logo
Home ProductsAB PLC-5 Systems

Allen Bradley PLC 1771-IV / 1771IV

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1771-IV / 1771IV

China Allen Bradley PLC 1771-IV / 1771IV supplier
Allen Bradley PLC 1771-IV / 1771IV supplier Allen Bradley PLC 1771-IV / 1771IV supplier Allen Bradley PLC 1771-IV / 1771IV supplier Allen Bradley PLC 1771-IV / 1771IV supplier Allen Bradley PLC 1771-IV / 1771IV supplier

Large Image :  Allen Bradley PLC 1771-IV / 1771IV

Product Details:

Place of Origin: Made in USA
Brand Name: PLC Module
Certification: All goods we supply with 1 year warranty!
Model Number: Allen Bradley PLC 1771-IV / 1771IV

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $902.00 (USD/PCS)
Packaging Details: 100% New packaging
Delivery Time: IN STOCK; 2-4 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 2 PCS
Detailed Product Description

1771-IV technical data PDF download 1771-IV Rockwell Driver Logic Input Module

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: Bulletin 1771 · PLC-5 input modules

1771-IV is a Driver logic input module for the 1771 I/O chassis used by PLC-5 and PLC-2 processors. A driver logic input card reads the output of a power driver rather than a switch, which is how a 1771 rack monitors a drive or a solid state contactor without a separate feedback relay.

Field connections land on the 1771-WA wiring arm, the 10-terminal arm that swings up to the module so the arm can stay wired while the module is swapped.


Product Specifications 1771-IV (PDF)
 Catalog number
 1771-IV
 Product type
 Driver logic input module
 Number of inputs
 Not published
 Input signal
 Driver logic level
 Module series
 A
 1771 chassis compatibility
 Series A and B chassis
 Lifecycle status
 Discontinued
 Discontinued date
 31 March 2021
 Replacement category
 Engineering Replacement
 UPC
 612598002474
 Country of origin
 Mexico
 Field wiring arm
 1771-WA, 10 terminal

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publication 1771-TD180 (module specifications) and the Rockwell literature library (installation instructions).

1771-IV 1771-IV

What the module does in a 1771 rack

1771-IV is a Driver logic input module for the 1771 I/O chassis used by PLC-5 and PLC-2 processors. A driver logic input card reads the output of a power driver rather than a switch, which is how a 1771 rack monitors a drive or a solid state contactor without a separate feedback relay.

The slot it occupies is one 1771 slot, and the input image it claims is fixed by the module series: Not published. That number decides how much of the processor input table the rack consumes, not how many wires the panel brings in.

Signal level is Driver logic level. Nothing in the module is software configurable, so the field device has to match the printed range before the module is ordered.

Wiring, keying and the 1771-WA arm

Field connections land on the 1771-WA wiring arm, the 10-terminal arm that swings up to the module so the arm can stay wired while the module is swapped.

Keying bands in the chassis connector must line up with the slots on the module board. 1771 chassis are keyed per module type precisely so a 120 V AC module cannot be pushed into a slot wired for a 24 V DC module.

Backplane current comes from the chassis supply, so the load of every module in the rack has to be added up before a rack is repopulated with these cards.

Published compatibility: image bits 8, module series A, unrestricted in both chassis series.

Chassis compatibility and addressing

Chassis compatibility is published per module series: Series A and B chassis. Series A modules fit the superseded 1771-A1, -A2 and -A4 chassis as well as the current A1B to A4B and AM1/AM2 chassis.

Some 32-point and isolated cards can only be placed under 1-slot or 2-slot addressing rules, so the addressing mode of the chassis has to be confirmed before a mixed rack is built.

Lifecycle and replacement

Rockwell lists 1771-IV as Discontinued, replacement category Engineering Replacement.

The published discontinued date is 31 March 2021.

The family replacement path is a 1756 or 1794 migration, which means the field wiring, the wiring arms and the addressing scheme all change. Buying the same catalog number is usually cheaper than re-terminating a panel.

Buying a used module

Ask for a photo of the label side and the wiring arm. A module removed without its arm has to be re-keyed and re-wired, which is where most of the cost of a used card actually sits.

Check the module series letter against the chassis series: an A-series card in an A1B chassis works, but the reverse combination is what produces "module not recognised" faults.

These are static-sensitive cards. A unit shipped loose without conductive foam is a risk, whatever the price.

FAQ — 1771-IV

How many inputs does 1771-IV have?

Not published, on the published 1771 data sheet.

What input signal does 1771-IV accept?

Driver logic level.

Which 1771 chassis will accept 1771-IV?

Series A and B chassis.

Is 1771-IV still available from Rockwell?

No. It is listed as Discontinued with replacement category Engineering Replacement.

What is the discontinued date of 1771-IV?

