Product Details:
Payment & Shipping Terms:
|
1746-FIO4V is the 4 Point Fast Analog Voltage Combination Module in the Allen-Bradley SLC 500 range: SLC 500 fast analog combination module, 2 inputs and 2 voltage outputs.
It occupies one I/O slot, takes both backplane rails, and is configured channel by channel from the processor; the ranges, resolution and filter settings below are the ones a project engineer needs before the loop is designed.
| 1746-FIO4I | 4 Point Fast Analog Current Combination Module | IN STOCK |
| 1746-FIO4V | 4 Point Fast Analog Voltage Combination Module | IN STOCK |
Application |
SLC 500 fast analog combination module, 2 inputs and 2 voltage outputs |
Cat Num |
1746-FIO4V |
Brand Name |
Rockwell |
Product Type |
4 Point Fast Analog Voltage Combination Module |
Channels |
2 inputs + 2 voltage outputs |
Input range |
2 differential inputs, voltage or current selectable per channel |
Output range |
2 voltage outputs, ±10V dc -1 LSB |
Resolution |
12-bit input, 14-bit output at 1.22070 mV/LSB |
Backplane current, 5V DC |
55 mA |
Backplane current, 24V DC |
120 mA |
Update time / filtering |
Successive approximation, 7 kHz bandwidth, 100 µs step response |
Isolation |
500V dc field wiring to backplane |
Lifecycle |
Discontinued |
Discontinued date |
Not published (Rockwell product page retired) |
Replacement category |
Engineering Replacement |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1746-IN008 (module specifications) and 1747-UM011 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Official Rockwell description: SLC 500 fast analog combination module, 2 inputs and 2 voltage outputs.
4 Point Fast Analog Voltage Combination Module with 2 inputs + 2 voltage outputs.
Application: SLC 500 fast analog combination module, 2 inputs and 2 voltage outputs.
Cat Num: 1746-FIO4V.
Brand Name: Rockwell.
Product Type: 4 Point Fast Analog Voltage Combination Module.
Channels: 2 inputs + 2 voltage outputs.
Input range: 2 differential inputs, voltage or current selectable per channel.
Output range: 2 voltage outputs, ±10V dc -1 LSB.
Resolution: 12-bit input, 14-bit output at 1.22070 mV/LSB.
Backplane current, 5V DC: 55 mA.
Backplane current, 24V DC: 120 mA.
Update time / filtering: Successive approximation, 7 kHz bandwidth, 100 µs step response.
Isolation: 500V dc field wiring to backplane.
Lifecycle: Discontinued.
Discontinued date: Not published (Rockwell product page retired).
Replacement category: Engineering Replacement.
These fast modules trade resolution for speed: 12-bit input with a 7 kHz bandwidth and a 100 µs step response, against 16-bit and a 10 Hz bandwidth on the standard 4-channel cards.
A fast input needs a well grounded and shielded transducer, because the wideband front end passes the noise that the standard card's filter removes.
They are combination modules, 2 inputs and 2 outputs, and are aimed at pressure or position loops in a press or a molding machine rather than at slow process temperatures.
Rockwell lists 1746-FIO4V as Discontinued, discontinued date Not published (Rockwell product page retired), replacement category Engineering Replacement.
No replacement catalog number is printed on the Rockwell page, so the route is an engineering substitution with a re-ranged analogue front end, not a part-for-part swap.
Rockwell's migration guidance for Bulletin 1746 routes analog points to Compact 5000 analog modules with a Logix controller; machines that stay on SLC 500 are supported from the secondary market.
The terminal block, the slot address and the module ID code stay the same when a card is replaced by the same catalog number, which is why the original number still has a place in a maintenance spares list after the end of sale.
A modular SLC 500 reserves slot 0 for the processor or the adapter, so this module goes in any other I/O slot; the current drawn from 5V dc and 24V dc both count against the chassis supply.
The analog front end is factory calibrated and, on the newer cards, autocalibrates at power-up and on channel enable, so an accuracy figure quoted at 25 °C is what the card delivers without a field trim.
Isolation is 500V dc field wiring to backplane between the field terminals and the backplane; that figure, not the channel count, is what decides whether a card can sit next to a drive with a noisy earth.
The card in red in the catalogue table at the top of this page is the one described here.
What is 1746-FIO4V?
SLC 500 fast analog combination module, 2 inputs and 2 voltage outputs. 4 Point Fast Analog Voltage Combination Module.
How many channels does 1746-FIO4V have?
2 inputs + 2 voltage outputs.
What ranges does 1746-FIO4V accept?
Inputs: 2 differential inputs, voltage or current selectable per channel. Outputs: 2 voltage outputs, ±10V dc -1 LSB.
How much backplane current does 1746-FIO4V draw?
55 mA at 5V dc and 120 mA at 24V dc.
Is 1746-FIO4V still available?
Rockwell lists it as Discontinued, discontinued date Not published (Rockwell product page retired), replacement category Engineering Replacement.