logo
Home ProductsAB FlexLogix I/O 1794

Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK

Customer Reviews
Welcome to PLC-VIP , Your online shop for Allen Bradley & Siemens PLC parts.

—— PLC-VIP.SHOP

We also wish to be able to continue doing good business with you and your company in the years to come. We are very thankful for that.

—— Rodrigo

I'm Online Chat Now

Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK

China Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK supplier
Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK supplier Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK supplier Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK supplier Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK supplier Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK supplier Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK supplier Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK supplier Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK supplier Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK supplier Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK supplier Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK supplier Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK supplier

Large Image :  Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK

Product Details:

Place of Origin: Made in MALAYSIA
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1794-TB3TSK / 1794TB3TSK

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $108.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 10 PCS
Detailed Product Description

1794-TB3TSK technical data PDF download FLEX I/O 1794-TB3TSK / 1794TB3TSK Coated Spring Temperature Base

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: PLC I/O

The 1794-TB3TSK is the coated spring clamp temperature base: 16 I/O points, two cold junction compensation sets, eight chassis ground terminals and a conformal coating for condensing or corrosive air.

The CJC sets are the reason this base exists — a 1794-IRT8 or 1794-IT8 in thermocouple mode needs a reference junction at the terminals, not on the module.

1794-TB2 16-terminal cage clamp base, 2-wire, up to 132V AC IN STOCK
1794-TB3 16-terminal cage clamp base, 3-wire devices IN STOCK
1794-TB3S 16-terminal spring clamp base, 3-wire devices IN STOCK
1794-TB32 32-terminal cage clamp base for 32-point modules IN STOCK
1794-TB32S 32-terminal spring clamp base for 32-point modules IN STOCK
1794-TB3T temperature base with two cold junction compensation sets IN STOCK
1794-TB3TS spring clamp temperature base with CJC sets IN STOCK
1794-TB3G grounded screw clamp base, 36 I/O, 10 chassis ground IN STOCK
1794-TB3GS grounded spring clamp base, 36 I/O, 10 chassis ground IN STOCK
1794-TBKD cage clamp base with 16 knife disconnects IN STOCK
1794-TBN NEMA-style screw clamp base, up to 264V AC/DC IN STOCK
1794-TBNF fused NEMA-style base, eight 5 x 20 mm fuses IN STOCK
1794-TB37DS 37-pin D-shell termination for digital and analog modules IN STOCK
1794-TB62DS 62-pin D-shell termination for digital and analog modules IN STOCK

Product Specifications 1794-TB3TSK (PDF)
 Application
 FLEX I/O temperature terminal base, coated
 Cat Num
 1794-TB3TSK
 Brand Name
 Rockwell
 Termination type
 Spring clamp, temperature
 Connections
 16 I/O; 10 common; 4 +V; 8 chassis ground; 2 CJC sets
 Maximum voltage
 132V AC / 156V DC
 Current capacity, max
 10 A
 Coating
 Conformal coated
 Operature temperature
 -20...70 deg C
 Dimensions
 94 x 94 x 69 mm

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1794-TB3TSK original product photograph, wide view 1794-TB3TSK original product photograph, wide view 1794-TB3TSK original product photograph, wide view

Terminal layout

16 I/O, 10 common, 4 +V, 8 chassis ground, plus two sets of cold junction compensation for temperature modules.

The 8 chassis ground terminals are what separate this base from the plain 1794-TB3S.

<Rated to 132V AC / 156V DC, the standard TB3 voltage ceiling.

Spring clamp termination for faster wiring than the cage clamp 1794-TB3TK.

Coating and rating

Conformal coating to ANSI/ISA-S71.04 Class G1, G2 and G3, plus the CEI, UL 746E and MIL-1-46058C references the selection guide lists.

-20...70 deg C operating range, the same as the uncoated temperature bases.

10 A current capacity and 0.34...3.3 mm2 (22...12 AWG) wire, 75 deg C rating minimum.

94 x 94 x 69 mm, which keeps the DIN rail footprint unchanged from the rest of the family.

