Product Details:
Payment & Shipping Terms:
|
1771-IVN is a 1771 input module for the 1771 I/O chassis used by PLC-5 and PLC-2 processors. A catalog variant of the 1771 driver logic input family, with no current Rockwell product page.
Field connections land on the 1771-WA wiring arm, the 10-terminal arm that swings up to the module so the arm can stay wired while the module is swapped.
Catalog number |
1771-IVN |
Product type |
1771 input module |
Number of inputs |
Not published |
Input signal |
Not published |
Module series |
Not published |
1771 chassis compatibility |
Not published |
Lifecycle status |
Discontinued |
Discontinued date |
Not published |
Replacement category |
Not published |
UPC |
Not published |
Country of origin |
Not published |
Field wiring arm |
1771-WA, 10 terminal |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see the Rockwell literature library and the module-specific publication named in the technical data section above.
1771-IVN is a 1771 input module for the 1771 I/O chassis used by PLC-5 and PLC-2 processors. A catalog variant of the 1771 driver logic input family, with no current Rockwell product page.
The slot it occupies is one 1771 slot, and the input image it claims is fixed by the module series: Not published. That number decides how much of the processor input table the rack consumes, not how many wires the panel brings in.
Signal level is Not published. Nothing in the module is software configurable, so the field device has to match the printed range before the module is ordered.
Field connections land on the 1771-WA wiring arm, the 10-terminal arm that swings up to the module so the arm can stay wired while the module is swapped.
Keying bands in the chassis connector must line up with the slots on the module board. 1771 chassis are keyed per module type precisely so a 120 V AC module cannot be pushed into a slot wired for a 24 V DC module.
Backplane current comes from the chassis supply, so the load of every module in the rack has to be added up before a rack is repopulated with these cards.
The functional description of the base card is what the page can defend; the exact variant has to be ordered and checked by label.
Chassis compatibility is published per module series: Not published. Series A modules fit the superseded 1771-A1, -A2 and -A4 chassis as well as the current A1B to A4B and AM1/AM2 chassis.
Some 32-point and isolated cards can only be placed under 1-slot or 2-slot addressing rules, so the addressing mode of the chassis has to be confirmed before a mixed rack is built.
Rockwell lists 1771-IVN as Discontinued, replacement category Not published.
The published discontinued date is Not published.
The family replacement path is a 1756 or 1794 migration, which means the field wiring, the wiring arms and the addressing scheme all change. Buying the same catalog number is usually cheaper than re-terminating a panel.
Ask for a photo of the label side and the wiring arm. A module removed without its arm has to be re-keyed and re-wired, which is where most of the cost of a used card actually sits.
Check the module series letter against the chassis series: an A-series card in an A1B chassis works, but the reverse combination is what produces "module not recognised" faults.
These are static-sensitive cards. A unit shipped loose without conductive foam is a risk, whatever the price.
How many inputs does 1771-IVN have?
Not published, on the published 1771 data sheet.
What input signal does 1771-IVN accept?
Not published.
Which 1771 chassis will accept 1771-IVN?
Not published.
Is 1771-IVN still available from Rockwell?
No. It is listed as Discontinued with replacement category Not published.
What is the discontinued date of 1771-IVN?
Not published.
1771-IVN is a 1771 PLC-5 32 point DC input module, Series C, and the figures below come from the Rockwell installation data for the module rather than from a distributor listing.
| Specification | Value |
|---|---|
| Catalog number | 1771-IVN Series C, 32 point DC input module |
| Inputs per module | 32 |
| Input voltage range | 10 to 30V DC, referenced to the user supply |
| Nominal input current | 4.5 mA at supply minus 10V DC |
| On-state and off-state voltage | On-state at supply minus 10V DC; off-state 5V DC maximum referenced to the supply |
| Off-state current | 1.7 mA at supply minus 5V DC |
| Input impedance | 2.2 kOhm |
| Input signal delay | Low to high 6 ms plus or minus 2 ms; high to low 6 ms plus or minus 2 ms |
| Power dissipation | 15.6 W maximum, 1.5 W minimum |
| Thermal dissipation | 53.3 BTU per hour maximum, 5.1 BTU per hour minimum |
| Backplane current | 280 mA at 5V DC maximum |
| Isolation voltage | 1500V AC rms |
| Wiring note | 14 gauge wire on all terminals may prevent the field wiring arm cover from closing; a smaller gauge is permitted |
| Source | 1771-TD180-EN-P and installation data 1771-TD169 |
Thirty two inputs on one module means two field wiring arms worth of terminals, and the published note about fourteen gauge wire preventing the cover from closing is a real installation constraint rather than a curiosity. The arm cover is part of the touch protection.
