8-point 24V DC sinking input module | IN STOCK |
| 1794-IB16 | 16-point 24V DC sinking input module | IN STOCK |
| 1794-IB32 | 32-point 24V DC sinking input module | IN STOCK |
| 1794-IB10XOB6 | 10 inputs / 6 sourcing outputs, 24V DC combo module | IN STOCK |
| 1794-IB16XOB16P | 16 inputs / 16 protected sourcing outputs combo module | IN STOCK |
| 1794-IB16D | 16-point diagnostic sinking input module | IN STOCK |
| 1794-IB16XT | 16-point 24V DC sinking input, extended temperature | IN STOCK |
| 1794-IB10XOB6XT | 10 inputs / 6 sourcing outputs, extended temperature | IN STOCK |
| 1794-IA8 | 8-point 120V AC input module | IN STOCK |
| 1794-IA16 | 16-point 120V AC input module | IN STOCK |
| 1794-IC16 | 16-point 48V DC sinking input module | IN STOCK |
| 1794-IG16 | 16-point 5V DC TTL input module | IN STOCK |
| 1794-IH16 | 16-point 125V DC sinking input module | IN STOCK |
| 1794-IM8 | 8-point 240V AC input module | IN STOCK |
| 1794-IM16 | 16-point 240V AC input module | IN STOCK |
| 1794-IV16 | 16-point 24V DC sourcing input module | IN STOCK |
| 1794-IV32 | 32-point 24V DC sourcing input module | IN STOCK |
Application |
FLEX I/O-XT combination digital module |
Cat Num |
1794-IB10XOB6XT |
Brand Name |
Rockwell |
Number of inputs |
10, nonisolated, sinking |
Number of outputs |
6, nonisolated, sourcing |
On-state voltage |
10...31.2V DC, 24V DC nominal |
Input current |
2.0 mA min, 8.0 mA @ 24V, 11 mA max |
Output current |
2.0 A max per output, 10.0 A max per module |
Output surge |
4.0 A for 50 ms, repeatable every 2 s |
Isolation |
type tested 1365V AC for 60 s |
Terminal base |
1794-TB2, 1794-TB3, 1794-TB3S |
Operating temperature |
-20...70 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
10 sinking inputs at 8.0 mA nominal, 11 mA maximum, on 10...31.2V DC.
Off-state below 5.0V DC with 1.5 mA minimum off current, 4.8 k ohm input impedance.
Inputs land on A-0...A-9, supply on C-35...C-44, commons on B-17...B-26, per the wiring table.
Input filter time is set in write word 3, a separate FT field for the group.
6 sourcing outputs, 2.0 A per channel, 10.0 A per module, which is the densest current rating in this family after the 1794-OB8EPXT.
4.0 A surge for 50 ms repeatable every 2 s, 1.0V drop at 2 A, 0.5V at 1 A.
<Off-state leakage 0.5 mA, relevant for holding relays and pilot lamps.
Wiring on A-10...A-15 with the output commons on B-27...B-32.
-20...70 deg C, coated to ISA Class G3, per 1794-IN124.
1365V AC for 60 s type test, field side to system, no channel-to-channel isolation.
50 mA Flexbus, 6.0 W dissipation, 20.3 BTU/hr, the combined load of both halves.
10 yellow status indicators, logic driven, plus the output states.
Compact islands with a few sensors and a few actuators.
Valve and solenoid drive where 2 A per point is needed.
Not a substitute for 16-point density when the count is symmetric.
Not for AC devices.
-XT islands with mixed small I/O counts.
Remote panels where module slots are scarce.
Not for 32 points; the 1794-IB16XOB16P covers 16 and 16.
Not for high inductive loads without suppression.
How many inputs and outputs has the 1794-IB10XOB6XT?
10 sinking inputs and 6 sourcing outputs.
What is the output current rating?
2.0 A per output and 10.0 A per module.
What is the on-state voltage range?
10...31.2V DC, 24V DC nominal.
Which bases are used?
1794-TB2, 1794-TB3 and 1794-TB3S.
What is the operating temperature?
-20...70 deg C with conformal coating.
Is there channel-to-channel isolation?
No; isolation is field side to system only.
1794-IB10XOB6XT is a combination digital DC module with 10 inputs and 6 outputs in the FLEX I/O range, rated for 24V DC. It mounts on the 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK terminal base unit, which is ordered separately and is the part that actually carries the field terminals.
| Attribute | Value |
| Catalog number | 1794-IB10XOB6XT |
| Module type | combination digital DC module |
| Points | 10 inputs and 6 outputs |
| Electrical range | 24V DC |
| Terminal base unit | 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK |
| Isolation | 50V continuous basic insulation, type tested at 1250V AC for 60 s field to system, routine tested at 2121V DC for 1 s, no isolation between individual channels |
| Power dissipation | 6.0 W at 31.2V DC, 20.3 BTU per hour |
| Fusing | Individual outputs require external fusing, unlike the 1794-IB16XOB16P whose outputs are self-protected |
| Temperature rating | Extended temperature version of the 1794-IB10XOB6 |
The XT suffix is the extended temperature build rather than a different circuit: the same terminal base list, the same field voltage, and an operating range that reaches 70 C instead of the 55 C of the standard version. Specifying XT and then derating the panel back to 55 C gives away the only thing that was paid for.
Point density drives the base choice before the module choice: 8 and 16 point modules fit the 16 I/O terminal bases, the 32 point modules need the 1794-TB32 or 1794-TB32S, and the 1794-IB16D diagnostic input is listed on the 32 point base because its diagnostics use the extra common and voltage terminals.
FLEX I/O bases and modules are separate line items on a purchase order, and the price of getting that wrong is a second shipment: a module without its base cannot be installed, and a base of the wrong termination type cannot be reworked in the field because the module keys to the base family.
For a retrofit into an existing slice, the addressing is decided by position rather than by catalog number: FLEX I/O assigns the module its place in the rack by the order of the bases on the rail, so inserting a module in the middle shifts the addresses of everything to its right and requires the program to be re-checked.
Conformal coating on a K suffix base is applied to the assembled board and not to the terminals, so the coating protects the electronics against condensation while the field terminals remain serviceable. That is the point of ordering the coated base instead of sealing the whole enclosure.
On the 32 point bases the common and voltage terminals are grouped in eight pairs rather than eighteen, which is why the 32 point digital modules can mix sinking and sourcing groups in one slice and why the terminal numbering on the drawing does not follow the 16 point pattern.
Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.
This part sits in the Allen-Bradley Flex I/O 1794 modules category, with the other models and spare parts listed alongside it.