This page covers catalog number 1771-ID16K, the catalog number this shop lists as 1771-ID16K, set against the published 1771-ID16 sixteen point AC input module data. Where a suffix on this listing is not defined by the manufacturer, the page says so and prints the documented module data; no specification has been invented for the suffix.
| Specification | Value |
|---|---|
| Catalog number, module | 1771-ID16 |
| Inputs per module | 16 |
| Input voltage range | 74 to 138V AC at 47 to 63 Hz; 105 to 138V DC |
| Nominal input voltage | 120V AC or DC |
| Minimum on voltage | 74V AC, 105V DC |
| Minimum on current | 6.0 mA at 74V AC 47 to 63 Hz; 12.0 mA at 105V DC |
| Maximum off current | 4 mA at 45V AC 47 to 63 Hz; 0.8 mA at 63V DC |
| Maximum off voltage | 45V AC, 66V DC |
| Input impedance | 9.3 kΩ at 47 Hz, 6.9 kΩ at 63 Hz |
| Input signal delay, AC | Selectable 9 or 18 ms on to off; 0.57 ms off to on; filter factory set to 9.0 ms |
| Input signal delay, DC | 9.0 ms on to off, 0.57 ms off to on |
| Power dissipation | 7.0 W maximum |
| Chassis requirement | Series B or later 1771 I/O chassis; not compatible with the 1771-AL local I/O adapter |
| Bleeder resistor for high leakage sensors | 5 kΩ 3 W, from the bleeder table in publication 871-WD001 |
| Maximum off-state current used for sensor selection | 4.0 mA |
| Lifecycle | Discontinued, Engineering Replacement category |
| Technical data | 1771-TD189; installation instructions 1771-IN070 |
Sixteen points in one slot share a reference, and that is the published trade against the six point isolated card. The shared reference means all sixteen signals sit on one 120 volt circuit with one common; it also means an insulation fault on one field cable can affect the group, which is why a mixed panel separates isolated signals from dense ones.
The published input range starts at seventy four volts, which is below the ninety two volt floor of the six point isolated card in the same family. A 120 volt circuit that sags under load stays inside this window and leaves the tighter card, and that difference decides which card survives a brownout rather than which card is cheaper.
Nine milliseconds is the factory filter setting, and eighteen is available for a channel that picks up contact bounce. The parameter is per module rather than per channel on this card, so one noisy input sets the response time for all sixteen, and the published instruction to select before commissioning follows from that.
The published on current of twelve milliamps at one hundred and five volts DC is the figure for DC sensors, and it is high because a DC input has to hold its own opto current without the AC crossing that helps an AC channel. A DC sensor rated for ten milliamps at its own voltage is therefore marginal on this channel rather than comfortable.
Long field runs on AC input are a cable capacitance problem before they are a voltage drop problem. The published impedance falls from nine point three kilo-ohms at forty seven hertz to six point nine at sixty three, which is a network that draws current continuously, and a long cable adds its own capacitance on top of it.
A dense card looks like a cheaper way to get sixteen points and it is, until one channel needs isolation or a different reference. The published data for both cards makes the boundary visible, and the boundary is engineering rather than commercial: density shares a reference, isolation does not.
The published bleeder table in the sensor interface manual names a five kilo-ohm three watt resistor for this module, and that resistor exists because four milliamps of leakage is easy to exceed with a long cable or a solid state sensor. Fitting the bleeder is a published remedy, not an improvisation.
Selectable filtering of nine or eighteen milliseconds on the AC path is published, with the short setting as factory default. The long setting rejects contact bounce and line noise at the cost of response; a channel that must catch a short pulse cannot use it, and a channel that chatters should.
Nine point three kilo-ohms at forty seven hertz against six point nine at sixty three hertz is a published impedance that falls with frequency, which is what a capacitive input looks like. It also explains why this card draws a small AC current continuously, and why an insulation test on the field wiring must be done with the card removed.
The published restriction against the 1771-AL local I/O adapter is the kind of row that decides an upgrade path. A chassis that uses a local adapter cannot carry this module, and that fact is invisible until the module is installed and refuses to be scanned.
Seven watts maximum dissipation is published for sixteen AC inputs, and it is the thermal number a closed cabinet has to carry. Sixteen points at 120 volts are not free: the input network dissipates continuously, and the published figure is the sum of it.
Discontinued status with an engineering replacement category means the published data outlives the product, and it is the only reliable description of what is installed. Reseller pages round the figures and drop the restriction rows, and the restriction rows are the ones that stop a substitution from working.
Density and isolation are traded against each other in this family. The six point card is isolated per channel; this sixteen point card is dense and shares its reference. A panel that needs both buys two cards, and the published data makes the reason visible.
Sixteen inputs in a published window of seventy four to one hundred and thirty eight volts AC is a dense AC card, and density on an AC input is bought with current. The minimum on current of six milliamps at seventy four volts is what a two wire sensor has to deliver, and the maximum off current of four milliamps is what it must not leak.
The other 1771 modules and PLC-5 chassis parts are collected in the PLC-5 category. This catalog number can be checked against the shop listing at 1771-ID16K.