Product Details:
Payment & Shipping Terms:
|
1746-FIO4V is the 4 Point Fast Analog Voltage Combination Module in the Allen-Bradley SLC 500 range: SLC 500 fast analog combination module, 2 inputs and 2 voltage outputs.
It occupies one I/O slot, takes both backplane rails, and is configured channel by channel from the processor; the ranges, resolution and filter settings below are the ones a project engineer needs before the loop is designed.
| 1746-FIO4I | 4 Point Fast Analog Current Combination Module | IN STOCK |
| 1746-FIO4V | 4 Point Fast Analog Voltage Combination Module | IN STOCK |
Application |
SLC 500 fast analog combination module, 2 inputs and 2 voltage outputs |
Cat Num |
1746-FIO4V |
Brand Name |
Rockwell |
Product Type |
4 Point Fast Analog Voltage Combination Module |
Channels |
2 inputs + 2 voltage outputs |
Input range |
2 differential inputs, voltage or current selectable per channel |
Output range |
2 voltage outputs, ±10V dc -1 LSB |
Resolution |
12-bit input, 14-bit output at 1.22070 mV/LSB |
Backplane current, 5V DC |
55 mA |
Backplane current, 24V DC |
120 mA |
Update time / filtering |
Successive approximation, 7 kHz bandwidth, 100 µs step response |
Isolation |
500V dc field wiring to backplane |
Lifecycle |
Discontinued |
Discontinued date |
Not published (Rockwell product page retired) |
Replacement category |
Engineering Replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN008 (module specifications) and 1747-UM011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Official Rockwell description: SLC 500 fast analog combination module, 2 inputs and 2 voltage outputs.
4 Point Fast Analog Voltage Combination Module with 2 inputs + 2 voltage outputs.
Application: SLC 500 fast analog combination module, 2 inputs and 2 voltage outputs.
Cat Num: 1746-FIO4V.
Brand Name: Rockwell.
Product Type: 4 Point Fast Analog Voltage Combination Module.
Channels: 2 inputs + 2 voltage outputs.
Input range: 2 differential inputs, voltage or current selectable per channel.
Output range: 2 voltage outputs, ±10V dc -1 LSB.
Resolution: 12-bit input, 14-bit output at 1.22070 mV/LSB.
Backplane current, 5V DC: 55 mA.
Backplane current, 24V DC: 120 mA.
Update time / filtering: Successive approximation, 7 kHz bandwidth, 100 µs step response.
Isolation: 500V dc field wiring to backplane.
Lifecycle: Discontinued.
Discontinued date: Not published (Rockwell product page retired).
Replacement category: Engineering Replacement.
These fast modules trade resolution for speed: 12-bit input with a 7 kHz bandwidth and a 100 µs step response, against 16-bit and a 10 Hz bandwidth on the standard 4-channel cards.
A fast input needs a well grounded and shielded transducer, because the wideband front end passes the noise that the standard card's filter removes.
They are combination modules, 2 inputs and 2 outputs, and are aimed at pressure or position loops in a press or a molding machine rather than at slow process temperatures.
Rockwell lists 1746-FIO4V as Discontinued, discontinued date Not published (Rockwell product page retired), replacement category Engineering Replacement.
No replacement catalog number is printed on the Rockwell page, so the route is an engineering substitution with a re-ranged analogue front end, not a part-for-part swap.
Rockwell's migration guidance for Bulletin 1746 routes analog points to Compact 5000 analog modules with a Logix controller; machines that stay on SLC 500 are supported from the secondary market.
The terminal block, the slot address and the module ID code stay the same when a card is replaced by the same catalog number, which is why the original number still has a place in a maintenance spares list after the end of sale.
A modular SLC 500 reserves slot 0 for the processor or the adapter, so this module goes in any other I/O slot; the current drawn from 5V dc and 24V dc both count against the chassis supply.
The analog front end is factory calibrated and, on the newer cards, autocalibrates at power-up and on channel enable, so an accuracy figure quoted at 25 °C is what the card delivers without a field trim.
Isolation is 500V dc field wiring to backplane between the field terminals and the backplane; that figure, not the channel count, is what decides whether a card can sit next to a drive with a noisy earth.
The card in red in the catalogue table at the top of this page is the one described here.
What is 1746-FIO4V?
SLC 500 fast analog combination module, 2 inputs and 2 voltage outputs. 4 Point Fast Analog Voltage Combination Module.
How many channels does 1746-FIO4V have?
2 inputs + 2 voltage outputs.
What ranges does 1746-FIO4V accept?
Inputs: 2 differential inputs, voltage or current selectable per channel. Outputs: 2 voltage outputs, ±10V dc -1 LSB.
How much backplane current does 1746-FIO4V draw?
55 mA at 5V dc and 120 mA at 24V dc.
Is 1746-FIO4V still available?
Rockwell lists it as Discontinued, discontinued date Not published (Rockwell product page retired), replacement category Engineering Replacement.
Analog modules are the expensive ones on an SLC backplane: one 8-channel input can draw more 5 V current than six digital modules. The table below prints channels, range, resolution and both backplane currents for the modules of the same analog group, so a rack can be sized on current rather than on the channel count in a quotation.
| Catalog | Channels | Range printed | Resolution | 5 V backplane | 24 V backplane | Update |
| 1746-FIO4I | 2 inputs + 2 current outputs | 2 differential inputs, voltage or current selectable per channel | 12-bit input, 13-bit output at 2.56348 µA/LSB | 55 mA | 150 mA | Successive approximation, 7 kHz bandwidth, 100 µs step response |
| 1746-FIO4V | 2 inputs + 2 voltage outputs | 2 differential inputs, voltage or current selectable per channel | 12-bit input, 14-bit output at 1.22070 mV/LSB | 55 mA | 120 mA | Successive approximation, 7 kHz bandwidth, 100 µs step response |
Where this module sits: What the rack feels is the backplane current, not the channel count: 1746-FIO4V is 55 mA at 5 V and 120 mA at 24 V. Added up, on the 5 A 1746-P2 the 5 V rail carries 90 and the 24 V rail carries 8, so the 24 V rail binds first at 8 modules, and that is below the thirteen slots of an A13.
Two things this block does not answer. It gives the module current, not the surge a rack sees at power-up, which is printed separately as inrush for the supply and not per module. And it says nothing about the 24 V field supply drawn by the loads themselves - the 24 V backplane figure is what the module takes from the rack, not what the sensors and coils take from the field supply.
Source: Rockwell 1746-IN027 digital I/O specification rows, 1746-IN008 and 1746-UM007 analog rows, 1746-IN016/IN004 chassis and supply rows. Backplane currents are quoted as printed; only the "how many fit" divisions are arithmetic, and they are integer divisions of the printed capacity.
This part sits in the Allen-Bradley SLC 500 1746 I/O modules category, with the other models and spare parts listed alongside it.