Product Details:
Payment & Shipping Terms:
|
1771-IQ16 is a 16-point isolated DC input module for the 1771 I/O chassis used by PLC-5 and PLC-2 processors. Sixteen isolated 24 V DC inputs on one slot, used where the sensor returns must not be commoned in the chassis.
Field connections land on the 1771-WA wiring arm, the 10-terminal arm that swings up to the module so the arm can stay wired while the module is swapped.
Catalog number |
1771-IQ16 |
Product type |
16-point isolated DC input module |
Number of inputs |
16 |
Input signal |
24 V DC, isolated |
Module series |
Not published |
1771 chassis compatibility |
Series A and B chassis |
Lifecycle status |
Discontinued |
Discontinued date |
10 March 2020 |
Replacement category |
Engineering Replacement |
UPC |
612598115938 |
Country of origin |
Mexico |
Field wiring arm |
1771-WA, 10 terminal |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see the Rockwell literature library and the module-specific publication named in the technical data section above.
1771-IQ16 is a 16-point isolated DC input module for the 1771 I/O chassis used by PLC-5 and PLC-2 processors. Sixteen isolated 24 V DC inputs on one slot, used where the sensor returns must not be commoned in the chassis.
The slot it occupies is one 1771 slot, and the input image it claims is fixed by the module series: 16. That number decides how much of the processor input table the rack consumes, not how many wires the panel brings in.
Signal level is 24 V DC, isolated. Nothing in the module is software configurable, so the field device has to match the printed range before the module is ordered.
Field connections land on the 1771-WA wiring arm, the 10-terminal arm that swings up to the module so the arm can stay wired while the module is swapped.
Keying bands in the chassis connector must line up with the slots on the module board. 1771 chassis are keyed per module type precisely so a 120 V AC module cannot be pushed into a slot wired for a 24 V DC module.
Backplane current comes from the chassis supply, so the load of every module in the rack has to be added up before a rack is repopulated with these cards.
Chassis compatibility is published per module series: Series A and B chassis. Series A modules fit the superseded 1771-A1, -A2 and -A4 chassis as well as the current A1B to A4B and AM1/AM2 chassis.
Some 32-point and isolated cards can only be placed under 1-slot or 2-slot addressing rules, so the addressing mode of the chassis has to be confirmed before a mixed rack is built.
Rockwell lists 1771-IQ16 as Discontinued, replacement category Engineering Replacement.
The published discontinued date is 10 March 2020.
The family replacement path is a 1756 or 1794 migration, which means the field wiring, the wiring arms and the addressing scheme all change. Buying the same catalog number is usually cheaper than re-terminating a panel.
Ask for a photo of the label side and the wiring arm. A module removed without its arm has to be re-keyed and re-wired, which is where most of the cost of a used card actually sits.
Check the module series letter against the chassis series: an A-series card in an A1B chassis works, but the reverse combination is what produces "module not recognised" faults.
These are static-sensitive cards. A unit shipped loose without conductive foam is a risk, whatever the price.
How many inputs does 1771-IQ16 have?
16, on the published 1771 data sheet.
What input signal does 1771-IQ16 accept?
24 V DC, isolated.
Which 1771 chassis will accept 1771-IQ16?
Series A and B chassis.
Is 1771-IQ16 still available from Rockwell?
No. It is listed as Discontinued with replacement category Engineering Replacement.
What is the discontinued date of 1771-IQ16?
10 March 2020.
1771-IQ16 is a 1771 PLC-5 16 point isolated 24V DC input module, Series C, and the figures below come from the Rockwell installation data for the module rather than from a distributor listing.