Four and a half milliamps at ten volts referenced to the supply, with a six millisecond delay plus or minus two, makes this the dense general purpose input of the family. The dissipation of fifteen point six watts maximum and the adjacent slot allowance are what limit how many of them sit in one chassis.
Every figure on this page is taken from the Rockwell publication named in the source row, and where a value belongs to a companion table or to the family rather than to this exact catalog number, the row says so. No figure here is estimated, averaged or carried over from a similar part.
The gap between the on-state and off-state windows is the noise margin of the whole channel. A module that is on above 79 volts and off below 43 volts tolerates a large amount of induced noise between those two thresholds, and a module with a narrow gap will chatter on a long unshielded run.
Series letters carry real differences. A Series C module is not a cosmetic update of Series A, and the publication that covers one series does not necessarily describe the other; a replacement decision on an installed base has to read the series letter on the label first.
The published delay figures include a tolerance for a reason. Fifteen milliseconds plus or minus seven is a range that spans more than the nominal value, and a sequence that assumes the nominal value will occasionally see a scan where the input has not yet arrived.
Keying is a mechanical interlock, and the published keying positions are the only accepted ones for that catalog number. A wiring arm keyed for a different module type will either refuse to seat or, worse, seat on a module whose field wiring assumes a different voltage.
The wiring arm is the serviceable part. Field wires land on the arm, the arm carries the keying, and replacing a module means moving the arm rather than rewiring the panel. That is the practical reason the arm part number appears in the specification table.
A PLC-5 input module is specified by four numbers that matter on site: the voltage window in which the input is guaranteed on, the voltage below which it is guaranteed off, the current the field device must sink or source, and the delay the module adds before the processor sees the change.
Isolation voltage on these modules is a type test figure, not a continuous working voltage. Fifteen hundred volts AC rms for a minute is a dielectric proof, and a panel that sees a continuous common mode voltage has to be designed for that voltage rather than for the test figure.
Two wire and three wire field devices present very different loads. A module quoted at a minimum on-state current of a few milliamps will not reliably pick up a dry contact that carries almost nothing, and a module quoted at a high nominal current will not be driven by a low power sensor without a relay.
Every 1771 module in this family publishes its backplane current, its power dissipation and a maximum adjacent slot dissipation. Those three figures are how a chassis is planned: the backplane supply has a budget, the chassis has a thermal limit, and a hot module next to another hot module is a derating decision made on paper.
A module that is not compatible with a particular adapter is a statement about backplane protocol, not about power. The 1771 local I/O adapter family supports a subset of the catalog, and a module outside that subset will not run behind that adapter regardless of the wiring.
These modules are mature products with an installed base measured in decades, which changes what the page is for. It is not a selection tool for new designs; it is a reference for identifying, replacing and re-rating a module that is already in a panel, often with the original drawing missing.
Filtering and delay are the same trade expressed twice. A module with a selectable delay lets the programmer choose between a fast response that inherits contact bounce and a slow response that ignores it, and the field device decides which of the two is correct.
Chassis temperature inside the enclosure is the sum of the modules, not the average. A rack full of input modules runs cool, a rack with high dissipation output modules runs hot, and the published maximum adjacent slot dissipation is the rule that keeps a hot module from cooking its neighbour.
Plan the two wiring arms and the wire gauge, and check the chassis thermal budget before installing a full rack of thirty two point inputs.
This part sits in the Allen-Bradley PLC-5 systems and 1771 I/O category, with the other models and spare parts listed alongside it.