Which modules use it

1794-IT8 and 1794-IRT8 in thermocouple mode are the documented residents.

The 8 chassis ground terminals also serve the 1794-IR8 and analog modules.

The uncoated 1794-TB3TS is the same base without the coating.

The 1794-TB3TK is the cage clamp coated alternative.

Application

Thermocouple loops in washdown or coastal cabinets, where the coating earns its place.

Panels that already use the 1794-IRT8 and need a coated spare base.

Not for 32-point modules; those need the 32-terminal pattern.

Not for 264V AC modules; the NEMA bases carry that.

Where it fits

Coated temperature islands.

Spare-part strategy where one base type covers TC and RTD work.

Not the D-shell option.

Not for high-voltage AC I/O.

FAQ — 1794-TB3TSK

What is the 1794-TB3TSK?

A conformally coated spring clamp temperature terminal base with two CJC sets.

How many terminals does it have?

16 I/O, 10 common, 4 +V, 8 chassis ground.

What voltage is it rated for?

Up to 132V AC or 156V DC.

Which modules use it?

1794-IT8 and 1794-IRT8 in thermocouple mode, and analog modules needing chassis ground.

What coating standard applies?

ANSI/ISA-S71.04 Class G1, G2 and G3 environments.

What is the operating temperature?

-20...70 deg C.


Data sources. Technical values on this page come from Rockwell publication 1794-SG002 (FLEX I/O Selection Guide, terminal base comparison). Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Related numbers

Where the 1794-TB3TSK sits in the FLEX I/O range

1794-TB3TSK is a FLEX I/O terminal base unit, not an I/O module. It is the part that carries the field terminals, plugs into the adjacent base to form the backplane, and holds the module on top. The termination type here is Spring clamp, temperature with 16 I/O, 10 common, 4 +V, 8 chassis ground, 2 sets of CJC.

AttributeValue
Catalog number1794-TB3TSK
Termination typeSpring clamp, temperature
Connections16 I/O, 10 common, 4 +V, 8 chassis ground, 2 sets of CJC
Current capacity, maximum10 A
Wiring category2
Field voltageUp to 132V AC / 156V DC
Operating temperature-20...+70 C
Purpose in the rangeThe conformal coated version of the 1794-TB3TS.

The conductor range for this base is 0.34 to 3.3 mm2 (22 to 12 AWG) solid or stranded copper rated 75 C or greater, with 1.2 mm maximum insulation, with a maximum current capacity of 10 A across the base. Those figures are the base rating and not the module rating: a 16 point module on a 10 A base is still limited by the module output current per channel.

Selecting a base is a compatibility step, not a preference step. The module data sheet names the bases that are permitted for it, and a base outside that list may key differently, may not carry the required common and voltage terminals, or may not be rated for the field voltage of the module.

Conformal coated variants carry a K suffix and exist because the same base can be asked to survive washdown, condensate, or corrosive atmosphere. Ordering the uncoated base and treating it in the field is not equivalent and does not carry the same published rating.

FLEX I/O bases and modules are separate line items on a purchase order, and the price of getting that wrong is a second shipment: a module without its base cannot be installed, and a base of the wrong termination type cannot be reworked in the field because the module keys to the base family.

For a retrofit into an existing slice, the addressing is decided by position rather than by catalog number: FLEX I/O assigns the module its place in the rack by the order of the bases on the rail, so inserting a module in the middle shifts the addresses of everything to its right and requires the program to be re-checked.

On the 32 point bases the common and voltage terminals are grouped in eight pairs rather than eighteen, which is why the 32 point digital modules can mix sinking and sourcing groups in one slice and why the terminal numbering on the drawing does not follow the 16 point pattern.

Any FLEX I/O position is a pair on the purchase order: one base, one module. Stocking modules without bases, or bases without the matching modules, produces a slice that cannot be commissioned, and the two part numbers are never interchangeable across the 8, 16 and 32 point families.

Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.

Other catalog numbers and accessories for the same range are collected in the Allen-Bradley Flex I/O 1794 modules category.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)