Product Details:
Payment & Shipping Terms:
|
The 1756-IF8 (also written 1756IF8) is the workhorse analog input of the ControlLogix chassis: eight single-ended inputs, reconfigurable as four differential or two high-speed differential channels, backplane load 200 mA at 5.1 V DC and 30 mA at 24 V DC, power consumption 1.74 W (1756-TD002).
Resolution is quoted per count: 320 µV on the ±10 V range, 160 µV on 0...10 V, 80 µV on 0...5 V and 0.32 µA on 0...20 mA. Input impedance is 10 MΩ or greater in voltage mode and 249 Ω in current mode, which is what makes a 4...20 mA loop readable without an external resistor.
Accuracy is published separately for the two signal types: 0.05 % of range for voltage and 0.15 % for current, immediately after calibration, with module error over the temperature range quoted at 0.1 % and 0.3 % respectively. Module scan time runs from 16 to 488 ms depending on the notch filter setting.
Isolation is 250 V continuous basic from inputs to the backplane, with no isolation between individual inputs. That is the line that separates the IF8 from the IF8I, and it decides whether grounded thermocouples or transmitters on separate supplies may be mixed on one module. Technical data 1756-TD002, user manual 1756-UM009, installation instructions 1756-IN063.
1756-IF4FXOF2F |
4 high-speed differential inputs + 2 outputs, 375 mA, reinforced isolation |
In stock |
1756-IF6CIS |
6 isolated current inputs with sourcing 24 V DC loop supply |
In stock |
1756-IF6I |
6 isolated inputs, 16-bit, 250 mA, channel-to-channel basic isolation |
In stock |
1756-IF8 |
8 single-ended / 4 differential inputs, 200 mA, 250 V basic to backplane |
In stock |
1756-IF8H |
8 differential HART current inputs, A and B series |
In stock |
1756-IF16 |
16 single-ended / 8 differential inputs, 200 mA, 15 Hz bandwidth |
In stock |
1756-IF16H |
16 differential HART current inputs, A and B series |
In stock |
1756-IRT8I |
8 isolated RTD and thermocouple inputs, 24-bit, 1756-CJC required |
In stock |
1756-IR6I |
6 isolated RTD inputs, 20-pin block, discontinued 2017 |
In stock |
1756-IT6I |
6 thermocouple inputs, two mV ranges, one CJC sensor |
In stock |
1756-IT6I2 |
6 isolated thermocouple inputs, 16-bit, two CJC sensors |
In stock |
Application |
Analog input |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-IF8 |
Communication |
Backplane (producer/consumer) |
Display |
— |
Enclosure |
None (open-style) |
Interface |
Removable terminal block |
Mounting |
Chassis slot |
Number Of Channels |
8 |
Standard |
CE, UL, CSA, RCM |
Sub Brand |
ControlLogix |
Type |
Analog Input Module |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN063 (analog I/O installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The IF8 is the standard choice for a mixed analog panel: pressure and level transmitters on 4...20 mA, a few 0...10 V signals from drives, and temperature only where a thermocouple is already conditioned externally.
Because all eight channels share a reference, the IF8 suits a marshalled installation where every transmitter is loop-powered from the same panel supply and returns to the same common — the ordinary case in process skids and packaged plant.
Where the panel has to prove separation between field circuits, the module is the wrong starting point. Specify the IF8I and get 250 V reinforced to the backplane plus basic channel-to-channel, at 24-bit resolution.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | Basic isolation only | 250 V basic to the backplane and no channel-to-channel barrier. Grounded junctions at different potentials need the IF8I. |
| Check 3 | Scan time follows the notch filter | 16...488 ms across the filter settings. A 488 ms update is a deliberate choice for noise rejection, not a fault. |
| Check 4 | Current input is 249 Ω | A 4...20 mA loop across 249 Ω develops 1.0...5.0 V at the terminals; the loop supply has to carry that burden. |
| Check 5 | Backplane 200 mA | Cheaper than the isolated family per channel, but a chassis of eight IF8 modules still draws 1.6 A from the 5.1 V rail. |
Specifications per Rockwell publication 1756-TD002 (ControlLogix I/O Modules Specifications); module behaviour per 1756-UM009 and 1756-IN050.
The isolated equivalent is 1756-IF8I: eight isolated channels, 250 V reinforced to the backplane, 250 V basic input-to-input, 24-bit resolution.
For channel count without isolation, 1756-IF16 carries 16 single-ended inputs at the same 200 mA backplane figure and the same 250 V basic barrier.
For HART instruments, 1756-IF8H adds a HART modem (one per module on the A series, one per channel on the B series); for RTDs and thermocouples, 1756-IRT8I and 1756-IR12.
What is the 1756-IF8?
An 8-channel analog input module for the ControlLogix chassis, configurable as 8 single-ended, 4 differential or 2 high-speed differential inputs.
What is the backplane current?
200 mA at 5.1 V DC and 30 mA at 24 V DC, 1.74 W power consumption (1756-TD002).
What resolution does it have?
320 µV per count on ±10 V, 160 µV on 0...10 V, 80 µV on 0...5 V and 0.32 µA per count on 0...20 mA.
What accuracy is published?
0.05 % of range for voltage and 0.15 % for current immediately after calibration; module error 0.1 % and 0.3 % over the temperature range.
What isolation does it provide?
250 V continuous basic insulation from inputs to the backplane, with no isolation between individual inputs.
How long is the scan time?
16...488 ms, depending on the notch filter configuration.
Can I mix voltage and current channels?
Yes — each channel is configured individually for its range in the Logix Designer project.
What documents cover it?
1756-TD002 for technical data, 1756-UM009 for the user manual and 1756-IN063 for installation.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-IF8. Values re-checked 15 November 2026.