Allen Bradley PLC 1794-TB2 / 1794TB2

China Allen Bradley PLC 1794-TB2 / 1794TB2 supplier
Allen Bradley PLC 1794-TB2 / 1794TB2 supplier Allen Bradley PLC 1794-TB2 / 1794TB2 supplier Allen Bradley PLC 1794-TB2 / 1794TB2 supplier Allen Bradley PLC 1794-TB2 / 1794TB2 supplier Allen Bradley PLC 1794-TB2 / 1794TB2 supplier Allen Bradley PLC 1794-TB2 / 1794TB2 supplier Allen Bradley PLC 1794-TB2 / 1794TB2 supplier Allen Bradley PLC 1794-TB2 / 1794TB2 supplier Allen Bradley PLC 1794-TB2 / 1794TB2 supplier

Large Image :  Allen Bradley PLC 1794-TB2 / 1794TB2

Product Details:

Place of Origin: Made in SINGAPORE
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1794-TB2 / 1794TB2

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $46.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 10 PCS
Detailed Product Description

1794-TB2 technical data PDF download FLEX I/O 1794-TB2 / 1794TB2 Terminal Base Unit, 2-Wire

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC I/O

The 1794-TB2 is the 2-wire base: 16 I/O, 18 common but only 2 +V terminals, for field devices that do not need a supply at every point.

The selection guide calls it a generic 2-wire version of the 1794-TB3. The missing +V terminals are the difference, and they are what a 3-wire proximity switch needs.

1794-TB2 16-terminal cage clamp base, 2-wire, up to 132V AC IN STOCK
1794-TB3 16-terminal cage clamp base, 3-wire devices IN STOCK
1794-TB3S 16-terminal spring clamp base, 3-wire devices IN STOCK
1794-TB32 32-terminal cage clamp base for 32-point modules IN STOCK
1794-TB32S 32-terminal spring clamp base for 32-point modules IN STOCK
1794-TB3T temperature base with two cold junction compensation sets IN STOCK
1794-TB3TS spring clamp temperature base with CJC sets IN STOCK
1794-TB3G grounded screw clamp base, 36 I/O, 10 chassis ground IN STOCK
1794-TB3GS grounded spring clamp base, 36 I/O, 10 chassis ground IN STOCK
1794-TBKD cage clamp base with 16 knife disconnects IN STOCK
1794-TBN NEMA-style screw clamp base, up to 264V AC/DC IN STOCK
1794-TBNF fused NEMA-style base, eight 5 x 20 mm fuses IN STOCK
1794-TB37DS 37-pin D-shell termination for digital and analog modules IN STOCK
1794-TB62DS 62-pin D-shell termination for digital and analog modules IN STOCK

Product Specifications 1794-TB2 (PDF)
 Application
 FLEX I/O 2-wire terminal base, 1794 backplane
 Cat Num
 1794-TB2
 Brand Name
 Rockwell
 Termination
 Cage clamp, 16 I/O, 18 common, 2 +V
 Wire size
 0.21...1.3 mm2 (24...16 AWG) stranded, 105 deg C or greater
 Current capacity
 10 A maximum
 Voltage
 Up to 132V AC / 156V DC
 Wiring category
 2
 Dimensions
 94 x 94 x 69 mm
 Operating temperature
 -20...55 deg C

Same-family catalog numbers: 1794-TB3, 1794-TB3S, 1794-TB32, 1794-TB32S. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1794 family.

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1794-TB2 original product photograph, wide view 1794-TB2 original product photograph, wide view 1794-TB2 original product photograph, wide view

Terminals

16 I/O, 18 common and 2 +V terminals, against 18 +V on the 1794-TB3.

Two-wire field devices — dry contacts, 2-wire proximity sensors — use the common return and need no supply terminal at each point.

10 A maximum current capacity, with 24...16 AWG stranded wire rated 105 deg C or greater.

Up to 132V AC / 156V DC on the terminals, category 2 wiring.

What it cannot do

No 3-wire sensor support, because a 3-wire device needs +V at its own terminal pair.

-20...55 deg C — narrower than the TB3 family's 70 deg C, so an -XT island does not use this base.

Narrower wire window 24...16 AWG than the 22...12 AWG of the 1794-TB3S, which matters on a retrofit.

