Product Details:
Payment & Shipping Terms:
|
The 1756-IF6I (also written 1756IF6I) is the isolated 6-channel analog input: six individually isolated channels accepting ±10.5 V, 0...10.5 V, 0...5.25 V or 0...21 mA, backplane load 250 mA at 5.1 V DC and 100 mA at 24 V DC, total backplane power 3.7 W (1756-TD002).
Resolution is 16 bits with the per-count figures quoted per range: 343 µV on ±10.5 V, 171 µV on 0...10.5 V, 86 µV on 0...5.25 V and 0.34 µA on 0...21 mA. The overrange indication means a transmitter driven past its span is reported rather than clipped.
The reason to buy this module is the barrier: 250 V continuous basic insulation between the input channels as well as from the channels to the backplane, routine tested at 1350 V AC for 2 seconds. Six transmitters on six different supplies, or six grounded thermocouples at different potentials, can share one module without a common path.
Published limits worth knowing before specifying: calibrated accuracy better than 0.1 % of range with a 6-month calibration interval, module error 0.54 % of range, input impedance above 10 MΩ in voltage mode and 249 Ω in current mode, and overvoltage protection of 120 V AC/DC on voltage inputs against 8 V AC/DC on current inputs. Technical data 1756-TD002, user manual 1756-UM009, installation instructions 1756-IN063.
1756-IF4FXOF2F |
4 high-speed differential inputs + 2 outputs, 375 mA, reinforced isolation |
In stock |
1756-IF6CIS |
6 isolated current inputs with sourcing 24 V DC loop supply |
In stock |
1756-IF6I |
6 isolated inputs, 16-bit, 250 mA, channel-to-channel basic isolation |
In stock |
1756-IF8 |
8 single-ended / 4 differential inputs, 200 mA, 250 V basic to backplane |
In stock |
1756-IF8H |
8 differential HART current inputs, A and B series |
In stock |
1756-IF16 |
16 single-ended / 8 differential inputs, 200 mA, 15 Hz bandwidth |
In stock |
1756-IF16H |
16 differential HART current inputs, A and B series |
In stock |
1756-IRT8I |
8 isolated RTD and thermocouple inputs, 24-bit, 1756-CJC required |
In stock |
1756-IR6I |
6 isolated RTD inputs, 20-pin block, discontinued 2017 |
In stock |
1756-IT6I |
6 thermocouple inputs, two mV ranges, one CJC sensor |
In stock |
1756-IT6I2 |
6 isolated thermocouple inputs, 16-bit, two CJC sensors |
In stock |
Application |
Analog input |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-IF6I |
Communication |
Backplane (producer/consumer) |
Display |
— |
Enclosure |
None (open-style) |
Interface |
Removable terminal block |
Mounting |
Chassis slot |
Number Of Channels |
6 |
Standard |
CE, UL, CSA, RCM |
Sub Brand |
ControlLogix |
Type |
Analog Input Module |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN063 (analog I/O installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The IF6I is the module for panels where the transmitters do not share a supply: a retrofit tying a new skid into an existing line, a laboratory or test stand with instruments on their own isolated outputs, or a plant where each supplier's cabinet keeps its own 24 V rail.
It is also the correct choice for grounded thermocouples at different potentials when a dedicated thermocouple module is not wanted, because the channel-to-channel barrier removes the circulating-current path that a common-referenced module creates.
The trade is resolution and accuracy against isolation: 16 bits and 0.54 % module error here, against 24 bits and a reinforced barrier on the IF8I. Choose on which of the two the loop actually depends.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | Calibration every 6 months | The published calibration interval is 6 months, shorter than the 12 months on the non-isolated family. A plant calibration policy has to match it. |
| Check 3 | 0.54 % module error | The widest error figure in the analog range, and the price of per-channel isolation. A 0.1 % loop cannot be built on this module without trimming. |
| Check 4 | Current inputs tolerate 8 V AC/DC | Voltage inputs tolerate 120 V AC/DC. A 24 V source mis-applied to a current channel is outside the protected range. |
| Check 5 | 20-pin terminal block | 1756-TBNH or 1756-TBSH, ordered separately; the six channels use 20 terminals with returns. |
Specifications per Rockwell publication 1756-TD002 (ControlLogix I/O Modules Specifications); module behaviour per 1756-UM009 and 1756-IN050.
The non-isolated 8-channel module is 1756-IF8 at 200 mA backplane and 250 V basic to the backplane only; the 1756-IF16 doubles the count at the same backplane figure.
The 24-bit isolated module is 1756-IF8I: 250 V reinforced to the backplane, 250 V basic input-to-input, 200 mA at 5.1 V DC.
For current loops that need loop power from the module, 1756-IF6CIS supplies 24 V DC per channel for 2-wire transmitters.
What is the 1756-IF6I?
A 6-channel isolated analog input module for the ControlLogix chassis, 16-bit resolution, ±10.5 V and 0...21 mA ranges.
What is the backplane current?
250 mA at 5.1 V DC and 100 mA at 24 V DC, 3.7 W total backplane power (1756-TD002).
What isolation does it provide?
250 V continuous basic insulation between input channels and from channels to the backplane, routine tested at 1350 V AC for 2 seconds.
What resolution per range?
343 µV per bit on ±10.5 V, 171 µV on 0...10.5 V, 86 µV on 0...5.25 V and 0.34 µA on 0...21 mA.
How accurate is it?
Better than 0.1 % of range immediately after calibration, with 0.54 % module error over the temperature range and a 6-month calibration interval.
What is the input impedance?
Above 10 MΩ in voltage mode and 249 Ω in current mode.
Why does it cost backplane current?
Per-channel isolation is separate circuitry for each input, which is why 250 mA is drawn against 200 mA for eight non-isolated channels on the IF8.
Which terminal block fits?
1756-TBNH or 1756-TBSH, ordered separately, with a T4A North American and T4 IEC temperature code.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-IF6I. Values re-checked 15 November 2026.