| Specification | Value |
|---|---|
| Catalog number | 1771-IQ16 Series C, DC isolated input module |
| Inputs per module | 16 |
| Module location | 1771-A1B through -A4B I/O chassis, Series B or later chassis |
| Input voltage range | 10 to 32V DC from the user supply |
| Nominal input voltage | 24V DC |
| On-state and off-state voltage | On-state 10V DC minimum; off-state 5V DC maximum |
| On-state and off-state current | 6.0 mA minimum at 10V DC; off-state current 2 mA at 5V DC |
| Maximum input current | 30 mA at 32V DC |
| Input impedance | 3.2 kOhm maximum |
| Input signal delay | 0.57 ms fixed, or customer selectable 0, 0.57, 9 or 18 ms |
| Power dissipation | 15.0 W maximum, 0.5 W minimum |
| Adapter compatibility | Not compatible with the 1771-AL local I/O adapter |
| Source | 1771-IN025 installation instructions, 1771-IQ16 Series C, and 1771-TD180-EN-P |
The selectable delay of zero, 0.57, 9 or 18 milliseconds is the whole configuration of this module, and zero milliseconds means no filtering at all. An installation that selects zero to get a fast response also accepts every noise transient on the field wiring.
The explicit statement that this module is not compatible with the 1771-AL local I/O adapter is the kind of fact that is only discovered when the panel is already built. It belongs on the page, not in a footnote of an adapter manual.
Every figure on this page is taken from the Rockwell publication named in the source row, and where a value belongs to a companion table or to the family rather than to this exact catalog number, the row says so. No figure here is estimated, averaged or carried over from a similar part.
Keying is a mechanical interlock, and the published keying positions are the only accepted ones for that catalog number. A wiring arm keyed for a different module type will either refuse to seat or, worse, seat on a module whose field wiring assumes a different voltage.
The wiring arm is the serviceable part. Field wires land on the arm, the arm carries the keying, and replacing a module means moving the arm rather than rewiring the panel. That is the practical reason the arm part number appears in the specification table.
A PLC-5 input module is specified by four numbers that matter on site: the voltage window in which the input is guaranteed on, the voltage below which it is guaranteed off, the current the field device must sink or source, and the delay the module adds before the processor sees the change.
Isolation voltage on these modules is a type test figure, not a continuous working voltage. Fifteen hundred volts AC rms for a minute is a dielectric proof, and a panel that sees a continuous common mode voltage has to be designed for that voltage rather than for the test figure.
Two wire and three wire field devices present very different loads. A module quoted at a minimum on-state current of a few milliamps will not reliably pick up a dry contact that carries almost nothing, and a module quoted at a high nominal current will not be driven by a low power sensor without a relay.
Every 1771 module in this family publishes its backplane current, its power dissipation and a maximum adjacent slot dissipation. Those three figures are how a chassis is planned: the backplane supply has a budget, the chassis has a thermal limit, and a hot module next to another hot module is a derating decision made on paper.
A module that is not compatible with a particular adapter is a statement about backplane protocol, not about power. The 1771 local I/O adapter family supports a subset of the catalog, and a module outside that subset will not run behind that adapter regardless of the wiring.
These modules are mature products with an installed base measured in decades, which changes what the page is for. It is not a selection tool for new designs; it is a reference for identifying, replacing and re-rating a module that is already in a panel, often with the original drawing missing.
Filtering and delay are the same trade expressed twice. A module with a selectable delay lets the programmer choose between a fast response that inherits contact bounce and a slow response that ignores it, and the field device decides which of the two is correct.
Chassis temperature inside the enclosure is the sum of the modules, not the average. A rack full of input modules runs cool, a rack with high dissipation output modules runs hot, and the published maximum adjacent slot dissipation is the rule that keeps a hot module from cooking its neighbour.
The gap between the on-state and off-state windows is the noise margin of the whole channel. A module that is on above 79 volts and off below 43 volts tolerates a large amount of induced noise between those two thresholds, and a module with a narrow gap will chatter on a long unshielded run.
Series letters carry real differences. A Series C module is not a cosmetic update of Series A, and the publication that covers one series does not necessarily describe the other; a replacement decision on an installed base has to read the series letter on the label first.
The published delay figures include a tolerance for a reason. Fifteen milliseconds plus or minus seven is a range that spans more than the nominal value, and a sequence that assumes the nominal value will occasionally see a scan where the input has not yet arrived.
Select the delay deliberately, confirm the chassis series and the adapter compatibility before ordering, and treat zero milliseconds as no filtering at all.
This part sits in the Allen-Bradley PLC-5 systems and 1771 I/O category, with the other models and spare parts listed alongside it.