Product Details:
Payment & Shipping Terms:
|
The 1794-TBNF puts a fuse in series with each output group: eight 5 x 20 mm fuses on a NEMA-style base, supplied with 1.6 A 250V AC slow-blow fuses.
It is the base for the 1794-OA8 AC output module, and the same base can be re-fused for the 1794-OM8 and 1794-OW8 when those outputs need individual protection.
| 1794-TB2 | 16-terminal cage clamp base, 2-wire, up to 132V AC | IN STOCK |
| 1794-TB3 | 16-terminal cage clamp base, 3-wire devices | IN STOCK |
| 1794-TB3S | 16-terminal spring clamp base, 3-wire devices | IN STOCK |
| 1794-TB32 | 32-terminal cage clamp base for 32-point modules | IN STOCK |
| 1794-TB32S | 32-terminal spring clamp base for 32-point modules | IN STOCK |
| 1794-TB3T | temperature base with two cold junction compensation sets | IN STOCK |
| 1794-TB3TS | spring clamp temperature base with CJC sets | IN STOCK |
| 1794-TB3G | grounded screw clamp base, 36 I/O, 10 chassis ground | IN STOCK |
| 1794-TB3GS | grounded spring clamp base, 36 I/O, 10 chassis ground | IN STOCK |
| 1794-TBKD | cage clamp base with 16 knife disconnects | IN STOCK |
| 1794-TBN | NEMA-style screw clamp base, up to 264V AC/DC | IN STOCK |
| 1794-TBNF | fused NEMA-style base, eight 5 x 20 mm fuses | IN STOCK |
| 1794-TB37DS | 37-pin D-shell termination for digital and analog modules | IN STOCK |
| 1794-TB62DS | 62-pin D-shell termination for digital and analog modules | IN STOCK |
Application |
FLEX I/O fused terminal base for AC output modules |
Cat Num |
1794-TBNF |
Brand Name |
Rockwell |
Termination |
Screw clamp, NEMA style, fused |
Fuses |
Eight 5 x 20 mm fuses, 1.6 A 250V AC slow-blow supplied |
Fuse alternatives |
Littelfuse 23901.6, Allen-Bradley 94171304, SAN-O SD6-1.6A |
Connections |
16 I/O, 2 common, 2 +V |
Voltage |
Up to 264V AC/DC |
Dimensions |
94 x 94 x 69 mm |
Operating temperature |
-20...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Eight 5 x 20 mm fuse holders, one per output group, on a 264V AC/DC NEMA base.
Supplied with 1.6 A 250V AC slow-blow fuses, identified in the guide as Littelfuse 23901.6, Allen-Bradley 94171304 and SAN-O SD6-1.6A.
Slow-blow is deliberate; an AC output driving a contactor draws an inrush that a fast fuse would not survive.
The fuse is replaceable without rewiring the field circuit, which is the reason to put it in the base rather than a separate holder.
1794-OA8 AC outputs as the primary application, eight points protected by eight fuses.
1794-OM8 and 1794-OW8 can use the base with the fuse rating changed for the load.
16 I/O, 2 common, 2 +V terminals, so it is an output-side base rather than a general purpose one.
-20...55 deg C — narrower than the plain NEMA base's 70 deg C.
Fuse rating follows the load, not the module; the 1.6 A shipped value suits small AC loads only.
Check the total per group against the module's per-point and per-module limits.
The 1794-TBN is the unfused 264V base when the circuit is already protected upstream.
Not a DC base substitute if the module's wiring pattern differs.
35 x 7.5 mm DIN rail with 25 mm air space.
Zinc-plated, yellow-chromated steel rail for chassis grounding.
1794-NM1 panel kit for panel mounting.
One end cap per system and bases plugging together for the backplane.
AC output islands that need per-point protection at the termination.
Retrofit panels where adding external fuse holders is not practical.
Not for high inrush loads beyond the fuse's slow-blow tolerance.
Not for analog modules; the fused holder occupies the output wiring path.
How many fuses does the 1794-TBNF hold?
Eight 5 x 20 mm fuses, one per output group.
What fuse is supplied?
1.6 A 250V AC slow-blow: Littelfuse 23901.6, Allen-Bradley 94171304 or SAN-O SD6-1.6A.
Which module is it intended for?
The 1794-OA8 AC output module; the OM8 and OW8 can use it with a suitable fuse rating.
What voltage is the base rated for?
Up to 264V AC/DC at the terminals.
What is the operating temperature?
-20...55 deg C.
Can the fuse rating be changed?
Yes; select it for the load, not the module.
1794-TBNF is a FLEX I/O terminal base unit, not an I/O module. It is the part that carries the field terminals, plugs into the adjacent base to form the backplane, and holds the module on top. The termination type here is Screw clamp, NEMA style, fused with 16 I/O, 2 common, 2 +V.
| Attribute | Value |
| Catalog number | 1794-TBNF |
| Termination type | Screw clamp, NEMA style, fused |
| Connections | 16 I/O, 2 common, 2 +V |
| Current capacity, maximum | module dependent |
| Wiring category | module dependent |
| Field voltage | 264V AC / DC |
| Operating temperature | -20...+70 C |
| Purpose in the range | A NEMA style screw clamp base fitted with fusing on the field side. |
The conductor range for this base is 0.34 to 3.3 mm2 (22 to 12 AWG) solid or stranded copper rated 75 C or greater, with 1.2 mm maximum insulation, with a maximum current capacity of module dependent across the base. Those figures are the base rating and not the module rating: a 16 point module on a 10 A base is still limited by the module output current per channel.
Selecting a base is a compatibility step, not a preference step. The module data sheet names the bases that are permitted for it, and a base outside that list may key differently, may not carry the required common and voltage terminals, or may not be rated for the field voltage of the module.
FLEX I/O is a backplane-free architecture: the terminal base unit snaps onto the DIN rail to the right of the adapter and the bases plug together to form the backplane. The module then sits on top of the base, so the base is chosen for the field wiring and the module for the signal, and the two are ordered separately.
For a retrofit into an existing slice, the addressing is decided by position rather than by catalog number: FLEX I/O assigns the module its place in the rack by the order of the bases on the rail, so inserting a module in the middle shifts the addresses of everything to its right and requires the program to be re-checked.
FLEX I/O bases and modules are separate line items on a purchase order, and the price of getting that wrong is a second shipment: a module without its base cannot be installed, and a base of the wrong termination type cannot be reworked in the field because the module keys to the base family.
Mounting is a DIN rail operation on both parts and the order of assembly is base first, module second: the base slides onto the rail, its backplane fingers engage the neighbouring base, and the module is then pressed onto the base and secured. Removing a module does not break the backplane, which is why a failed slice can be swapped without rewiring the row.
The 22 to 12 AWG acceptance range on the standard bases is wider than the field device terminals in most panels, so the practical constraint is usually the device end, not the base end. Where a 24V DC sensor cable is 18 AWG and the base accepts 12 AWG, the conductor still has to be torqued to the published value rather than to feel.
Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley Flex I/O 1794 modules category.