The 1794-IV32 puts 32 sourcing inputs in one module, on a 1794-TB32 base with two groups of 16 channels.
Two groups mean two separate +V1 and +V2 feeds, so one group can be isolated for maintenance without dropping the other.
| 1794-IB8 | 8-point 24V DC sinking input module | IN STOCK |
| 1794-IB16 | 16-point 24V DC sinking input module | IN STOCK |
| 1794-IB32 | 32-point 24V DC sinking input module | IN STOCK |
| 1794-IB10XOB6 | 10 inputs / 6 sourcing outputs, 24V DC combo module | IN STOCK |
| 1794-IB16XOB16P | 16 inputs / 16 protected sourcing outputs combo module | IN STOCK |
| 1794-IB16D | 16-point diagnostic sinking input module | IN STOCK |
| 1794-IB16XT | 16-point 24V DC sinking input, extended temperature | IN STOCK |
| 1794-IB10XOB6XT | 10 inputs / 6 sourcing outputs, extended temperature | IN STOCK |
| 1794-IA8 | 8-point 120V AC input module | IN STOCK |
| 1794-IA16 | 16-point 120V AC input module | IN STOCK |
| 1794-IC16 | 16-point 48V DC sinking input module | IN STOCK |
| 1794-IG16 | 16-point 5V DC TTL input module | IN STOCK |
| 1794-IH16 | 16-point 125V DC sinking input module | IN STOCK |
| 1794-IM8 | 8-point 240V AC input module | IN STOCK |
| 1794-IM16 | 16-point 240V AC input module | IN STOCK |
| 1794-IV16 | 16-point 24V DC sourcing input module | IN STOCK |
| 1794-IV32 | 32-point 24V DC sourcing input module | IN STOCK |
Application |
FLEX I/O 24V DC sourcing input, 32 points |
Cat Num |
1794-IV32 |
Brand Name |
Rockwell |
Number of inputs |
32, current, sourcing |
On-state voltage |
19.2V DC min, 24V DC nom, 31.2V DC max |
On-state current |
2.0 mA min, 4.1 mA @ 24V, 6.0 mA max |
Off-state voltage, max |
5V DC |
Input impedance |
6 k ohm |
Isolation |
type tested 850V DC for 60 s |
External supply |
19.2...31.2V DC |
Terminal base |
1794-TB32, 1794-TB32S, 1794-TB62DS |
Operating temperature |
0...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
19.2...31.2V DC on-state, 4.1 mA at 24V nominal, 2.0 mA minimum and 6.0 mA maximum.
Off-state below 5V DC, 1.5 mA maximum, 6 k ohm input impedance.
32 sourcing inputs in two groups of 16, each with its own power and common pair.
Keyswitch position 2 and 32 field-side indicators.
Inputs 0...15 on A-0...A-15, with +V1 on C-35, C-37, C-39, C-41 and COM1 on C-36 to C-42.
<Inputs 16...31 on B-17...B-32, with +V2 on C-43 to C-49 and COM2 on C-44 to C-50.
Terminals 16, 33, 34 and 51 carry no connection on this module.
Daisy chain by jumpering C-41 to the next base's power, C-42 to its common, and likewise for group 2.
50V continuous isolation, type tested at 850V DC for 60 s, field side to system.
No channel-to-channel isolation, so the two groups share the module's reference.
0.25...32 ms selectable filter times for the 32 inputs.
<40 mA Flexbus at 5V, 6 W dissipation, 20.5 BTU/hr.
High point-count sourcing panels where 32 points save a slot and a base.
Machines split into two maintenance groups, each with its own 24V feed.
Not a sinking card; the 1794-IB32 is the sinking 32-point part.
Not for extended temperature; 0...55 deg C.
Dense sourcing input islands on a TB32 base.
Panels where 16-point cards would double the module count.
Not for the TB3 base; 32 points need the TB32 pattern.
Not for 48V DC; use the 1794-IC16 for that range.
How many inputs has the 1794-IV32?
32 sourcing inputs in two groups of 16.
What terminal base does it need?
1794-TB32, 1794-TB32S or 1794-TB62DS.
What is the on-state current?
4.1 mA at 24V DC, 2.0 to 6.0 mA.
What is the input impedance?
6 k ohm.
How are the two groups fed?
Separate +V1 and +V2 terminals with their own COM1 and COM2 returns.
What is the operating temperature?
0...55 deg C.
1794-IV32 is a digital DC input with 32 inputs in the FLEX I/O range, rated for 48V DC, sourcing. It mounts on the 1794-TB32, 1794-TB32S terminal base unit, which is ordered separately and is the part that actually carries the field terminals.
| Attribute | Value |
| Catalog number | 1794-IV32 |
| Module type | digital DC input |
| Points | 32 inputs |
| Electrical range | 48V DC, sourcing |
| Terminal base unit | 1794-TB32, 1794-TB32S |
| On-state current | 5 mA at 48V DC |
| Power dissipation | 6.4 W at 60V DC |
| Operating temperature | -20 to +55 C |
FLEX I/O is a backplane-free architecture: the terminal base unit snaps onto the DIN rail to the right of the adapter and the bases plug together to form the backplane. The module then sits on top of the base, so the base is chosen for the field wiring and the module for the signal, and the two are ordered separately.
One point about the 24V DC digital slices that catches panel builders: the adapter supplies the field power for the modules on its own 24V output, and that output is current limited. On a 1794-ADN the supply output is 450 mA at 24V, so a slice of 16 point DC modules can exhaust the adapter before the cabinet is half filled, and a separate field supply has to be introduced rather than assumed.
Temperature class is written per module and per base, and the lower of the two governs the slice. A 70 C base carrying a 55 C module is a 55 C slice, which is why the extended temperature modules exist as a matched set rather than as an upgrade to one part of the pair.
Mounting is a DIN rail operation on both parts and the order of assembly is base first, module second: the base slides onto the rail, its backplane fingers engage the neighbouring base, and the module is then pressed onto the base and secured. Removing a module does not break the backplane, which is why a failed slice can be swapped without rewiring the row.
The 22 to 12 AWG acceptance range on the standard bases is wider than the field device terminals in most panels, so the practical constraint is usually the device end, not the base end. Where a 24V DC sensor cable is 18 AWG and the base accepts 12 AWG, the conductor still has to be torqued to the published value rather than to feel.
Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.
Browse the Allen-Bradley Flex I/O 1794 modules category for the other models, options and spare parts that share this range.