Product Details:
Payment & Shipping Terms:
|
1771-IH is a 8-point DC input module for the 1771 I/O chassis used by PLC-5 and PLC-2 processors. The wide 24 to 48 V DC window makes it the card for panels that carry both voltages, or for a 48 V DC station that occasionally sees 24 V devices.
Field connections land on the 1771-WA wiring arm, the 10-terminal arm that swings up to the module so the arm can stay wired while the module is swapped.
Catalog number |
1771-IH |
Product type |
8-point DC input module |
Number of inputs |
8 |
Input signal |
24-48 V DC |
Module series |
A |
1771 chassis compatibility |
Series A and B chassis |
Lifecycle status |
Discontinued |
Discontinued date |
31 January 2021 |
Replacement category |
Engineering Replacement |
UPC |
662468205535 |
Country of origin |
Not published |
Field wiring arm |
1771-WA, 10 terminal |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publication 1771-TD180 (module specifications) and the Rockwell literature library (installation instructions).
1771-IH is a 8-point DC input module for the 1771 I/O chassis used by PLC-5 and PLC-2 processors. The wide 24 to 48 V DC window makes it the card for panels that carry both voltages, or for a 48 V DC station that occasionally sees 24 V devices.
The slot it occupies is one 1771 slot, and the input image it claims is fixed by the module series: 8. That number decides how much of the processor input table the rack consumes, not how many wires the panel brings in.
Signal level is 24-48 V DC. Nothing in the module is software configurable, so the field device has to match the printed range before the module is ordered.
Field connections land on the 1771-WA wiring arm, the 10-terminal arm that swings up to the module so the arm can stay wired while the module is swapped.
Keying bands in the chassis connector must line up with the slots on the module board. 1771 chassis are keyed per module type precisely so a 120 V AC module cannot be pushed into a slot wired for a 24 V DC module.
Backplane current comes from the chassis supply, so the load of every module in the rack has to be added up before a rack is repopulated with these cards.
As with every card in the family, the field range has to be printed on the device before it is wired.
Chassis compatibility is published per module series: Series A and B chassis. Series A modules fit the superseded 1771-A1, -A2 and -A4 chassis as well as the current A1B to A4B and AM1/AM2 chassis.
Some 32-point and isolated cards can only be placed under 1-slot or 2-slot addressing rules, so the addressing mode of the chassis has to be confirmed before a mixed rack is built.
Rockwell lists 1771-IH as Discontinued, replacement category Engineering Replacement.
The published discontinued date is 31 January 2021.
The family replacement path is a 1756 or 1794 migration, which means the field wiring, the wiring arms and the addressing scheme all change. Buying the same catalog number is usually cheaper than re-terminating a panel.
Ask for a photo of the label side and the wiring arm. A module removed without its arm has to be re-keyed and re-wired, which is where most of the cost of a used card actually sits.
Check the module series letter against the chassis series: an A-series card in an A1B chassis works, but the reverse combination is what produces "module not recognised" faults.
These are static-sensitive cards. A unit shipped loose without conductive foam is a risk, whatever the price.
How many inputs does 1771-IH have?
8, on the published 1771 data sheet.
What input signal does 1771-IH accept?
24-48 V DC.
Which 1771 chassis will accept 1771-IH?
Series A and B chassis.
Is 1771-IH still available from Rockwell?
No. It is listed as Discontinued with replacement category Engineering Replacement.
What is the discontinued date of 1771-IH?
31 January 2021.
1771-IH is a discrete module for the 1771 I/O chassis used with PLC-5 and earlier Allen-Bradley controllers, specified here from the Rockwell installation data so that the threshold, the backplane load and the wiring arm part number are on one page instead of in three documents.
| Specification | Value |
|---|---|
| Inputs | 8 per module |
| Input voltage range | 24 to 50V DC |
| Nominal input current | 8.4 mA at 24V DC, 20 mA at 48V DC |
| Minimum on-state voltage | 10V DC |
| Input impedance | 2.5 to 3 kOhm maximum on-state, 5 to 6 kOhm maximum off-state |
| Backplane current | 74 mA at 5V DC plus or minus 5 percent |
| Field wiring arm | 1771-WA, 10 terminals |
| Compatible devices | 2-wire devices, including DC proximity switches, pushbuttons, limit switches, float and selector switches |
| Module location | 1771 I/O chassis, keyed slot |
| Isolation | Opto-electrical isolation between field and backplane, per the installation data sheet |
| Operating temperature | 0 to 60 degrees C, storage -40 to 85 degrees C, 5 to 95 percent humidity |
| Source | 1771-2.8 installation data, publication 1771-TD008 |
The 24 to 48V input is the workhorse card for a plant that runs a 48V DC control bus rather than 24V. The published figures make the difference visible: 8.4 mA at 24V and 20 mA at 48V, with a 10V minimum on-state threshold and a 2.5 to 3 kOhm on-state impedance, which is what a two-wire sensor has to drive.
The trap on this card is the off-state impedance, 5 to 6 kOhm. A sensor with a leakage current sized for a 24V input may not pull the point below the threshold on a 48V bus, and the symptom is an input that stays on. Checking leakage against the published impedance is faster than replacing the module.
A 1771 card is bought against three numbers: the backplane current, because the chassis supply has to carry the whole rack, the on-state threshold, because the field device has to reach it, and the field wiring arm catalog number, because a module without the right arm cannot be wired at all. All three are in the table above.
Opto-electrical isolation is quoted in the thousands of volts on these modules, which is what allows a 120V field circuit and a 5V backplane to share a card. It does not protect against a wrong supply applied to the wrong terminal, so polarity and terminal identification remain the installer's job.
A chassis is a shared resource: the adapter module sits in the leftmost slot, and every I/O card is addressed relative to it. Adding a card in the middle of a rack can shift addressing unless the rack is planned as 1-slot or 1/2-slot from the start, which is why the addressing mode is documented with the chassis rather than with the module.
A 1771 module is a single slot in a PLC-5 era chassis, and everything it needs travels through the backplane except the field signals themselves. That is why the backplane current figure matters more than the module footprint: a rack full of these has to stay inside the chassis power supply budget, and the number is printed on every installation data sheet for exactly that reason.
Check the sensor leakage against the 5 to 6 kOhm off-state impedance before the card is blamed, key the slot for this module, and order the 1771-WA arm with every spare.
The Allen-Bradley PLC-5 systems and 1771 I/O category lists the related catalog numbers, options and accessories for this range.