31 March 2021.


Data sources. Point counts, input signal ranges and chassis codes come from the 1771 technical data sheets (1771-TD180 for DC, 1771-TD041 and 1771-IN082 for the 24 V AC module, 1771-IN046 and 1771-IN051 for analog); lifecycle dates, UPC and country of origin come from the Rockwell product page for the catalog number. Where Rockwell has withdrawn the catalog page, the field is marked Not published rather than guessed. Any attribute a publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Related numbers

1771-IV: 8 point sourcing DC input module

1771-IV is a 1771 PLC-5 8 point sourcing DC input module, and the figures below come from the Rockwell installation data for the module rather than from a distributor listing.

SpecificationValue
Catalog number1771-IV, DC input module, sourcing configuration
Inputs per module8
Input voltage range12 to 24V DC, referenced to the user supply
Nominal input current8 mA at supply minus 12V DC; 24 mA at supply minus 24V DC
On-state and off-state voltageOn-state at supply minus 10V DC; off-state current 3.0 mA at supply minus 7V DC
Input impedance1 to 2 kOhm on-state maximum; 2 to 3 kOhm off-state maximum
Input signal delayLow to high 15 ms plus or minus 7 ms; high to low 15 ms plus or minus 7 ms
Power dissipation5.8 W maximum, 0.4 W minimum
Thermal dissipation19.9 BTU per hour maximum, 1.3 BTU per hour minimum
Backplane current74 mA at 5V DC
Isolation voltage1500V AC rms
Operating temperature0 to 60 degrees C; storage minus 40 to 85 degrees C
KeyingBetween 8 and 10, and between 12 and 14
Source1771-TD180-EN-P, 1771 digital I/O DC input and output modules

This module is referenced to the user supply rather than to a fixed threshold, so the on-state point moves with the supply. A twelve volt supply puts the on-state point at two volts above common, and a twenty four volt supply puts it at fourteen, which changes the margin against a leaking field device.

Fifteen milliseconds of delay in both directions makes this a general purpose module. It is not for registration or for fast interlocks, and the published tolerance of plus or minus seven milliseconds is wide enough to matter in a sequence that counts scans.

Every figure on this page is taken from the Rockwell publication named in the source row, and where a value belongs to a companion table or to the family rather than to this exact catalog number, the row says so. No figure here is estimated, averaged or carried over from a similar part.

Filtering and delay are the same trade expressed twice. A module with a selectable delay lets the programmer choose between a fast response that inherits contact bounce and a slow response that ignores it, and the field device decides which of the two is correct.

Chassis temperature inside the enclosure is the sum of the modules, not the average. A rack full of input modules runs cool, a rack with high dissipation output modules runs hot, and the published maximum adjacent slot dissipation is the rule that keeps a hot module from cooking its neighbour.

The gap between the on-state and off-state windows is the noise margin of the whole channel. A module that is on above 79 volts and off below 43 volts tolerates a large amount of induced noise between those two thresholds, and a module with a narrow gap will chatter on a long unshielded run.

Series letters carry real differences. A Series C module is not a cosmetic update of Series A, and the publication that covers one series does not necessarily describe the other; a replacement decision on an installed base has to read the series letter on the label first.

The published delay figures include a tolerance for a reason. Fifteen milliseconds plus or minus seven is a range that spans more than the nominal value, and a sequence that assumes the nominal value will occasionally see a scan where the input has not yet arrived.

Keying is a mechanical interlock, and the published keying positions are the only accepted ones for that catalog number. A wiring arm keyed for a different module type will either refuse to seat or, worse, seat on a module whose field wiring assumes a different voltage.

The wiring arm is the serviceable part. Field wires land on the arm, the arm carries the keying, and replacing a module means moving the arm rather than rewiring the panel. That is the practical reason the arm part number appears in the specification table.

A PLC-5 input module is specified by four numbers that matter on site: the voltage window in which the input is guaranteed on, the voltage below which it is guaranteed off, the current the field device must sink or source, and the delay the module adds before the processor sees the change.

Isolation voltage on these modules is a type test figure, not a continuous working voltage. Fifteen hundred volts AC rms for a minute is a dielectric proof, and a panel that sees a continuous common mode voltage has to be designed for that voltage rather than for the test figure.

Two wire and three wire field devices present very different loads. A module quoted at a minimum on-state current of a few milliamps will not reliably pick up a dry contact that carries almost nothing, and a module quoted at a high nominal current will not be driven by a low power sensor without a relay.

Every 1771 module in this family publishes its backplane current, its power dissipation and a maximum adjacent slot dissipation. Those three figures are how a chassis is planned: the backplane supply has a budget, the chassis has a thermal limit, and a hot module next to another hot module is a derating decision made on paper.

A module that is not compatible with a particular adapter is a statement about backplane protocol, not about power. The 1771 local I/O adapter family supports a subset of the catalog, and a module outside that subset will not run behind that adapter regardless of the wiring.

These modules are mature products with an installed base measured in decades, which changes what the page is for. It is not a selection tool for new designs; it is a reference for identifying, replacing and re-rating a module that is already in a panel, often with the original drawing missing.

Design the threshold against the actual supply voltage, not against the nominal, and keep this module out of fast interlock paths.

Browse the Allen-Bradley PLC-5 systems and 1771 I/O category for the other models, options and spare parts that share this range.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)