94 x 94 x 69 mm footprint is the same as the rest of the family.

Application

Dry contact inputs and 2-wire sensors in a 24V DC panel.

Simple output groups where the load supply is field-side and not distributed from the base.

Not for 3-wire proximity switches, which need the 1794-TB3 or 1794-TB3S.

Not for -XT modules, because of the 55 deg C ceiling.

Mounting

35 x 7.5 mm DIN rail with 25 mm air space, or the 1794-NM1 panel-mount kit.

Zinc-plated, yellow-chromated steel rail for chassis grounding through the rail.

1492-EA35 rail locks where vibration or vertical mounting is expected.

Bases plug together to form the backplane, with one end cap per system.

Where it fits

2-wire field devices with no local supply requirement.

Cost-sensitive 24V islands in a heated panel.

Not for 3-wire sensors or -XT modules; the 1794-TB3 covers both.

Not for 32-point cards; the 1794-TB32 provides 32 I/O terminals.

FAQ — 1794-TB2

What is different about the 1794-TB2?

It has only 2 +V terminals instead of 18, for 2-wire field devices.

What voltage is it rated for?

Up to 132V AC / 156V DC.

What wire size does it accept?

0.21...1.3 mm2 (24...16 AWG) stranded, 105 deg C or greater.

What is the operating temperature?

-20...55 deg C, narrower than the 1794-TB3.

Can it take 3-wire proximity switches?

No; those need a +V terminal at each point, as on the 1794-TB3.

What current can it carry?

10 A maximum.


Data sources. Technical values on this page come from Rockwell publication 1794-SG002 (FLEX I/O Selection Guide, terminal base comparison) and 1794-IN092. Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Related numbers

Where the 1794-TB2 sits in the FLEX I/O range

1794-TB2 is a FLEX I/O terminal base unit, not an I/O module. It is the part that carries the field terminals, plugs into the adjacent base to form the backplane, and holds the module on top. The termination type here is Cage clamp with 16 I/O, 18 common, 2 +V.

AttributeValue
Catalog number1794-TB2
Termination typeCage clamp
Connections16 I/O, 18 common, 2 +V
Current capacity, maximum10 A
Wiring category2
Field voltageUp to 132V AC / 156V DC
Operating temperature-20...+55 C
Purpose in the rangeA generic 2-wire version of the 1794-TB3.

The conductor range for this base is 0.21 to 1.3 mm2 (24 to 16 AWG) stranded copper rated 105 C or greater, with 1.2 mm maximum insulation, with a maximum current capacity of 10 A across the base. Those figures are the base rating and not the module rating: a 16 point module on a 10 A base is still limited by the module output current per channel.

Selecting a base is a compatibility step, not a preference step. The module data sheet names the bases that are permitted for it, and a base outside that list may key differently, may not carry the required common and voltage terminals, or may not be rated for the field voltage of the module.

The D-shell bases, 1794-TB37DS and 1794-TB62DS, exist so a pre-wired cable can land on a connector instead of on screw terminals. They measure 127 by 94 by 69 mm with an expansion module installed, which is taller than the 94 by 94 by 69 mm envelope of the standard bases and has to be allowed for in the panel layout.

One point about the 24V DC digital slices that catches panel builders: the adapter supplies the field power for the modules on its own 24V output, and that output is current limited. On a 1794-ADN the supply output is 450 mA at 24V, so a slice of 16 point DC modules can exhaust the adapter before the cabinet is half filled, and a separate field supply has to be introduced rather than assumed.

Temperature class is written per module and per base, and the lower of the two governs the slice. A 70 C base carrying a 55 C module is a 55 C slice, which is why the extended temperature modules exist as a matched set rather than as an upgrade to one part of the pair.

Any FLEX I/O position is a pair on the purchase order: one base, one module. Stocking modules without bases, or bases without the matching modules, produces a slice that cannot be commissioned, and the two part numbers are never interchangeable across the 8, 16 and 32 point families.

Mounting is a DIN rail operation on both parts and the order of assembly is base first, module second: the base slides onto the rail, its backplane fingers engage the neighbouring base, and the module is then pressed onto the base and secured. Removing a module does not break the backplane, which is why a failed slice can be swapped without rewiring the row.

Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.

The Allen-Bradley Flex I/O 1794 modules category lists the related catalog numbers, options and accessories for this range.