Product Details:
Payment & Shipping Terms:
|
The 1794-TB62DS is the 62-pin D-shell base, for modules whose field connections exceed what a 37-pin connector carries.
Like the 1794-TB37DS it serves digital and analog modules, and like it, it trades point-level access for a single pluggable cable.
| 1794-TB2 | 16-terminal cage clamp base, 2-wire, up to 132V AC | IN STOCK |
| 1794-TB3 | 16-terminal cage clamp base, 3-wire devices | IN STOCK |
| 1794-TB3S | 16-terminal spring clamp base, 3-wire devices | IN STOCK |
| 1794-TB32 | 32-terminal cage clamp base for 32-point modules | IN STOCK |
| 1794-TB32S | 32-terminal spring clamp base for 32-point modules | IN STOCK |
| 1794-TB3T | temperature base with two cold junction compensation sets | IN STOCK |
| 1794-TB3TS | spring clamp temperature base with CJC sets | IN STOCK |
| 1794-TB3G | grounded screw clamp base, 36 I/O, 10 chassis ground | IN STOCK |
| 1794-TB3GS | grounded spring clamp base, 36 I/O, 10 chassis ground | IN STOCK |
| 1794-TBKD | cage clamp base with 16 knife disconnects | IN STOCK |
| 1794-TBN | NEMA-style screw clamp base, up to 264V AC/DC | IN STOCK |
| 1794-TBNF | fused NEMA-style base, eight 5 x 20 mm fuses | IN STOCK |
| 1794-TB37DS | 37-pin D-shell termination for digital and analog modules | IN STOCK |
| 1794-TB62DS | 62-pin D-shell termination for digital and analog modules | IN STOCK |
Application |
FLEX I/O D-shell termination base, digital and analog |
Cat Num |
1794-TB62DS |
Brand Name |
Rockwell |
Termination |
62-pin D-shell connector |
Used with |
Digital and analog modules |
Dimensions |
94 x 94 x 69 mm; 127 x 94 x 69 mm with an extended module |
Operating temperature |
0...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
62-pin D-shell connector, 25 more pins than the 1794-TB37DS.
Digital and analog modules, the same application range as the 37-pin base.
94 x 94 x 69 mm, or 127 x 94 x 69 mm with an extended module installed.
0...55 deg C operating range.
Pin count follows the module's field terminal requirement, so the module datasheet decides between 37 and 62.
One pre-made cable per module, built and tested away from the panel.
Cable replacement restores all points at once, which shortens a recovery but widens a fault.
Breakout boxes are needed for point-level measurement.
High terminal count modules in harness-wired panels.
Machine builders shipping pre-wired assemblies, with digital and analog on the same connector style.
Not for high-voltage field circuits; the connector is for module-level signals.
Not the 37-pin variant; check the module's terminal count first.
35 x 7.5 mm DIN rail with 25 mm air space.
Zinc-plated, yellow-chromated steel rail for the chassis path.
1794-NM1 panel kit where rail is unavailable.
One end cap per system; bases plug together to form the backplane.
Panel shops with harness capability, where the labour saving is real.
Modules with more field terminals than a 37-pin connector carries.
Not for retrofit wiring, where the existing terminations are screw type.
Not for outdoor cabinets; 0...55 deg C only.
What connector does the 1794-TB62DS use?
A 62-pin D-shell connector.
Which modules use it?
Digital and analog FLEX I/O modules that need the higher pin count.
What are its dimensions?
94 x 94 x 69 mm, or 127 x 94 x 69 mm with an extended module.
What is the operating temperature?
0...55 deg C.
How do I choose between the 37-pin and 62-pin base?
By the module's field terminal count.
Can I probe individual points at the base?
No; a breakout is needed.
1794-TB62DS is a FLEX I/O terminal base unit, not an I/O module. It is the part that carries the field terminals, plugs into the adjacent base to form the backplane, and holds the module on top. The termination type here is D-shell, 62 pin with per module pinout.
| Attribute | Value |
| Catalog number | 1794-TB62DS |
| Termination type | D-shell, 62 pin |
| Connections | per module pinout |
| Current capacity, maximum | 10 A |
| Wiring category | 2 |
| Field voltage | Per module |
| Operating temperature | -20...+70 C |
| Purpose in the range | A 62 pin D-shell base in the same 127 by 94 by 69 mm envelope, used for pre-wired cable interfaces. |
The conductor range for this base is 0.34 to 3.3 mm2 (22 to 12 AWG) solid or stranded copper rated 75 C or greater, with 1.2 mm maximum insulation, with a maximum current capacity of 10 A across the base. Those figures are the base rating and not the module rating: a 16 point module on a 10 A base is still limited by the module output current per channel.
Selecting a base is a compatibility step, not a preference step. The module data sheet names the bases that are permitted for it, and a base outside that list may key differently, may not carry the required common and voltage terminals, or may not be rated for the field voltage of the module.
The wiring category matters as much as the gauge: category 2 bases are the general field wiring class, while grounded bases in the 1794-TB3G family carry 10 chassis ground terminals for analog and temperature modules where a separate signal common is needed.
FLEX I/O bases and modules are separate line items on a purchase order, and the price of getting that wrong is a second shipment: a module without its base cannot be installed, and a base of the wrong termination type cannot be reworked in the field because the module keys to the base family.
For a retrofit into an existing slice, the addressing is decided by position rather than by catalog number: FLEX I/O assigns the module its place in the rack by the order of the bases on the rail, so inserting a module in the middle shifts the addresses of everything to its right and requires the program to be re-checked.
The 22 to 12 AWG acceptance range on the standard bases is wider than the field device terminals in most panels, so the practical constraint is usually the device end, not the base end. Where a 24V DC sensor cable is 18 AWG and the base accepts 12 AWG, the conductor still has to be torqued to the published value rather than to feel.
Conformal coating on a K suffix base is applied to the assembled board and not to the terminals, so the coating protects the electronics against condensation while the field terminals remain serviceable. That is the point of ordering the coated base instead of sealing the whole enclosure.
Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.
The Allen-Bradley Flex I/O 1794 modules category groups the other catalog numbers, options and spare parts in the same range.